HomeFG WilsonFG Wilson PG1250B2

FG Wilson PG1250B2 Generator Set

The FG Wilson PG1250B2 is a 1000 kW (1250 kVA) LPG, Nat Gas standby generator set powered by a Perkins 4016-61TRS2 engine. It is available at 380 V and 415 V, 3-phase and 50 Hz. It holds 330 L (87.2 gal) of coolant, with a maximum ambient rating of 50 °C. The set measures 6340×2100×3370 mm (249.6×82.7×132.7 in) and weighs about 5820 kg (12831 lb). The same 4016-61TRS2 engine also powers generator sets from Perkins.

1000 kW
Standby
61.123 L
Displacement
1
Document types

How to read your FG Wilson serial & model number →

Specifications

FuelLPG, Nat Gas
Frequency50.0 Hz
Standby power1000 kW
Standby kVA1250
Prime power1000 kW
ControllerPowerWizard 2
AlternatorLeroy-Somer LL8224P
Voltage options380 V, 415 V
Phase3 Phase
Power factor0.8
Circuit breaker2000 A
Coolant capacity330 L
Max ambient50 °C
Dimensions (L×W×H)6340×2100×3370 mm
Dry weight5820 kg

Engine

Perkins 4016-61TRS2
Displacement61.123 L
AspirationTurbocharged
Rated speed1500 rpm

Maintenance & consumables

for the Perkins 4016-61TRS2
ItemSpecCapacityPart #Interval
OilSee Perkins Service Bulletin 48

Common questions

What is the power rating of the FG Wilson PG1250B2?

The FG Wilson PG1250B2 is rated 1000 kW standby (1250.0 kVA).

What engine does the FG Wilson PG1250B2 use?

The FG Wilson PG1250B2 is powered by the Perkins 4016-61TRS2 engine.

What fuel does the FG Wilson PG1250B2 use?

The FG Wilson PG1250B2 runs on LPG, Nat Gas.

What alternator does the FG Wilson PG1250B2 use?

The FG Wilson PG1250B2 uses a Leroy-Somer LL8224P alternator.

Fuel consumption

RatingLoadL/hgal/h
Prime30%273.09599.0

Available documents

Spec sheet — Gas ratings summary(ES)(0112) (FG Wilson)Spec sheet — Gas ratings summary(GB)(0112) (FG Wilson)Spec sheet — Gas ratings summary(GB)(0114) (FG Wilson)Spec sheet — Gas ratings summary(IT)(0112) (FG Wilson)Spec sheet — Gas+ratings+summary(GB)(1110) (FG Wilson)

Other sets with this engine