Service parts for the SD2000
Grouped by system, with how many of each the parts manual calls for.
Fuel system
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | No. 2 Diesel Fuel |
|---|---|
| Standby power | 2000 kW |
| Standby kVA | 2000 |
| Prime power | 1600 kW |
| Controller | Generac "E" Control Panel |
| Oil capacity | 250.0 L |
| Voltage options | 277/480 V, 600 V, 220/380 V, 230/400 V, 260/415 V |
| Phase | 3-phase |
| Power factor | 0.8 |
| Battery voltage | 12V V |
| Battery quantity | 4 |
| Coolant capacity | 492 L |
| Max ambient | 50 °C |
Engine
| Oil capacity | 250.0 L |
|---|---|
| Coolant capacity | 206.0 L |
| Displacement | 65.0 L |
| Aspiration | Turbocharged/Aftercooled |
Maintenance & consumables
for the Detroit Diesel 16V4000| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Fuel filter | Paper Element Type | 33645 | eBay | ||
| Oil filter | Full Flow Cartridge and Bypass | — | |||
| Coolant | 492.0 liter | — | |||
| Oil | 250.0 liter | — |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | No. 2 Diesel Fuel | ASTM Spec. Minimum Cetane of 45 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Generac SD2000?
The Generac SD2000 is rated 2000 kW standby (2000.0 kVA).
What engine does the Generac SD2000 use?
The Generac SD2000 is powered by the Detroit Diesel 16V4000 engine.
What fuel type does the Generac SD2000 take?
The Generac SD2000 runs on No. 2 Diesel Fuel.
What is the oil capacity of the Generac SD2000?
The Detroit Diesel 16V4000 engine in the Generac SD2000 has an oil capacity of 250.0 liters.
Which fuel filter part number does the Generac SD2000 take?
The Generac SD2000 uses fuel filter part number 33645.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 113.0 | 30.0 |
| Prime | 50% | 208.0 | 55.0 |
| Prime | 75% | 300.0 | 79.0 |
| Prime | 100% | 405.0 | 107.0 |
| Standby | 25% | 143.0 | 37.7 |
| Standby | 50% | 260.0 | 68.8 |
| Standby | 75% | 375.0 | 99.0 |
| Standby | 100% | 509.0 | 134.5 |