Home›Hipower›Hipower HMW 510 T6U

Hipower HMW 510 T6U Generator Set

The Hipower HMW 510 T6U is a 500 kW (625 kVA) diesel standby generator set powered by a MTU 10V 1600 G80S engine. It is available at 120/208 V, 120/240 V, 277/480 V and 347/600 V, 3-phase and 60 Hz. It holds about 68.5 L (18.1 gal) of oil and 94 L (24.8 gal) of coolant. Starting uses 2 batteries rated 800 CCA at 24 V. The set measures 3599×1603×2121 mm (141.7×63.1×83.5 in), weighs about 3864 kg (8519 lb) and produces 73 dBA at 7 m. An integrated tank holds 740 L (195.5 gal), roughly 8 hours of runtime. The same 10V 1600 G80S engine also powers generator sets from MTU.

500 kW
Standby
17.5 L
Displacement
68.5 L
Oil capacity
1
Document types

Typical fuel consumption for 500–505 kW Diesel generators →

Compare with other 500–505 kW Diesel generators →

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power500 kW
Standby kVA625
Prime power450 kW
EmissionsTier 2
ControllerDSE7310
Oil capacity68.5 L
AlternatorStamford/AvK HCI 544 F (4-pole, Class H insulation)
Voltage options120/208 V, 120/240 V, 277/480 V, 347/600 V
Phase3
Power factor0.8
Battery cranking800 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity94 L
Dimensions (L×W×H)3599×1603×2121 mm
Dry weight3864 kg
Sound level73.0 dBA @ 7 m
Fuel tank740.0 L
Tank runtime8.0 hr

Engine

MTU 10V 1600 G80S
Oil capacity68.5 L
Coolant capacity94.0 L
Displacement17.5 L
AspirationTurbocharged, aftercooled
Rated speed1800 rpm

Same engine, other brands

1 brand

The MTU 10V 1600 G80S in this set also powers 2 generator sets sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
MTU10V1600 DS500, 500 kW DS500 Standby Diesel Generator

Maintenance & consumables

for the MTU 10V 1600 G80S
ItemSpecCapacityPart #Interval
Air filterMedium duty - double cartridge, two-stage dry element, replaceable element—
Fuel filterSecondary, 8 microns at 98% efficiency—
Battery2 x 75 Ah, 24 V, 800 CCA minimum—
Coolant94.0 L—
OilS10 W4068.5 L—

Common questions

How many kW is the Hipower HMW 510 T6U?

The Hipower HMW 510 T6U is rated 500 kW standby (625.0 kVA).

What engine does the Hipower HMW 510 T6U use?

The Hipower HMW 510 T6U is powered by the MTU 10V 1600 G80S engine.

Is the Hipower HMW 510 T6U diesel or gas?

The Hipower HMW 510 T6U runs on diesel.

What's the oil capacity on a Hipower HMW 510 T6U?

The MTU 10V 1600 G80S engine in the Hipower HMW 510 T6U has an oil capacity of 68.5 liters.

What is the coolant capacity of the Hipower HMW 510 T6U?

The Hipower HMW 510 T6U cooling system holds 94 liters (24.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Hipower HMW 510 T6U?

The Hipower HMW 510 T6U is rated 450 kW prime (562 kVA), against 500 kW standby.

What is the sound level of the Hipower HMW 510 T6U?

The Hipower HMW 510 T6U is rated at 73.0 dBA at 7 m, per the manufacturer specification sheet.

What is the dry weight of the Hipower HMW 510 T6U?

The Hipower HMW 510 T6U has a dry weight of 3864 kg (8518 lb).

What size fuel tank does the Hipower HMW 510 T6U have?

The Hipower HMW 510 T6U has a 740 liter (195 US gallon) fuel tank, giving about 8.0 hours of runtime.

What voltage does the Hipower HMW 510 T6U produce?

The Hipower HMW 510 T6U is offered in 120/208 V, 120/240 V, 277/480 V, 347/600 V, 3-phase.

How many cold cranking amps does the Hipower HMW 510 T6U require?

The Hipower HMW 510 T6U uses 2 batteryies, 24 V each, 800 CCA, per the manufacturer specification sheet.

What alternator comes on the Hipower HMW 510 T6U?

The Hipower HMW 510 T6U uses a Stamford/AvK HCI 544 F alternator. It has 4 poles. Insulation class H.

Fuel consumption

RatingLoadL/hgal/h
Prime25%43.2711.43
Prime50%57.6915.24
Prime75%76.9220.32
Prime100%102.5527.09
Standby25%47.3212.5
Standby50%67.017.7
Standby75%90.0923.8
Standby100%113.9430.1