Cummins/Onan — Load Sharing Controls Troubleshoot Procedure

Testing & diagnosis

From a Cummins/Onan service manual covering: 1000DFHD-60 / 900DFHD-50, 750DFHA-60 / 620DFHA-50, 800DFHB-60 / 700DFHB-50, 900DFHC-60 / 800DFHC-50. Check it applies to your exact model before use.

Applies to: Cummins/Onan DFHA, Cummins/Onan DFHB, Cummins/Onan DFHC, Cummins/Onan DFHD, Cummins/Onan QST30 engine, Cummins/Onan QST30-G1 engine, Cummins/Onan QST30G2 engine, Cummins/Onan QST30-G3 engine, MTU QST30G3 engine

Procedure

  1. Measure bus voltage and frequency and generator set voltage and frequency with a true RMS digital meter; calibrate sensing circuits and match bus conditions.
  2. Check that the load sharing control wiring is properly connected.
  3. Check that each generator set in the system can carry its rated load.
  4. Fine adjust KW BALANCE and KVAR BALANCE settings under the paralleling setup menu.
  5. If sets share load approximately equally but load oscillates between them, reduce the governor gain.
  6. Consult factory for any other load sharing problems.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Load sharing should be within plus or minus 5%

Full service-parts list: Cummins/Onan DFHA →, Cummins/Onan DFHB →, Cummins/Onan DFHC →, Cummins/Onan DFHD →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.