HomeMagnumMagnum MMG130

Magnum MMG130 Generator Set

The Magnum MMG130 is a 96 kW (96 kVA) diesel standby generator set powered by a John Deere PE4045HFG93 engine. It is available at 120/240 V, 120/208 V and 277/480 V, single-phase, 60 Hz and rated 400 A. It holds about 31.2 L (8.2 gal) of oil and 29.8 L (7.9 gal) of coolant, with a maximum ambient rating of 48.9 °C. Starting uses 1 group-24 battery rated 1000 CCA at 12 V. The set measures 3657×1270×1956 mm (144.0×50.0×77.0 in), weighs about 2469 kg (5443 lb) and produces 68 dBA at 7.01 m. An integrated tank holds 1294.5 L (342.0 gal), roughly 44 hours of runtime. The same PE4045HFG93 engine also powers generator sets from Generac and John Deere.

96 kW
Standby
4.5 L
Displacement
31.2 L
Oil capacity
2
Document types

Typical fuel consumption for 105–110 kW Diesel generators →

Compare with other 105–110 kW Diesel generators →

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power96 kW
Standby kVA96
Prime power90 kW
EmissionsInterim Tier IV
ControllerPower Zone
Oil capacity31.2 L
AlternatorMarathon 363PSL1607
Voltage options120/240 V, 120/208 V, 277/480 V
Phasesingle/three
Rated current400 (240V 1Ø) A
Power factor1 (1Ø), 0.8 (3Ø)
Circuit breaker450 A
Battery group24
Battery cranking1000 CCA
Battery voltage12 V
Battery quantity1
Coolant capacity29.8 L
Max ambient48.9 °C
Dimensions (L×W×H)3657×1270×1956 mm
Dry weight2469 kg
Wet weight3596 kg
Sound level68.0 dBA @ 7.01 m
Fuel tank1294.5 L
Tank runtime44 hr

Engine

John Deere PE4045HFG93
Oil capacity31.2 L
Coolant capacity29.8 L
Displacement4.5 L
Aspirationturbocharged
Rated speed1800 rpm

Maintenance & consumables

for the John Deere PE4045HFG93
ItemSpecCapacityPart #Interval
Air filterDisposable air filter - paper element250 hr
Fuel filter500 hr
Oil filter500 hr
Battery500 hr
Belt1000 hr
Coolant250 hr
Oil31.2500 hr
Spark plug250 hr

Service intervals

4
ItemActionHoursMonthsNotes
Engine mountsCheck500 hr12 mo
Engine oil and oil filterChange500 hr12 moAfter first 100 hours, then every 500 hours; every 250 hours if not using John Deere Plus 50 II
Fuel filter elementsReplace500 hr12 mo
Generator drive plate torqueCheck3000 hr36 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

6
TypeItemValueUnitCondition
PressureOil pressure20psishutdown threshold
PressureOil pressure25psiwarning threshold
TemperatureCoolant temperature220°Fwarning threshold
TemperatureCoolant temperature230°Fshutdown threshold
VoltageBattery voltage11VDCunder warning
VoltageBattery voltage15VDCover warning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilJohn Deere Plus 50 II recommended31.2 qtChange interval: 500 hours on John Deere Plus 50 II; 250 hours on other oils
FuelClean diesel fuel1295.0 LUse only clean diesel fuel

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

How many kW is the Magnum MMG130?

The Magnum MMG130 is rated 96 kW standby (96.0 kVA).

Which engine powers the Magnum MMG130?

The Magnum MMG130 is powered by the John Deere PE4045HFG93 engine.

What kind of fuel does the Magnum MMG130 run on?

The Magnum MMG130 runs on diesel.

How much oil does the Magnum MMG130 take?

The John Deere PE4045HFG93 engine in the Magnum MMG130 has an oil capacity of 31.2 liters.

What alternator comes on the Magnum MMG130?

The Magnum MMG130 uses a Marathon 363PSL1607 alternator.

Troubleshooting

6

Fault codes

CodeMeaningRemedy
00383Exhaust Filter Cleaning enabled.
1To ServiceOil Maintenance

Symptoms & remedies

SymptomCauseRemedy
LOW FUEL LEVEL SHUTDOWNFuel level on the LCD window is low, fuel tank has leaks, fuel level sender or wiring damaged.Check and refill fuel. Inspect for leaks. Check fuel level sender and wiring.
LOW OIL PRESSURE SHUTDOWNOil pressure is less than 20 psi, engine has oil leaks.Check oil level with dipstick. Visually inspect for leaks. Restart and verify oil pressure. Check oil pressure sender.
LOW COOLANT LEVEL SHUTDOWNCoolant level in the radiator is low, coolant hoses, engine block or water pump have visible leaks.Check and add coolant. Inspect for leaks. Check engine oil for mixed coolant.
HIGH COOLANT TEMPERATURE SHUTDOWNCoolant temperature is 230°F or more.Check coolant level in overflow jug. Add coolant if low. Stop engine immediately.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Magnum MMG130 troubleshooting guide (10 entries) →

Parts

3
Part #DescriptionQtySystem
P-130D-001Air Filter1Air filter Amazon eBay
P-175-002Oil Filter1Oil filter Amazon eBay
P-205-003Fuel Filter1Fuel filter Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime50%14.03.7
Prime75%20.85.5
Prime100%28.07.4
Standby100%28.07.4

Available documents

Spec sheet (Magnum)Spec sheet — MMG130 Mobile (Magnum)Spec sheet — MMG130 Spec (Magnum)Operator's manual — 48962 (Magnum)