HomeMagnumMagnum MMG130D Super Start

Magnum MMG130D Super Start Generator Set

The Magnum MMG130D Super Start is a 107 kW (134 kVA) standby generator set powered by a John Deere PE4045HFG93 engine. It is available at 120 V, 139 V, 208 V, 220 V, 240 V and 277 V, 3Ø, 60 Hz and rated 161 A. It holds about 15.5 L (4.1 gal) of oil and 29.8 L (7.9 gal) of coolant. Starting uses 1 group-24 battery rated 1000 CCA at 12 V. The set weighs about 2469 kg (5443 lb). An integrated tank holds 1295 L (342.1 gal), roughly 44 hours of runtime. The same PE4045HFG93 engine also powers generator sets from Generac and John Deere.

107 kW
Standby
4.5 L
Displacement
15.5 L
Oil capacity
0
Document types

Specifications

Frequency60.0 Hz
Standby power107 kW
Standby kVA134
Prime power98 kW
Oil capacity15.5 L
AlternatorMarathon 363PSL1607
Voltage options120 V, 139 V, 208 V, 220 V, 240 V, 277 V
Phase
Rated current161 A
Power factor1 (1Ø), 0.8 (3Ø)
Circuit breaker450 A
Battery group24
Battery cranking1000 CCA
Battery voltage12V V
Battery quantity1
Dry weight2469 kg
Fuel tank1295.0 L
Tank runtime44 hr

Engine

John Deere PE4045HFG93
Oil capacity31.2 L
Coolant capacity29.8 L
Displacement4.5 L
Aspirationturbocharged
Rated speed1800 rpm

Maintenance & consumables

for the John Deere PE4045HFG93
ItemSpecCapacityPart #Interval
Air filterpaper element250 hr
Fuel filter500 hr
Oil filter500 hr
Battery500 hr
Belt1000 hr
Coolant250 hr
Oil31.2500 hr
Spark plug250 hr

Common questions

What size generator is the Magnum MMG130D Super Start?

The Magnum MMG130D Super Start is rated 107 kW standby (134.0 kVA).

Which engine powers the Magnum MMG130D Super Start?

The Magnum MMG130D Super Start is powered by the John Deere PE4045HFG93 engine.

What is the oil capacity of the Magnum MMG130D Super Start?

The John Deere PE4045HFG93 engine in the Magnum MMG130D Super Start has an oil capacity of 31.2 liters.

Which alternator is fitted to the Magnum MMG130D Super Start?

The Magnum MMG130D Super Start uses a Marathon 363PSL1607 alternator.

Troubleshooting

5

Fault codes

CodeMeaning
UbatBattery voltage is out of limits given by Batt Undervolt setpoints.

Symptoms & remedies

SymptomCauseRemedy
LOW FUEL LEVEL SHUTDOWNFuel level on the LCD window is low, fuel tank has leaks, fuel level sender or wiring damaged.Check and refill fuel. Inspect for leaks. Check fuel level sender and wiring.
LOW OIL PRESSURE SHUTDOWNOil pressure is less than 20 psi, engine has oil leaks.Check oil level with dipstick. Visually inspect for leaks. Restart and verify oil pressure. Check oil pressure sender.
LOW COOLANT LEVEL SHUTDOWNCoolant level in the radiator is low, coolant hoses, engine block or water pump have visible leaks.Check and add coolant. Inspect for leaks. Check engine oil for mixed coolant.
HIGH COOLANT TEMPERATURE SHUTDOWNCoolant temperature is 230°F or more.Check coolant level in overflow jug. Add coolant if low. Stop engine immediately.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

3
Part #DescriptionQtySystem
P-130D-001Air Filter1Air filter Amazon eBay
P-175-002Oil Filter1Oil filter Amazon eBay
P-205-003Fuel Filter1Fuel filter Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime100%48.512.8
Standby100%28.07.4

Available documents