Home›Repair guides›Generac›LP Conversion - Air-cooled standby using 992cc V-Twin engine

Generac — LP Conversion - Air-cooled standby using 992cc V-Twin engine

Repair & overhaul · Fuel system / demand regulator

From a Generac service manual covering: 4077, 4079, 4109, 4389, 4390, 4456, 4674, 4675. Check it applies to your exact model before use.

Applies to: Generac 4077, Generac 4079, Generac 4109, Generac 4389, Generac 4456

Before you start

  • The primary regulator for the propane supply is NOT INCLUDED with the generator.

Procedure

  1. Turn off the main gas supply.
  2. Remove the three carburetor fuel hoses from the outlet ports of the demand regulator.
  3. Disconnect wire #0 and wire #14 from the gas solenoid on top of the demand regulator.
  4. Remove the demand regulator from the enclosure by rotating counterclockwise.
  5. Remove the small brass hose fitting from the idle circuit port of the regulator housing.
  6. Remove the small jet (0D5698A) located in the side of the regulator port on the regulator.
  7. Refit the brass hose fitting to the idle circuit port using pipe thread sealant.
  8. Identify both adjustment screws (one accessed from the front, one from the back).
  9. Reverse procedure steps 1-4 to reinstall the demand regulator.
  10. To run on LP fuel, turn both adjuster screws 1/4 turn clockwise.
  11. Make minor adjustments to the preset screw settings to achieve maximum power.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • LP fuel pressure to fuel inlet: 11 to 14 inches of water column (0.6 psi)

Full service-parts list: Generac 4077 →, Generac 4079 →, Generac 4109 →, Generac 4389 →, Generac 4456 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →