Cummins/Onan YD series Generator Set

The Cummins/Onan YD series is a 6 kW standby generator set powered by a Cummins/Onan J block (Series JB/JC) engine. It is available at 50/60 V. It holds about 3.5 L (0.9 gal) of oil, with a maximum ambient rating of 120 °C. Starting uses group-74 battery at 12 V.

6 kW
Standby
1.2 L
Displacement
3.5 L
Oil capacity
1
Document types

How to read your Cummins/Onan serial & model number →

Service parts for the YD series

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required
145-289-000Air filtersee priceAmazon

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Standby power6 kW
Prime power6 kW
Oil capacity3.5 L
AlternatorYD (4-pole)
Voltage options50/60 V
Battery group74
Battery voltage12 V
Max ambient[120] °C

Engine

Cummins/Onan J block (Series JB/JC)
Displacement1.2 L
Aspirationair cooled
Rated speed1500 rpm

Maintenance & consumables

for the Cummins/Onan J block (Series JB/JC)
ItemSpecCapacityPart #Interval
Air filterAIR CLEANER FILTER ELEMENT145-289-000 Amazon eBay
Fuel filterfuel filter—1000 hr
Oil filteroil filter—500 hr
Batterybattery charge rate adjusting resistor—1200 hr
Beltcrankcase breather—1000 hr
Coolant—1000 hr
Oilcrankcase oil3.5 quarts—500 hr
Spark plugignition breaker points (Series JB) or distributor (Series JC)—500 hr

Service intervals

15
ItemActionHoursMonthsNotes
Exhaust systemInspect8 hrDaily
Generator setInspect8 hrDaily
Air cleanerCheck50 hr
BatteryCheck50 hrCheck condition of the battery
Crankcase oilChange100 hrFirst service — Change crankcase oil after the first 50 hours
Fuel filterClean100 hrFuel filter sediment bowl
Governor linkageClean100 hrClean and adjust (governor rod ball joints)
Crankcase breatherReplace200 hrSeries JB
GeneratorClean200 hrClean the generator
Ignition breaker pointsAdjust200 hrSeries JC; clean and adjust
Spark plugCheck200 hrCheck the spark plug gap
PCV valveClean500 hrSeries JC
Starter disconnect breakerReplace500 hrService the starter disconnect breaker
Oil panClean1000 hrRemove and clean the oil pan
ValvesAdjust1000 hrGrind the valves if necessary - contact an authorized Onan dealer

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

16
TypeItemValueUnitCondition
GapIgnition breaker point gap0.018-0.022in (0.46-0.58 mm)
GapIgnition breaker point gap0.019-0.021in (0.48-0.53 mm)
GapSpark plug gap0.025in (0.64 mm)
GapSpark plug gap0.035in (0.89 mm)
GapStarter disconnect breaker point gap0.020in (0.51 mm)
OtherDistributor rotationClockwise
OtherFiring order1-2-4-3
OtherIgnition timing (gas and combination gas/gasoline)35degrees BTC at 1800 RPMat 1800 RPM
OtherIgnition timing (gasoline)25degrees BTC at 1800 RPMat 1800 RPM
SpeedDwell angle48-54degrees
TorqueCylinder head bolt torque28-30ft-lbs (38-41 N m)
TorqueGenerator diode stud torque25ft-lbs (33 Nm)
Valve clearanceValve clearance - exhaust (gas and combination gas/gasoline)0.020in (0.51 mm)Cold, crank at 10-45 degrees ATC on power stroke
Valve clearanceValve clearance - exhaust (gasoline)0.015in (0.38 mm)Cold, crank at 10-45 degrees ATC on power stroke
Valve clearanceValve clearance - intake (gas and combination gas/gasoline)0.013in (0.33 mm)Cold, crank at 10-45 degrees ATC on power stroke
Valve clearanceValve clearance - intake (gasoline)0.012in (0.30 mm)Cold, crank at 10-45 degrees ATC on power stroke

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilSAE viscosity grades per ambient temperature chart (10W-30, 10W-40, 20W-40, 20W-50, 30 shown on chart)API service classification SF or SF/CC; must have passed MS Sequence Tests (or ASTM G-IV Sequence Tests); do not use Service DS oil3.5 quartsIncludes 0.5 quarts (0.47 l) for the oil filter. Viscosity chart temperature range shown as -20 to 100 F.
FuelGasoline/propane/natural gasHigh compression pistons are necessary for full rated output on natural gas.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

11
Battery Charge Rate Adjustment maintenance

⚠ Batteries emit highly explosive hydrogen gas. Never smoke near a battery, and keep sparks, flames and other sources of ignition away.

  1. Locate the battery charge rate adjusting resistor in the outlet of the generator cooling blower.
  2. Shut down the set before adjusting the slide tap.
  3. Adjust the slide tap up to increase the charge rate if necessary to maintain a specific gravity of at least 1.260.
  4. Keep battery terminals clean and tight; apply a light coat of vaseline to retard corrosion.
  5. Fill the cells with distilled water to keep the electrolyte level up to the split rings.
Generator Rectifier Cleaning maintenance

Tools: Filtered low pressure compressed air, Torque wrench

  1. Remove the generator end cover for access to the rotating rectifiers.
  2. Use filtered, low pressure compressed air to blow away accumulated dust on the diodes.
  3. Torque the diode studs to 25 ft-lbs (33 Nm).
Oil Change maintenance

⚠ Hot oil can cause burns. Shut down the set before checking the oil level to prevent hot oil from blowing out on you.

  1. Drain the crankcase oil while the engine is still hot.
  2. Refill with oil of the correct API designation and SAE viscosity grade suitable for the ambient temperature.
Oil Filter Installation maintenance
  1. Lightly oil the gasket.
  2. Turn the filter on by hand until the gasket just touches the block.
  3. Tighten 1/2 turn more.
Out-of-Service Protection maintenance
  1. Perform all scheduled maintenance.
  2. Change the oil and attach a tag indicating the viscosity grade.
  3. Pour one ounce of rust inhibiting oil (or SAE Grade 10) into each cylinder, crank the engine several times and replace the spark plugs.
  4. Plug the exhaust outlet to prevent the entrance of insects, dust and moisture.
  5. Lightly wipe with grease or oil metal parts that would otherwise rust.
  6. Disconnect the battery (negative [-] cable first) and store it following standard procedures.
  7. Cover the set to protect it from dust and moisture.
Returning an Out-of-Service Set to Service maintenance
  1. Unplug the exhaust and remove the protective cover.
  2. Change the oil if the viscosity grade recorded on the tag is not suitable for the current ambient temperature.
  3. Service the battery and connect it (negative [-] cable last).
  4. See Operation for starting and operating the set.
Break-in Procedure operation

⚠ Running the set continuously with less than 1/2 full rated load during the first hundred hours can result in poor seating of the piston rings and consequent problems with ring blowby and high oil consumption.

  1. Connect 1/2 of the full rated load for the first half hour of operation.
  2. Connect 3/4 of the full rated load for the next half hour of operation.
  3. Operate with the full rated load connected any time thereafter.
  4. Drain and replace the engine oil after the first 50 hours of operation.
Combination Gas/Gasoline Sets operation
  1. Select the fuel to be used and close the supply valve for the other fuel.
  2. Engage the choke lock wire to keep the choke open when using gas fuel and release it when using gasoline.
Connecting the Load operation

⚠ Overloading can cause the generator to overheat and fail. The load may exceed the nameplate rating only momentarily, such as during the starting of a large motor.

  1. When possible, allow the set to warm up before connecting the full load.
  2. When possible, connect the load in steps.
  3. Occasionally connect the full rated load to burn off carbon deposits formed in the exhaust system during light-load operation.
Starting operation

⚠ Pressure cooled engines can quickly overheat and be damaged if run without the front air shroud/access cover in place.

  1. Check the fuel and oil levels.
  2. Make sure all the air shrouds and service access covers are in place.
  3. Press the START/STOP switch to START until the engine starts; the starter is disengaged automatically by the start disconnect switch.
  4. Do not crank for more than 30 seconds at a time; allow 60 seconds between cranks.
  5. A new set may not start right away if spark plug electrodes are coated by rust inhibiting oil; remove spark plugs and clean the oil off.
  6. The oil pressure gauge should indicate at least 20 psi.
  7. Connect the load and follow the break-in procedure for initial start-up.
Stopping operation
  1. Disconnect the load and let the generator set run for 10 minutes to cool off.
  2. Press the START/STOP switch to STOP until the engine stops.
  3. If a safety circuit stops the engine (high engine temperature or low oil pressure), determine the cause and service or repair before returning the set to service.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
110/1903V150 Hz; decoded from Figure 3-4 (OCR degraded)
110/2201V150 Hz; decoded from Figure 3-4 (OCR degraded)
115/2301V250 Hz; decoded from Figure 3-4 (OCR degraded)
118/2003V450 Hz; decoded from Figure 3-4 (OCR degraded)
120/2083V160 Hz; decoded from Figure 3-4 (OCR degraded)
120/2401V160 Hz; decoded from Figure 3-4 (OCR degraded)
120/2401V350 Hz; decoded from Figure 3-4 (OCR degraded)
127/2203V450 Hz; decoded from Figure 3-4 (OCR degraded)
139/2403V460 Hz; decoded from Figure 3-4 (OCR degraded)
230/4003V250 Hz; decoded from Figure 3-4 (OCR degraded)
240/4163V350 Hz; decoded from Figure 3-4 (OCR degraded)
254/4403V260 Hz; decoded from Figure 3-4 (OCR degraded)
254/4403V450 Hz; decoded from Figure 3-4 (OCR degraded)
277/4803V360 Hz; decoded from Figure 3-4 (OCR degraded)
347/6003V460 Hz; decoded from Figure 3-4 (OCR degraded)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Cummins/Onan YD series?

The Cummins/Onan YD series is rated 6 kW standby.

What engine is in the Cummins/Onan YD series?

The Cummins/Onan YD series is powered by the Cummins/Onan J block (Series JB/JC) engine.

What is the oil capacity of the Cummins/Onan YD series?

The Cummins/Onan YD series has an engine oil capacity of 3.5 liters (3.7 US quarts), per the manufacturer specification sheet.

What voltage does the Cummins/Onan YD series produce?

The Cummins/Onan YD series is offered in 50/60 V.

Which alternator is fitted to the Cummins/Onan YD series?

The Cummins/Onan YD series uses a YD alternator. It has 4 poles.

What air filter does the Cummins/Onan YD series use?

The Cummins/Onan YD series uses air filter part number 145-289-000.

Repair guides

5

Step-by-step procedures compiled from the Cummins/Onan service manual for this model.

Parts

4
Part #DescriptionQtySystem
145-289-000AIR CLEANER FILTER ELEMENT1Air filter Amazon eBay
145-367-000BATTERY CHARGE RATE ADJUSTING RESISTOR1Service part / kit Amazon eBay
42-1817FLEXIBLE CONDUIT1Service part / kit Amazon eBay
967-0120Safety Precautions ManualService part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
100%4.71.24

Available documents

Owner's manual — 967-0120 Onan JB JC Genset Operators manual (06-1989) (Cummins/Onan)Service manual — 967-0120 Onan JB JC Genset Operator's manual (06-1989) (Onan)