Cummins/Onan PCC 2100 — Emergency Stop Reset
Operation · Control panel emergency stop
For the Cummins/Onan PCC 2100, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan GGHE, Cummins/Onan GGHF, Cummins/Onan WSG-1068 engine
Before you start
- Emergency Stop shutdown can be reset only at the PCC front panel.
Procedure
- Pull the emergency stop button out and allow it to pop out.
- Turn the O/Manual/Auto switch to O (Off).
- Press the front panel Fault Acknowledge/Reset button.
- Select Manual or Auto, as required.
Full service-parts list: Cummins/Onan GGHE →, Cummins/Onan GGHF →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.