Specifications
| Fuel | gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Prime power | 175 kW |
| Oil capacity | 28.5 L |
| Alternator | 432CSL6210 (4-pole) |
| Voltage options | 240 V, 208 V, 480 V, 600 V |
| Phase | 3 |
| Rated current | 210 A |
| Power factor | 0.8 |
| Battery group | 4D |
| Battery cranking | 1050 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 149 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3607×1591×2026 mm |
| Dry weight | 3096 kg |
| Sound level | 86.3 dBA @ 7 m |
Engine
| Oil capacity | 28.5 L |
|---|---|
| Coolant capacity | 25.0 L |
| Displacement | 11.1 L |
| Aspiration | Turbo |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe Power Solutions International 11.1L CAC in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Hipower | HNG 210 T6 |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the MTU 6R0185 GS200?
The MTU 6R0185 GS200 is rated 200 kW standby (250.0 kVA).
What engine is in the MTU 6R0185 GS200?
The MTU 6R0185 GS200 is powered by the Power Solutions International 11.1L CAC engine.
Is the MTU 6R0185 GS200 diesel or gas?
The MTU 6R0185 GS200 runs on gas.
What is the oil capacity of the MTU 6R0185 GS200?
The Power Solutions International 11.1L CAC engine in the MTU 6R0185 GS200 has an oil capacity of 28.5 liters.
What is the cooling system capacity of the MTU 6R0185 GS200?
The MTU 6R0185 GS200 cooling system holds 149 liters (39.4 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 6R0185 GS200?
The MTU 6R0185 GS200 is rated 175 kW prime (218 kVA), against 200 kW standby.
What is the sound level of the MTU 6R0185 GS200?
The MTU 6R0185 GS200 is rated at 86.3 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 6R0185 GS200 weigh?
The MTU 6R0185 GS200 has a dry weight of 3096 kg (6825 lb).
What voltage does the MTU 6R0185 GS200 produce?
The MTU 6R0185 GS200 is offered in 240 V, 208 V, 480 V, 600 V, 3-phase.
What size battery does the MTU 6R0185 GS200 need?
The MTU 6R0185 GS200 uses 2 batteryies, 24 V each, 1050 CCA, group 4D, per the manufacturer specification sheet.
Which alternator is fitted to the MTU 6R0185 GS200?
The MTU 6R0185 GS200 uses a 432CSL6210 alternator. It has 4 poles.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents