Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 15 kW |
| Standby kVA | 19 |
| Prime power | 14 kW |
| Emissions | Stationary Emergency |
| Controller | Digital H Control Panel - Dual 4x20 Display |
| Oil capacity | 6.2 L |
| Alternator | 390 (Class NEMA MG1-32.6, NEMA MG1-1.66 insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 63 A |
| Power factor | 0.8 |
| Circuit breaker | 63 A |
| Battery group | See Battery Index 0161970SBY |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 2.8 L |
| Max ambient | 43.3 °C |
| Dimensions (L×W×H) | 1930×914×1168 mm |
| Dry weight | 934 kg |
| Tank runtime | 37 hr |
Engine
| Oil capacity | 6.2 L |
|---|---|
| Coolant capacity | 2.8 L |
| Displacement | 2.4 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Common questions
How many kW is the Generac SD015?
The Generac SD015 is rated 15 kW standby (19.0 kVA).
What engine does the Generac SD015 use?
The Generac SD015 is powered by the Generac SD015 engine.
What fuel does the Generac SD015 use?
The Generac SD015 runs on Diesel.
How much oil does the Generac SD015 take?
The Generac SD015 engine in the Generac SD015 has an oil capacity of 6.2 liters.
What is the cooling system capacity of the Generac SD015?
The Generac SD015 cooling system holds 2.8 liters (0.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Generac SD015?
The Generac SD015 is rated 14 kW prime (17 kVA), against 15 kW standby.
What is the dry weight of the Generac SD015?
The Generac SD015 has a dry weight of 934 kg (2059 lb).
What voltage does the Generac SD015 produce?
The Generac SD015 is offered in 120/240 V, 120/208 V, 277/480 V, 346/600 V, Three-Phase-phase.
What battery does the Generac SD015 use?
The Generac SD015 uses 1 battery, 12 V each, group See Battery Index 0161970SBY, per the manufacturer specification sheet.
Which alternator is fitted to the Generac SD015?
The Generac SD015 uses a 390 alternator. Insulation class NEMA MG1-32.6, NEMA MG1-1.66.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 1.9 | 0.5 |
| Standby | 50% | 3.5 | 0.92 |
| Standby | 75% | 4.6 | 1.22 |
| Standby | 100% | 5.6 | 1.47 |
Available documents
This page was generated from the 3 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.