Lombardini 12LD435-2 Engine

The Lombardini 12LD435-2 is a 0.87 L natural engine rated at 3600 rpm. It powers generator sets from Genmac, including the HSD17.

Also known as: LOMBARDINI 12LD435-2

Part of the Lombardini 12LD435 engine family — 2 variants share parts & fitment.

0.871 L
Displacement
3600 rpm
Rated speed

Engine specifications

Displacement0.871 L
Aspirationnatural
Rated speed3600 rpm

Generator sets powered by this engine

1

Common problems

9
  • Engine overspeed — Test 2: Manually hold the engine at the desired running speed, measure the DC voltage between terminals E(+) and H(-) on the speed control unit
    Cause: If the voltage reading is 1.0 to 1.5 VDC: speed adjustment set above desired speed; defective speed control unit
    Fix: Turn counterclockwise
  • Engine remains below desired speed — Test 1: measure the actuator output, terminals G & H, while running
    Cause: If voltage measurement is within 1.5 volts or more
  • Engine overspeed — Test 1: Do not crank, apply DC power to the governor system
    Cause: Actuator goes to full fuel
    Fix: Then disconnect speed sensor terminals C and D; if actuator still at full fuel — speed control unit defective; if actuator at minimum fuel position — erroneous speed signal, check speed sensor cable
  • Engine governing system does not function (system inoperative) — Step 4: terminals E(+) & H(-), normal reading 0.8-1.5 V while cranking
    Cause: Wiring error to actuator; defective speed control unit; defective actuator
  • Engine governing system does not function (system inoperative) — Step 3: terminals C(+) & D(-), normal reading 1.0 VAC RMS min. while cranking
    Cause: Gap between speed sensor and gear teeth too great; improper or defective wiring to the speed sensor; defective speed sensor
    Fix: Check gap; resistance between D & C should be 30 to 1200 Ω
  • Engine governing system does not function (system inoperative) — Step 2: terminals A(+) & B(-), normal reading 0-3.9 with speed trim, 7.1-7.9 without speed trim
    Cause: Speed trim shorted or miswired; defective unit
  • Engine governing system does not function (system inoperative) — Step 1: terminals E(+) & F(-), normal reading battery supply voltage (12 VDC)
    Cause: DC battery power not connected; blown fuse; low battery voltage; wiring error
  • Actuator does not energize fully while cranking — Test 2: momentarily connect terminal E to H; the actuator should move to the full fuel position
    Cause: Actuator or battery wiring in error; actuator or linkage binding; defective actuator
    Fix: Replace actuator
  • Actuator does not energize fully while cranking — Test 1: measure the DC voltage between terminals E(+) and H(-) on the speed control unit; should be 0.8 to 1.5 volts, if not
    Cause: Weak or undersized battery; actuator wiring incorrect; if voltage is greater than 1.5V, speed set too low
    Fix: Replace the battery if weak or undersized

Compiled from service & troubleshooting documentation across every generator set that uses the Lombardini 12LD435-2.

Common questions

What is the displacement of the Lombardini 12LD435-2?

The Lombardini 12LD435-2 has a displacement of 0.871 liters.

Which generators use the Lombardini 12LD435-2 engine?

The Lombardini 12LD435-2 powers 1 generator set(s), including Genmac HSD17.

What is a common problem with the Lombardini 12LD435-2 engine?

A commonly reported issue on generators using the Lombardini 12LD435-2 is: Engine overspeed — Test 2: Manually hold the engine at the desired running speed, measure the DC voltage between terminals E(+) and H(-) on the speed control unit. Cause: If the voltage reading is 1.0 to 1.5 VDC: speed adjustment set above desired speed; defective speed control unit. Fix: Turn counterclockwise.