Generac 4077 Generator Set

The Generac 4077 is a 6 kW standby generator set.

6 kW
Standby
1
Document types

How to read your Generac serial & model number →

Service parts for the 4077

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Oil system

1 required
070185Oil filter$3.59NAPA

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Standby power6 kW

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filterAir Filter (GN410)073111 Amazon eBay
Oil filterOil Filter (liquid cooled)070185 Amazon eBay $30.00 NAPA $3.59 FridayParts $45.99

Service intervals

1
ItemActionHoursMonthsNotes
BatteryInspect1 moMonthly battery inspection; reset the exercise timer after performing it.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

18
TypeItemValueUnitCondition
ClearanceDrive belt tension - compressed length of tensioning springs5/8inch (16mm)by turning the two adjusting bolts
GapStarter pinion to ring gear backlash.020-.035inchmeasure at eight equally spaced locations with manual engagement
OtherFuel regulator adjuster dimension (top of adjuster screw to top of threaded casting)5mmmmafter removing freeze plug
PressureFuel supply pressure to generator regulator11inches of water column
PressureLOS switch (P/N 99236) test air pressure20PSIapply 20 PSI air pressure to switch
PressureLP fuel pressure to generator fuel inlet11 to 14inches of water column (0.6 psi)
PressureNatural gas fuel supply pressure to generator fuel inlet11 to 14inches of water columnat generator fuel inlet
PressureOil pressure10-30psiengine running
Resistance057522 Low Coolant Level sensor resistance45 to 60ohmswith wire 85 disconnected, from sensor connector to body (ground)
Valve clearanceValve lash.002-.004
VoltageBattery charger / utility sensing voltage (red wire pcb pin #14 to #225A pcb pin #15)14-16vac
VoltageBattery voltage during cranking11volts DCminimum; below this recharge/replace battery
VoltageLine to line voltage (#T1 pcb pin #17 to #T2 pcb pin #16)208 or 240vacmust be line to line value
VoltagePCB #14 wire (J1-7) to ground (J1-13)greater than 10volts DCwhile engine is cranking
VoltagePCB #23 wire (J1-3) and #194 wire (J1-4)greater than 10volts DCin Auto
VoltagePCB #56 wire (J1-5) to #0 wire (J1-13)greater than 10volts DCwithin 5 seconds of placing unit to manual
VoltagePCB J1-14 (red wire) to J1-15 (#225A wire)greater than 12V ACin Auto; from secondary winding of utility sensing transformer
VoltageStarter contactor terminal voltage during cranking11-12volts DCduring cranking

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantlow silicate antifreezeCooling system should be completely drained and flushed. Only de-ionized water and low silicate anti-freeze and additives should be used. If not available use pre-mixed 50/50 low silicate antifreeze and low silicate supplemental additives. Do not over-concentrate; never exceed a 60/40 mixture. Anti-freeze should never be added to an engine without being mixed with water first.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

32
CodeNameMeaningSeverityAction
00OpenReason For Failure
01ShortedReason For Failure
02Missing / WrongReason For Failure
03Frozen / Tight / RoughReason For Failure
04Broken / CrackedReason For Failure
05Burnt / Bent / DistortedReason For Failure
06LeakReason For Failure
07Miswired / MisadjustedReason For Failure
08DefectiveReason For Failure
09Post Manuf. UpdateReason For Failure
10Dirty / CloggedReason For Failure
11LooseReason For Failure
12WeakReason For Failure
13NoisyReason For Failure
14Re-establish MagnetismReason For Failure
15Rebuilt StockReason For Failure
16New DefectiveReason For Failure
17PCB Timer WiringReason For Failure
99Other / MiscReason For Failure
AAlternatorPrimary Failure Code (What System?)
CPCB - Control CircuitryPrimary Failure Code (What System?)
DFuel SystemsPrimary Failure Code (What System?)
EEngine RelatedPrimary Failure Code (What System?)
FControl PanelPrimary Failure Code (What System?)
GGovernorPrimary Failure Code (What System?)
HIgnition SystemPrimary Failure Code (What System?)
LTransfer SwitchPrimary Failure Code (What System?)
OOil SystemPrimary Failure Code (What System?)
PGear BoxPrimary Failure Code (What System?)
SSheet MetalPrimary Failure Code (What System?)
WWater SystemPrimary Failure Code (What System?)
ZOther (Misc)Primary Failure Code (What System?)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Drive Belt Tension adjustment

⚠ On all new product make sure the belt tension is inspected before it is installed.

  1. Remove all covers and inspect belt for proper tensioning.
  2. Turn the two adjusting bolts until the compressed length of the springs is 5/8 inch (16mm).
Fuel Regulator Adjustment (hard starting GV410 gaseous fueled product) adjustment

⚠ Under no circumstances should this adjuster be completely removed.

⚠ A new freeze plug part # D2529 MUST be reinstalled to retain the tamperproof status of the regulator.

Tools: Spark tester, Feeler gauge

  1. Check for proper spark using a spark tester.
  2. Check for proper fuel supply to the regulator; 11 inches of water column should be available.
  3. Check valve lash; valves should be set between .002-.004.
  4. Verify the regulator is not stuck (manually choke the unit to start, then retry).
  5. Remove the freeze plug located directly above the inlet.
  6. Unscrew the threaded adjuster to achieve 5mm from the top of the adjuster screw to the top of the threaded casting.
  7. Start the generator a number of times until satisfied the condition is fixed.
  8. Reinstall a new freeze plug part # D2529 and mark an X across the freeze plug with a permanent marker.
Block Heater Test diagnostic

⚠ In multiple hairpin configurations, one hairpin can fail while the others remain functioning. Note the jumper position so they can be properly reassembled.

Tools: Phillips screwdriver (slip-joint pliers for explosion proof), Needle nose pliers or nut driver, Ohmmeter

  1. Disconnect the heater from the power source.
  2. For heaters with a thermostat, allow the coolant to cool below the thermostat range or remove the heater from the engine.
  3. Check for continuity with an ohmmeter between the element terminals inside the electrical box (remove all wires to avoid a false reading).
  4. If there is continuity through the element, check for continuity across the thermostat terminals (if applicable).
  5. If there is no continuity between the element or thermostat terminals the heater has failed; determine the cause of failure.
  6. If there is continuity through both the element and the thermostat, the heater is fine and the problem is improper installation, faulty wiring or an air pocket.
Check Oil Pressure diagnostic

Tools: Pressure gauge

  1. Remove plug or LOS switch from engine and install a pressure gauge.
  2. Start and run engine and note how much oil pressure you have.
GV410 Starter Pinion Jam Procedure diagnostic

⚠ New rubber bumper gets placed at base of block right above sump cover, and on the centerline of the starter.

Tools: Feeler gauge

  1. Measure the voltage at the starter contactor terminal; verify 11-12 volts DC during cranking.
  2. If below 11 volts DC, measure at the battery terminals during cranking; recharge/replace battery if below 11 volts DC.
  3. If battery voltage is above 11 volts DC, check for proper battery cable sizing.
  4. Manually engage the starter pinion into the ring gear and check for .020-.035 inch backlash, measuring at eight equally spaced locations.
  5. Shim or remove shims as necessary using shim kit part number 0D4791.
  6. Visually check that the starter motor is perpendicular to the ring gear; replace the starter motor if the mounting bracket is bent.
  7. Check position of rectangular rubber bumper part number 0C3794; older units used rubber dimples and should be replaced.
Procedure for Checking Control Board Number 76009A diagnostic

⚠ Record your measurements and include these findings on the Warranty Repair Report or the claim will be rejected.

⚠ Be careful when pushing the SW1 switch, there is LIVE voltage present on the PCB.

  1. With Auto/Off/Manual in Auto or Manual, check for battery voltage from wire #15A (J1-10) to wire #0 (J1-13); should be 12-14 VDC.
  2. IF STARTER DOES NOT CRANK: measure #56 wire (J1-5) to #0 (J1-13) within 5 seconds of placing unit to manual; should be greater than 10 VDC.
  3. If less than 10 VDC, remove #56 wire from J1 housing and re-measure across J1-5 to J1-13; if still less than 10 VDC, replace the board.
  4. Also check for a short to ground on wire #56 which could damage the board.
  5. IF STARTER CRANKS BUT UNIT DOES NOT COME UP TO SPEED: measure #14 wire (J1-7) to ground (J1-13) while cranking; should be greater than 10 VDC.
  6. If less than 10 VDC, remove #14 wire and re-measure J1-7 to J1-13; if still less than 10 VDC, replace the board.
  7. IN AUTO - UNIT DOES NOT TRANSFER AFTER UTILITY LOSS & 20 SECOND WARM-UP DELAY: measure #23 (J1-3) and #194 (J1-4); should be greater than 10 VDC.
  8. If not, remove #23 and #194 wires and re-measure J1-3 to J1-4; if less than 10 VDC, replace the board; also check for a short to ground on #194.
  9. IN AUTO - UNIT DOES NOT TRANSFER BACK TO UTILITY WHEN UTILITY VOLTAGE IS RESTORED: check voltage between J1-14 (red wire) and J1-15 (#225A wire); should be greater than 12 VAC.
  10. If utility is near rated (208 VAC or 240 VAC) and secondary is less than 12 VAC, check transformer wiring; if greater than 12 VAC and still no return, replace the board.
Test Method for Generac LOS - P/N 99236 diagnostic

Tools: Audible continuity meter, Air pressure source

  1. Apply 20 PSI air pressure to switch.
  2. Connect an audible continuity meter to the switch and ground.
  3. Release the air pressure and note the pressure when the meter sounds.
  4. Accept the part if the switch closes at the specified pressure; reject if it does not.
Testing the Battery Charger diagnostic

⚠ If the battery voltage measures greater than 13 volts it should be discharged to less than 12.6 volts.

Tools: Current meter, Voltmeter

  1. Set the exercise timer per the Owner's Manual (this sets the PCB to the zero reading).
  2. Remove the DC fuse from the control panel.
  3. Measure the DC voltage at the battery (+)(-) and record; if greater than 13 volts discharge it to less than 12.6 volts.
  4. Measure current across the fuse holder with the fuse removed (current flow should be into the battery, typically in the .5 amp range).
  5. If current cannot be measured, reinstall the fuse and measure battery voltage; over ten to fifteen minutes a slow increase should be seen.
Testing the Weekly Exercise Circuit diagnostic

⚠ Be careful when pushing the SW1 switch, there is LIVE voltage present on the PCB.

Tools: Non-conductive device (e.g., pencil eraser), Flashlight

  1. Remove the DC fuse from the control panel.
  2. Open the control panel front (be careful not to short any wiring).
  3. Remove the cover from the CMA box.
  4. Locate SW1 on the circuit board (76009-A) in the upper right corner.
  5. Install the fuse back in the control panel.
  6. Put the Auto-Off-Manual switch in the Auto position.
  7. Push and hold SW1 with a non-conductive device until the unit starts (about 30 seconds); the unit will run about 20 minutes then shutdown.
Setting the Exercise Timer operation

⚠ The exerciser will only work in the AUTO mode.

⚠ The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected.

⚠ The exerciser WILL NOT work if dip switch 2 (Remote Not Auto) is ON.

  1. Verify that the Auto/Off/Manual switch is set to AUTO.
  2. Hold down the set timer switch until the generator starts (approximately 10 seconds) and then release.
  3. The generator will start and run approximately seven (7) or twelve (12) minutes then shut down on its own; the exerciser is set to run at that time weekly.
LP Conversion - Air-cooled standby using 992cc V-Twin engine repair

⚠ The primary regulator for the propane supply is NOT INCLUDED with the generator.

Tools: Pipe thread sealant

  1. Turn off the main gas supply.
  2. Remove the three carburetor fuel hoses from the outlet ports of the demand regulator.
  3. Disconnect wire #0 and wire #14 from the gas solenoid on top of the demand regulator.
  4. Remove the demand regulator from the enclosure by rotating counterclockwise.
  5. Remove the small brass hose fitting from the idle circuit port of the regulator housing.
  6. Remove the small jet (0D5698A) located in the side of the regulator port on the regulator.
  7. Refit the brass hose fitting to the idle circuit port using pipe thread sealant.
  8. Identify both adjustment screws (one accessed from the front, one from the back).
  9. Reverse procedure steps 1-4 to reinstall the demand regulator.
  10. To run on LP fuel, turn both adjuster screws 1/4 turn clockwise.
  11. Make minor adjustments to the preset screw settings to achieve maximum power.
Re-positioning fuel hose between fuel solenoid and fuel regulator on the 1.5 liquid cooled Mitsubishi engine repair

⚠ Make sure you have clearance here (new mounting location).

  1. Remove M8 bolt from clamp located on the side of engine block.
  2. Reposition fuel hose and clamp to new mounting location on the timing belt case cover.
  3. Replace M8 bolt and tighten.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Generac 4077?

The Generac 4077 is rated 6 kW standby.

Which oil filter part number does the Generac 4077 take?

The Generac 4077 uses oil filter part number 070185.

Which air filter part number does the Generac 4077 take?

The Generac 4077 uses air filter part number 073111.

Troubleshooting

7

Symptoms & remedies

SymptomCauseRemedy
The generator cranks over for an excessive amount of time before starting, or does not start at all.Check for proper spark using a spark tester. Check for the proper fuel supply to the regulator, 11 inches of water column should be available to the generators regulator. Also check the valve lash for proper adjustment, valves should be set between .002-.004. A sticking regulator can also cause a no start, verify that the regulator is not stuck (manually choke the unit to start, then retry) If all this checks out an adjustment of the regulator can be made. The regulator is fitted with a freeze plug located directly above the inlet. This freeze plug must be removed. Under the plug is a threaded adjuster, which applies a spring pressure to the inlet seal. Unscrew the adjuster to achieve a dimension of 5mm from the top of the adjuster screw to the top of the threaded casting. Under no circumstances should this adjuster be completely removed. Start the generator a number of times until you are satisfied that the condition is fixed. A new freeze plug part # D2529 MUST be reinstalled in to the regulator to retain the tamperproof status of the regulator. As an identification that the regulator has been adjusted put an X across the freeze plug with a permanent marker.
Starter pinion jammed into flywheel on initial cranking.Measure the voltage at the terminal of the starter contactor and verify 11-12 volts DC is available to the generator during cranking. If voltage is below 11 volts DC, measure at the battery terminals during cranking. If battery voltage is below 11 volts DC, recharge/replace battery. If battery voltage is above 11 volts DC, check for proper battery cable sizing, see owners manual. Manually engage the starter pinion into to ring gear on the flywheel and check for .020-.035 inch backlash. When checking backlash, measure at eight equally spaced locations and make sure the gear teeth are in contact in the direction of rotation. Shim or remove shims as necessary, use shim kit part number 0D4791. Visually check that the starter motor is perpendicular to the ring gear. Replace the starter motor if the starter motor mounting bracket is bent. Check for proper position of rectangular rubber bumper part number 0C3794. Older units used rubber dimples, they should be replaced if jamming is occurring. New rubber bumper gets placed at base of block right above sump cover, and on the centerline of the starter.
The exercise function on some units may be accelerated by approximately 5 minutes per week.It is recommended that the customer reset the exercise timer after performing the monthly battery inspection, as outlined in the maintenance schedule.
The heater has been subjected to an air pocket preventing the coolant from circulating.Although the heated coolant can’t circulate, the heater thermostat continues to turn the heater on and off. The engine will then cool down, activating the low coolant temperature alarm.The engine should be thoroughly ‘purged’ to eliminate any air pockets before the heater is energized. We recommend running the engine up to operating temperature to open the engine thermostat after the installation. This will insure that no air pockets are left within the cooling system. Also check the outlet hose and make sure there is no point in the line where it flows down. Remember that heat rises and a downward trend will stop the flow of hot water.
The heater (Fig. 5,6 ) was actually mounted with the outlet facing sideways.In the pictures it can be seen that the coolant never reached the top portion of the tank. This exposes the hairpins to air and eliminates the heaters ability to ‘pull’ cold coolant from the engine.It is critical that the heater is completely full of coolant at all times. This means the outlet of the heater must be at the highest point of the heating system for it to work correctly.
Over-concentration of coolant will cause a gel-like slime to accumulate on the element.In severe cases, it may burn on the element causing a black sludge to form. Over-concentration of additives will cause a similar slime, but usually in a different color.
Insufficient Natural Gas fuel pressure supplied to the generator.Eleven to fourteen inches of water column pressure must be supplied to the generator.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

9
Part #DescriptionQtySystem
070185FILTER, OIL1Oil filter Amazon eBay $30.00 NAPA $3.59 FridayParts $45.99
072347SPARK PLUG2Spark plug eBay $1.99
073111FILTER, AIR1Air filter Amazon eBay
075281SWITCH, HIGH TEMPERATURE1Sensor Amazon eBay $39.00
081646PRE-CLEANER, AIR FILTER1Air filter Amazon eBay $11.17
099236Switch Oil Pressure Switch 8 PSI 1 Pole1Sensor eBay $9.98 FridayParts $11.41
0A46000SRVCarburetor Repair Kit (GN410)Service part / kit buy
0A7336BCARBURETOR, GN 410 L/P1Service part / kit eBay
0C1537ASSY HME STNDBY CNTR1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Service manual — c8495 (Generac)

This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Oil filter 070185$3.59
1 priced item$3.59