Home›Repair guides›Cummins/Onan›Generator Set Inspection

Cummins/Onan — Generator Set Inspection

Maintenance

From a Cummins/Onan operator's manual covering: 5.0 MDKUB, 6.0 MDKUB, 7.5 MDKWB, 9.0 MDKWB. Check it applies to your exact model before use.

Applies to: Cummins/Onan 5.0 MDKUB, Cummins/Onan 6.0 MDKUB, Cummins/Onan 7.5 MDKWB, Cummins/Onan 9.0 MDKWB, Cummins/Onan MDKUB, Cummins/Onan MDKWB, Kubota Z482B engine, Kubota D722B engine

Before you start

  • Inhalation of exhaust gases can cause severe personal injury or death.
  • Fuel leakage will create a fire hazard.
  • Ignition of explosive battery gases can cause severe personal injury.

Procedure

  1. Inspect daily or after every 8 hours of operation.
  2. Check exhaust system for leaks; repair immediately.
  3. Check fuel system for leaks; replace worn fuel line components.
  4. Check DC electrical system: battery terminals clean and tight.
  5. Check mechanical condition: loose belts, fittings, leaking gaskets, hoses, damage.
  6. With genset running, check gauges: oil pressure 28-64 psi; coolant 165-195°F; DC voltmeter 14-15 volts.

Specs & values

  • Oil pressure 28 to 64 psi (294 to 543 kPa)
  • Coolant temperature 165° to 195°F (74° to 91°C)
  • DC voltmeter 14 to 15 volts on 12-volt Amazon eBay $11.99 FridayParts $65.01 system
  • Raw water discharge about 3 gal/min (11.4 liter/min)

Full service-parts list: Cummins/Onan 5.0 MDKUB →, Cummins/Onan 6.0 MDKUB →, Cummins/Onan 7.5 MDKWB →, Cummins/Onan 9.0 MDKWB →, Cummins/Onan MDKUB →, Cummins/Onan MDKWB →, Kubota Z482B engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.