Home›Repair guides›Cummins/Onan›Emergency Stop Reset

Cummins/Onan PCC 2100 — Emergency Stop Reset

Operation · Control panel emergency stop

For the Cummins/Onan PCC 2100, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan GGHE, Cummins/Onan GGHF, Cummins/Onan WSG-1068 engine

Before you start

  • Emergency Stop shutdown can be reset only at the PCC front panel.

Procedure

  1. Pull the emergency stop button out and allow it to pop out.
  2. Turn the O/Manual/Auto switch to O (Off).
  3. Press the front panel Fault Acknowledge/Reset button.
  4. Select Manual or Auto, as required.

Full service-parts list: Cummins/Onan GGHE →, Cummins/Onan GGHF →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →