| AUXILIARY INPUTS | Auxiliary Inputs | Auxiliary inputs can be user configured and will display the message as written by the user. | Warning | |
| BATTERY OVER VOLTAGE | Battery Over Voltage | The DC supply has risen above the high volts setting level for the duration of the high battery volts timer. | Warning | |
| BATTERY UNDER VOLTAGE | Battery Under Voltage | The DC supply has fallen below the low volts setting level for the duration of the low battery volts timer. | Warning | |
| CAN ECU ERROR | CAN ECU Error | The engine ECU has detected a warning alarm and has informed the DSE module. The exact error is also indicated on the module's display. | Warning | |
| CHARGE FAILURE | Charge Failure | The auxiliary charge alternator voltage is low as measured from the W/L terminal. | Warning | |
| EARTH FAULT | Earth Fault | The measured Earth Fault Current has been in excess of the earth fault trip and has surpassed the IDMT curve of the Earth Fault alarm (DSE7310 V2.0 or above only). | Warning | |
| ECU WARNING | ECU Warning | The engine ECU has detected a warning alarm and has informed the DSE module. The exact error is also indicated on the module's display. | Warning | |
| ENGINE HIGH TEMPERATURE | Engine High Temperature | The engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired. | Warning | |
| ENGINE LOW TEMPERATURE | Engine Low Temperature | The engine coolant temperature has fallen below the high engine temperature pre-alarm setting level. | Warning | |
| FAIL TO STOP | Fail To Stop | The module has detected a condition that indicates that the engine is running when it has been instructed to stop. Could indicate a faulty oil pressure sensor or switch. | Warning | If the engine is at rest check oil sensor wiring and configuration. |
| FUEL USAGE | Fuel Usage | Indicates the amount of fuel measured by the fuel level sensor is in excess of the Fuel Usage alarm settings. Often indicates a fuel leak or potential fuel theft. | Warning | |
| GENERATOR OVER FREQUENCY | Generator Over Frequency | The generator output frequency has risen above the pre-set pre-alarm setting. | Warning | |
| GENERATOR OVER VOLTAGE | Generator Over Voltage | The generator output voltage has risen above the pre-set pre-alarm setting. | Warning | |
| GENERATOR UNDER FREQUENCY | Generator Under Frequency | The generator output frequency has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. | Warning | |
| GENERATOR UNDER VOLTAGE | Generator Under Voltage | The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. | Warning | |
| LOADING FREQUENCY NOT REACHED | Loading Frequency Not Reached | The generator frequency is not above the configured loading frequency. The generator will not take load when the alarm is present after the safety timer. | Warning | |
| LOADING VOLTAGE NOT REACHED | Loading Voltage Not Reached | The generator voltage is not above the configured loading voltage. The generator will not take load when the alarm is present after the safety timer. | Warning | |
| LOW FUEL LEVEL | Low Fuel Level | The level detected by the fuel level sensor is below the low fuel level setting. | Warning | |
| LOW OIL PRESSURE | Low Oil Pressure | The engine oil pressure has fallen below the low oil pressure pre-alarm setting level after the Safety On timer has expired. | Warning | |
| OVERSPEED | Overspeed | The engine speed has risen above the overspeed pre alarm setting. | Warning | |
| PROTECTIONS DISABLED | Protections Disabled | Shutdown and electrical trip alarms can be disabled by user configuration; the alarm text is displayed but the engine will continue to run. Available from V4 onwards. | Warning | |
| UNDERSPEED | Underspeed | The engine speed has fallen below the underspeed pre alarm setting. | Warning | |
| kW OVERLOAD | kW Overload | The measured Total kW is above the setting of the kW overload warning alarm. | Warning | |