Specifications
| Fuel | gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Prime power | 175 kW |
| Oil capacity | 28.5 L |
| Alternator | 432CSL6210 |
| Voltage options | 240 V, 208 V, 480 V, 600 V |
| Phase | 3 |
| Rated current | 210 A |
| Power factor | 0.8 |
| Battery group | 4D |
| Battery cranking | 1050 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 149 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3607×1591×2026 mm |
| Dry weight | 3096 kg |
| Sound level | 86.3 dBA @ 7 m |
Engine
| Oil capacity | 28.5 L |
|---|---|
| Coolant capacity | 25.0 L |
| Displacement | 11.1 L |
| Aspiration | Turbo |
| Rated speed | 1800 rpm |
Common questions
What size generator is the MTU 6R0185 GS200?
The MTU 6R0185 GS200 is rated 200 kW standby (250.0 kVA).
What engine is in the MTU 6R0185 GS200?
The MTU 6R0185 GS200 is powered by the Power Solutions International 11.1L CAC engine.
Is the MTU 6R0185 GS200 diesel or gas?
The MTU 6R0185 GS200 runs on gas.
What is the oil capacity of the MTU 6R0185 GS200?
The Power Solutions International 11.1L CAC engine in the MTU 6R0185 GS200 has an oil capacity of 28.5 liters.
Which alternator is fitted to the MTU 6R0185 GS200?
The MTU 6R0185 GS200 uses a 432CSL6210 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |