Home›Repair guides›Cummins/Onan›Flash the exciter field

Cummins/Onan — Flash the exciter field

Repair & overhaul

From a Cummins/Onan service manual covering: 4A2.3, 6A3.4-GS, 6AT3.4-GS, DL4, DL6, QSA3, QSA4, QSA6. Check it applies to your exact model before use.

Applies to: Cummins/Onan DGAB, Cummins/Onan DGAC, Cummins/Onan DGAD, Cummins/Onan DGAE, Cummins/Onan DL4, Cummins/Onan DL6

Before you start

  • Incorrect flashing procedure can damage the voltage regulator.

Procedure

  1. Assemble 12-volt battery, 10-ampere fuse, momentary-on switch, and 12-ampere diode.
  2. Connect positive lead to voltage regulator terminal 9 and negative to terminal 10.
  3. Start genset and operate at normal speed.
  4. Close switch until output voltage builds, but not longer than five seconds.
  5. Check output voltage, shut down, restart, and verify voltage builds without flashing.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Do not keep excitation circuitry connected longer than five seconds.

Full service-parts list: Cummins/Onan DGAB →, Cummins/Onan DGAC →, Cummins/Onan DGAD →, Cummins/Onan DGAE →, Cummins/Onan DL6 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.