Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 100 kW |
| Standby kVA | 125 |
| Prime power | 90 kW |
| Emissions | Stationary Emergency |
| Controller | POWERZONE 410 |
| Oil capacity | 17.0 L |
| Alternator | 390 (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 346/600 V |
| Power factor | 0.8 |
| Battery group | 27F |
| Battery cranking | 995 CCA |
| Battery voltage | 12 VDC V |
| Battery quantity | 1 |
| Coolant capacity | 21.4 L |
| Max ambient | 43.3 °C |
| Dimensions (L×W×H) | 2794×1016×1651 mm |
| Dry weight | 1408 kg |
Engine
| Oil capacity | 11.0 L |
|---|---|
| Coolant capacity | 10.4 L |
| Displacement | 4.8 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Generac BF4M1013EC Deutz| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | find | |||
| Fuel filter | — | find | |||
| Oil filter | — | find | |||
| Belt | — | find | |||
| Coolant | 15.9 liters | — | |||
| Oil | 18.0 liters | — |
Common questions
What is the power rating of the Generac SD100?
The Generac SD100 is rated 100 kW standby (125.0 kVA).
What engine does the Generac SD100 use?
The Generac SD100 is powered by the Generac BF4M1013EC Deutz engine.
What fuel does the Generac SD100 use?
The Generac SD100 runs on Diesel.
What is the oil capacity of the Generac SD100?
The Generac BF4M1013EC Deutz engine in the Generac SD100 has an oil capacity of 11.0 liters.
What alternator does the Generac SD100 use?
The Generac SD100 uses a 390 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 7.1 | 1.9 |
| Prime | 50% | 13.3 | 3.5 |
| Prime | 75% | 19.4 | 5.1 |
| Prime | 80% | 16.8 | 4.4 |
| Prime | 100% | 23.9 | 6.3 |
| Standby | 25% | 8.3 | 2.2 |
| Standby | 50% | 15.9 | 4.2 |
| Standby | 75% | 22.3 | 5.9 |
| Standby | 80% | 21.0 | 5.6 |
| Standby | 100% | 27.6 | 7.3 |