Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 500 kW |
| Standby kVA | 500 |
| Prime power | 450 kW |
| Emissions | EPA Tier 2 |
| Controller | ADEC |
| Oil capacity | 61.0 L |
| Alternator | Mecc Alte HM355A3 |
| Voltage options | 380 V, 400 V, 415 V |
| Phase | 3 |
| Rated current | [1561, 1353, 855, 738, 677, 541] A |
| Power factor | 0.8 |
| Battery group | 4D |
| Battery cranking | 1050 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 99.3 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3416×1873×2032 mm |
| Dry weight | 4175 kg |
| Sound level | 88.2 dBA @ 7 m |
| Fuel tank | 740.0 L |
| Tank runtime | 9 hr |
Engine
| Oil capacity | 61.0 L |
|---|---|
| Coolant capacity | 60.0 L |
| Displacement | 17.5 L |
| Aspiration | turbocharged |
| Rated speed | 1500 rpm |
Maintenance & consumables
for the MTU 10V 1600 G10F| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Medium duty - double cartridge, two-stage dry element, replaceable element | — | |||
| Fuel filter | Secondary, 8 microns at 98% efficiency | — | |||
| Oil filter | — | ||||
| Battery | 2 x 75 Ah, 24 V, 800 CCA minimum | — | |||
| Belt | — | ||||
| Coolant | 99.3 L | — | |||
| Oil | S10 W40 | 68.5 L | — | ||
| Spark plug | — |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the MTU 10V1600 DS500?
The MTU 10V1600 DS500 is rated 500 kW standby (500.0 kVA).
Which engine powers the MTU 10V1600 DS500?
The MTU 10V1600 DS500 is powered by the MTU 10V 1600 G10F engine.
What kind of fuel does the MTU 10V1600 DS500 run on?
The MTU 10V1600 DS500 runs on diesel.
What is the oil capacity of the MTU 10V1600 DS500?
The MTU 10V 1600 G10F engine in the MTU 10V1600 DS500 has an oil capacity of 61.0 liters.
What is the cooling system capacity of the MTU 10V1600 DS500?
The MTU 10V1600 DS500 cooling system holds 99.3 liters (26.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 10V1600 DS500?
The MTU 10V1600 DS500 is rated 450 kW prime (450 kVA), against 500 kW standby.
What is the sound level of the MTU 10V1600 DS500?
The MTU 10V1600 DS500 is rated at 88.2 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 10V1600 DS500 weigh?
The MTU 10V1600 DS500 has a dry weight of 4175 kg (9204 lb).
How big is the fuel tank on the MTU 10V1600 DS500?
The MTU 10V1600 DS500 has a 740 liter (195 US gallon) fuel tank, giving about 9 hours of runtime.
What voltage does the MTU 10V1600 DS500 produce?
The MTU 10V1600 DS500 is offered in 380 V, 400 V, 415 V, 3-phase.
How many cold cranking amps does the MTU 10V1600 DS500 require?
The MTU 10V1600 DS500 uses 2 batteryies, 24 V each, 1050 CCA, group 4D, per the manufacturer specification sheet.
Which alternator is fitted to the MTU 10V1600 DS500?
The MTU 10V1600 DS500 uses a Mecc Alte HM355A3 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 115.0 | 30.38 | |
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents
This page was generated from the 16 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.