Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 60 kW |
| Standby kVA | 75 |
| Prime power | 54 kW |
| Emissions | EPA Certified Stationary Emergency |
| Controller | Digital H Control Panel |
| Oil capacity | 13.6 L |
| Alternator | 390 (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 346/600 V |
| Phase | 1,3 |
| Battery group | 27F |
| Battery cranking | 995 CCA CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 17.44 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 2362×1016×1244 mm |
| Dry weight | 1100 kg |
| Sound level | 79.0 dBA @ 7 m |
Engine
| Oil capacity | 18.0 L |
|---|---|
| Coolant capacity | 6.4 L |
| Displacement | 3.9 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Generac 3.9DTA| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | find | |||
| Fuel filter | — | find | |||
| Oil filter | — | find | |||
| Belt | — | find | |||
| Coolant | 15.9 liters | — | |||
| Oil | 18.0 liters | — |
Common questions
What is the power rating of the Generac SD060?
The Generac SD060 is rated 60 kW standby (75.0 kVA).
What engine does the Generac SD060 use?
The Generac SD060 is powered by the Generac 3.9DTA engine.
What fuel does the Generac SD060 use?
The Generac SD060 runs on Diesel.
What is the oil capacity of the Generac SD060?
The Generac 3.9DTA engine in the Generac SD060 has an oil capacity of 18.0 liters.
What alternator does the Generac SD060 use?
The Generac SD060 uses a 390 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 4.4 | 1.2 |
| Prime | 50% | 8.2 | 2.2 |
| Prime | 75% | 12.0 | 3.2 |
| Prime | 80% | 11.3 | 3.0 |
| Prime | 100% | 16.0 | 4.2 |
| Standby | 25% | 5.3 | 1.4 |
| Standby | 50% | 10.2 | 2.7 |
| Standby | 75% | 14.4 | 3.8 |
| Standby | 80% | 13.5 | 3.6 |
| Standby | 100% | 18.2 | 4.8 |