Cummins/Onan — Insulation Resistance Testing

Maintenance · Generator windings

From a Cummins/Onan service manual covering: 1000DFHD-60 / 900DFHD-50, 750DFHA-60 / 620DFHA-50, 800DFHB-60 / 700DFHB-50, 900DFHC-60 / 800DFHC-50. Check it applies to your exact model before use.

Applies to: Cummins/Onan DFHA, Cummins/Onan DFHB, Cummins/Onan DFHC, Cummins/Onan DFHD, Cummins/Onan QST30 engine, Cummins/Onan QST30-G1 engine, Cummins/Onan QST30G2 engine, Cummins/Onan QST30-G3 engine, MTU QST30G3 engine

Procedure

  1. Disconnect plug J10 from the voltage regulator output stage module.
  2. Disconnect the AC control input leads (marked 5, 6, 7 and 8) from the generator output terminals.
  3. If the RTD option is installed, ground all six RTD temperature leads (18 leads total).
  4. Apply test potential between the winding and ground (winding laminations).
  5. Compare readings with Table 6-1; investigate and correct low readings before returning to service.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • P7 frame: main stator, main rotor, PMG, exciter stator 10.0-1.0 MEG at 500 VDC setting
  • HC6 frame: 5.0-1.0 MEG at 500 VDC setting

Full service-parts list: Cummins/Onan DFHA →, Cummins/Onan DFHB →, Cummins/Onan DFHC →, Cummins/Onan DFHD →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.