Specifications
| Frequency | 50.0 Hz |
|---|---|
| Standby power | 80 kW |
| Standby kVA | 100 |
| Prime power | 80 kW |
| Alternator | LL3014B |
| Voltage options | 380 V, 415 V |
| Phase | 1 |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 2370×735×1381 mm |
| Dry weight | 1167 kg |
| Sound level | 63.1 dBA @ 15 m |
| Fuel tank | 227.0 L |
Engine
| Displacement | 4.4 L |
|---|---|
| Aspiration | Turbocharged Air to Air Charge Cooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the FG Wilson P100P1?
The FG Wilson P100P1 is rated 80 kW standby (100.0 kVA).
What engine does the FG Wilson P100P1 use?
The FG Wilson P100P1 is powered by the Perkins 1104C-TAG2 engine.
What alternator does the FG Wilson P100P1 use?
The FG Wilson P100P1 uses a LL3014B alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 26.3 | 7.7 | |
| Standby | 29.3 | 7.7 |