Home›Repair guides›Cummins/Onan›P7 Generator Bearing Re-Lubrication

Cummins/Onan — P7 Generator Bearing Re-Lubrication

Maintenance

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFLB, Cummins/Onan DFLC, Cummins/Onan DFLE, Cummins/Onan DFM, Cummins/Onan KTA50 / KTTA50 engine, Cummins/Onan KTA50 engine, Cummins/Onan KTTA50 engine

Procedure

  1. Make sure grease gun nozzle and re-lubricating fitting are free from contaminants.
  2. With generator running, apply specified grease fill quantity through the grease fitting.
  3. Run generator a minimum of 10 minutes to allow excess grease to exhaust.
  4. Check inside the PMG cover for expelled grease and clean out as necessary.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 75 grams of Kluber type ASONIC GHY72
  • Re-lubrication period 4000-4500 hours

Full service-parts list: Cummins/Onan DFLB →, Cummins/Onan DFLC →, Cummins/Onan DFLE →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.