Specifications
| Fuel | natural gas / LP |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 260 kW |
| Standby kVA | 325 |
| Prime power | 235 kW |
| Controller | APM603 |
| Oil capacity | 38.1 L |
| Alternator | Fast-Response PMG (Class Class H insulation) |
| Voltage options | 480 V |
| Phase | 3-phase |
| Rated current | 902 A |
| Power factor | 0.8 |
| Battery cranking | 925 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 227.3 L |
| Engine jacket water | 43.2 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3500×1750×2148 mm |
| Dry weight | 3200 kg |
Engine
| Oil capacity | 47.1 L |
|---|---|
| Coolant capacity | 43.2 L |
| Displacement | 14.6 L |
| Aspiration | Turbocharged, Aftercooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Doosan D146L| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil filter | ×2 | — |
Service specifications
30| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12-lead optional voltage connections | 12 | Alternator optional feature | ||
| 4-lead dedicated voltages | 4 | Alternator standard feature | ||
| 110/127/139/240/254/277 | single-phase | switchable | Towable generator model specifications; some models n/a | |
| 208/220/240/415/440/480 | 3-phase | reconnectable | Towable generator model specifications | |
| 208/220/240/415/440/480 | 3-phase | switchable | Towable generator model specifications |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Kohler 250RZX?
The Kohler 250RZX is rated 260 kW standby (325.0 kVA).
What engine is in the Kohler 250RZX?
The Kohler 250RZX is powered by the Doosan D146L engine.
What fuel type does the Kohler 250RZX take?
The Kohler 250RZX runs on natural gas / LP.
What is the oil capacity of the Kohler 250RZX?
The Doosan D146L engine in the Kohler 250RZX has an oil capacity of 47.1 liters.
What is the coolant capacity of the Kohler 250RZX?
The Kohler 250RZX cooling system holds 227.3 liters (60.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Kohler 250RZX?
The Kohler 250RZX is rated 235 kW prime (294 kVA), against 260 kW standby.
What is the dry weight of the Kohler 250RZX?
The Kohler 250RZX has a dry weight of 3200 kg (7054 lb).
What voltage does the Kohler 250RZX produce?
The Kohler 250RZX is offered in 480 V, 3-phase-phase.
How many cold cranking amps does the Kohler 250RZX require?
The Kohler 250RZX uses 2 batteryies, 12 V each, 925 CCA, per the manufacturer specification sheet.
Which alternator is fitted to the Kohler 250RZX?
The Kohler 250RZX uses a Fast-Response PMG alternator. Insulation class Class H.