Genmac HSD17 Generator Set

The Genmac HSD17 is a 12 kW (12 kVA) DIESEL FUEL standby generator set powered by a Lombardini 12LD435-2 engine. It is available at 120 V, single-phase, 60 Hz and rated 100 A. The set measures 1800×890×950 mm (70.9×35.0×37.4 in), weighs about 577 kg (1272 lb) and produces 66.7 dBA at 7 m. An integrated tank holds 23 L (6.1 gal).

12 kW
Standby
0.871 L
Displacement
1
Document types

Typical fuel consumption for 10–15 kW Diesel generators →

Compare with other 10–15 kW Diesel generators →

Specifications

FuelDIESEL FUEL
Frequency60.0 Hz
Standby power12 kW
Standby kVA12
Prime power10.4 kW
Voltage options120 V, 240 V
Phasesingle
Rated current100 A
Circuit breaker100 A
Dimensions (L×W×H)1800×890×950 mm
Dry weight577 kg
Sound level66.7 dBA @ 7 m
Fuel tank23.0 L

Engine

Lombardini 12LD435-2
Displacement0.871 L
Aspirationnatural
Rated speed3600 rpm

Filters & service parts

model family
ItemSpecCapacityPart #Interval
Air filterair filter—500 hr
Fuel filterfuel filter—300 hr
Oil filterengine oil filter—100 hr
Batterybattery—
Belt—
Coolantautomotive antifreeze coolant—
Oilengine oil—100 hr
Spark plugspark plug—

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.

Common questions

How many kW is the Genmac HSD17?

The Genmac HSD17 is rated 12 kW standby (12.0 kVA).

What engine is in the Genmac HSD17?

The Genmac HSD17 is powered by the Lombardini 12LD435-2 engine.

What fuel type does the Genmac HSD17 take?

The Genmac HSD17 runs on DIESEL FUEL.

What is the prime power rating of the Genmac HSD17?

The Genmac HSD17 is rated 10.4 kW prime (10 kVA), against 12 kW standby.

How loud is the Genmac HSD17?

The Genmac HSD17 is rated at 66.7 dBA at 7 m, per the manufacturer specification sheet.

How much does the Genmac HSD17 weigh?

The Genmac HSD17 has a dry weight of 577 kg (1272 lb).

How big is the fuel tank on the Genmac HSD17?

The Genmac HSD17 has a 23 liter (6 US gallon) fuel tank.

What voltages is the Genmac HSD17 available in?

The Genmac HSD17 is offered in 120 V, 240 V, single-phase.

Troubleshooting

12

Symptoms & remedies

SymptomCauseRemedy
Engine governing system does not function (system inoperative) — Step 1: terminals E(+) & F(-), normal reading battery supply voltage (12 VDC)DC battery power not connected; blown fuse; low battery voltage; wiring error
Engine governing system does not function (system inoperative) — Step 2: terminals A(+) & B(-), normal reading 0-3.9 with speed trim, 7.1-7.9 without speed trimSpeed trim shorted or miswired; defective unit
Engine governing system does not function (system inoperative) — Step 3: terminals C(+) & D(-), normal reading 1.0 VAC RMS min. while crankingGap between speed sensor and gear teeth too great; improper or defective wiring to the speed sensor; defective speed sensorCheck gap; resistance between D & C should be 30 to 1200 Ω
Engine governing system does not function (system inoperative) — Step 4: terminals E(+) & H(-), normal reading 0.8-1.5 V while crankingWiring error to actuator; defective speed control unit; defective actuator
Engine overspeed — Test 1: Do not crank, apply DC power to the governor systemActuator goes to full fuelThen disconnect speed sensor terminals C and D; if actuator still at full fuel — speed control unit defective; if actuator at minimum fuel position — erroneous speed signal, check speed sensor cable
Engine overspeed — Test 2: Manually hold the engine at the desired running speed, measure the DC voltage between terminals E(+) and H(-) on the speed control unitIf the voltage reading is 1.0 to 1.5 VDC: speed adjustment set above desired speed; defective speed control unitTurn counterclockwise
Engine overspeed — Test 2: Manually hold the engine at the desired running speed, measure the DC voltage between terminals E(+) and H(-) on the speed control unitIf the voltage reading is above 1.5 VDC: actuator or linkage bindingReplace actuator
Engine overspeed — Test 2: Manually hold the engine at the desired running speed, measure the DC voltage between terminals E(+) and H(-) on the speed control unitSet point of over speed shutdown device set too low
Engine overspeed — Test 2: Manually hold the engine at the desired running speed, measure the DC voltage between terminals E(+) and H(-) on the speed control unitIf the voltage reading is below 0.8 VDC: defective speed control unit
Actuator does not energize fully while cranking — Test 1: measure the DC voltage between terminals E(+) and H(-) on the speed control unit; should be 0.8 to 1.5 volts, if notWeak or undersized battery; actuator wiring incorrect; if voltage is greater than 1.5V, speed set too lowReplace the battery if weak or undersized
Actuator does not energize fully while cranking — Test 2: momentarily connect terminal E to H; the actuator should move to the full fuel positionActuator or battery wiring in error; actuator or linkage binding; defective actuatorReplace actuator
Engine remains below desired speed — Test 1: measure the actuator output, terminals G & H, while runningIf voltage measurement is within 1.5 volts or more

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Fuel consumption

RatingLoadL/hgal/h
Prime100%1.97.2
Standby100%1.14.2

Available documents

Owner's manual — Elliott HSB 12-22kW OM 2004 (Genmac)

This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.