Cummins/Onan — Genset Reconnections

Adjustments · Generator

From a Cummins/Onan service manual covering: 3.3 KY, 3.3KY, 3.6 KY, 3.6KY, 4KY. Check it applies to your exact model before use.

Applies to: Cummins/Onan 3.6 KY, Cummins/Onan 3.6KY, Cummins/Onan 4KY

Before you start

  • Generator voltage is deadly

Procedure

  1. Remove control panel for access to generator leads and circuit breaker terminals.
  2. Reconnect generator leads in accordance with appropriate reconnection diagram.
  3. Check voltage after reconnections.
  4. Adjust no-load voltage with adjustment pot on control panel as necessary.

Full service-parts list: Cummins/Onan 3.6 KY →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.