Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 1000 kW |
| Standby kVA | 1250 |
| Prime power | 900 kW |
| Emissions | Tier 2 |
| Controller | PowerCommand 3.3 |
| Oil capacity | 132.0 L |
| Alternator | Stamford/AvK HCI634J1 |
| Voltage options | 480 V |
| Phase | 3 |
| Rated current | 1504 A |
| Power factor | 0.8 |
| Battery cranking | 1425 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 201 L |
| Dimensions (L×W×H) | 9144×2438×4137 mm |
| Fuel tank | 3785.0 L |
Engine
| Oil capacity | 132.0 L |
|---|---|
| Coolant capacity | 79.0 L |
| Displacement | 30.5 L |
| Aspiration | Turbocharged, Aftercooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Cummins/Onan QST30-G5 NR2| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry | — | |||
| Fuel filter | 30 micron Racor ® fuel filter system | — | |||
| Oil filter | Full Pressure 4 Spin-on Full Flow | — | |||
| Battery | 24 VDC | — | |||
| Belt | Belt Driven, Centrifugal | — | |||
| Coolant filter | Not specified | — | |||
| Spark plug | Not specified | — |
Common questions
What is the power rating of the MQ Power CG1000C2?
The MQ Power CG1000C2 is rated 1000 kW standby (1250.0 kVA).
What engine does the MQ Power CG1000C2 use?
The MQ Power CG1000C2 is powered by the Cummins/Onan QST30-G5 NR2 engine.
What fuel does the MQ Power CG1000C2 use?
The MQ Power CG1000C2 runs on Diesel.
How much oil does the MQ Power CG1000C2 take?
The Cummins/Onan QST30-G5 NR2 engine in the MQ Power CG1000C2 has an oil capacity of 132.0 liters.
What alternator comes on the MQ Power CG1000C2?
The MQ Power CG1000C2 uses a Stamford/AvK HCI634J1 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 65.5 | 17.3 |
| Prime | 50% | 121.5 | 32.1 |
| Prime | 75% | 179.8 | 47.5 |
| Prime | 100% | 241.9 | 63.9 |
| Standby | 25% | 72.3 | 19.1 |
| Standby | 50% | 135.5 | 35.8 |
| Standby | 75% | 204.8 | 54.1 |
| Standby | 100% | 273.3 | 72.2 |