Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 500 kW |
| Standby kVA | 625 |
| Prime power | 450 kW |
| Emissions | EPA Certified |
| Controller | Digital G |
| Oil capacity | 90.0 L |
| Alternator | WEG Standard |
| Voltage options | 120/208 V, 120/240 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 1,735 A |
| Power factor | 0.8 |
| Circuit breaker | 1,735 A |
| Battery group | 0161970SBY |
| Battery voltage | 12 VDC V |
| Battery quantity | 2 |
| Coolant capacity | 20.5 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 3923×1803×1794 mm |
| Dry weight | 4417 kg |
| Tank runtime | N/A hr |
Engine
| Oil capacity | 90.0 L |
|---|---|
| Coolant capacity | 87.0 L |
| Displacement | 21.9 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Generac MG500?
The Generac MG500 is rated 500 kW standby (625.0 kVA).
What engine does the Generac MG500 use?
The Generac MG500 is powered by the Generac V12 engine.
What fuel type does the Generac MG500 take?
The Generac MG500 runs on Natural Gas.
How much oil does the Generac MG500 take?
The Generac V12 engine in the Generac MG500 has an oil capacity of 90.0 liters.
What is the cooling system capacity of the Generac MG500?
The Generac MG500 cooling system holds 20.5 liters (5.4 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac MG500?
The Generac MG500 is rated 450 kW prime (563 kVA), against 500 kW standby.
How much does the Generac MG500 weigh?
The Generac MG500 has a dry weight of 4417 kg (9737 lb).
What voltages is the Generac MG500 available in?
The Generac MG500 is offered in 120/208 V, 120/240 V, 277/480 V, 346/600 V, Three-Phase-phase.
How many cold cranking amps does the Generac MG500 require?
The Generac MG500 uses 2 batteryies, 12 VDC V each, group 0161970SBY, per the manufacturer specification sheet.
What alternator comes on the Generac MG500?
The Generac MG500 uses a WEG Standard alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 100% | 5.0 | 148.3 |
| Standby | 100% | 5.0 | 164.8 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.