Cummins/Onan OTPC Generator Set

The Cummins/Onan OTPC is a generator set. It is available at 120 V, 190 V, 208 V, 220 V, 240 V, 380 V, 416 V, 440 V, 480 V and 600 V, single-phase.

4
Document types

How to read your Cummins/Onan serial & model number →

Specifications

Voltage options120 V, 190 V, 208 V, 220 V, 240 V, 380 V, 416 V, 440 V, 480 V, 600 V
Phase1 Phase, 2-W or 3-W,3 Phase, 3-W or 4-W

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter—
Battery—
Belt—
Coolant—
Oil—
Spark plug—

Service intervals

9
ItemActionHoursMonthsNotes
Batteries (3V lithium) in Digital Module and Network ModuleReplace24 moReplace batteries every two years.
Buswork and supporting hardwareInspect12 moCheck for carbon tracking, cracks, corrosion, or other deterioration.
Buswork, control wiring, power cables, system hardwareOther12 moTighten as necessary. Hardware torque values are given in section 5.
Cabinet exterior surfacesClean12 moWash with damp sponge (mild detergent and water); do not allow water to enter the cabinet.
Cable lug connectionsOther12 moRetorque all cable lug connections. Lug torque requirements are listed in Table 3-1.
Control wiring and power cablesInspect12 moCheck for signs of wear or deterioration and for loose connections (especially wiring between or near hinged door).
Controls, meters, switching mechanism components, interior buswork, connecting lugsClean12 moAnnual planned maintenance; thoroughly dust and vacuum.
Stationary and movable contactsInspect12 moIf contact replacement is necessary, see section 5.
System hardwareInspect12 moCheck cabinet interior for loose hardware; tighten as indicated.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

31
TypeItemValueUnitCondition
ResistanceClosed membrane switch resistance0 to 200ohmsdepending on how hard you press; measured between switch common (pin 10) and each switch
TorqueActuator mounting capscrews to block/switch assemblies (40-125 A)25-30in-lbs (2.8-3.4 Nm)
TorqueActuator mounting capscrews to switch assemblies (150-260 A)25-27in-lbs (2.8-3.0 Nm)
TorqueActuator rod end assembly capscrew70-75in-lbs (7.9-8.5 Nm)
TorqueArc chute to block assembly (800-1000 A)15-20in-lbs (1.7-2.3 Nm)
TorqueAuxiliary switches to bracket10-15in-lbs (1.1-1.7 Nm)
TorqueBlock and cross-bar assembly to base (150-260 A)70-75in-lbs (7.9-8.5 Nm)
TorqueBlock assembly to base screws (40-125 A)25-30in-lbs (2.8-3.4 Nm)
TorqueInterlock arm round head capscrews (150-260 A)15-20in-lbs (1.7-2.3 Nm)
TorqueInterlock arm to block assembly (300-600 A)70-75in-lbs (7.9-8.5 Nm)
TorqueInterlock bar machine screws (40-125 A)15-20in-lbs (1.7-2.3 Nm)
TorqueJumper bus bars to block assembly (300-600 A)10-12ft-lbs (13.6-16.3 Nm)
TorqueJumper bus bars to load bus bars (800-1000 A)10-12ft-lbs (13.6-16.3 Nm)
TorqueJumper bus bars to switch assemblies (800-1000 A)18-20ft-lbs (24.4-27.1 Nm)
TorqueLug set screw, 1/2 inch socket (across flats)500in-lbs (57 N-m)minimum torque for proper operation
TorqueLug set screw, 1/4 inch socket (across flats)200in-lbs (23 N-m)minimum torque for proper operation
TorqueLug set screw, 3/16 inch socket (across flats)80in-lbs (9 N-m)minimum torque for proper operation
TorqueLug set screw, 3/8 inch socket (across flats)375in-lbs (43 N-m)minimum torque for proper operation
TorqueLug set screw, 5/16 inch socket (across flats)275in-lbs (31 N-m)minimum torque for proper operation
TorqueLug set screw, 9/16 inch socket (across flats)600in-lbs (68 N-m)minimum torque for proper operation
TorqueLug terminals (150-260 A)10-12ft-lbs (13.6-16.3 Nm)
TorqueLug terminals (800-1000 A)28-33ft-lbs (40.0-44.7 Nm)
VoltageBattery charger float voltage, 12 volt NiCad batteries14voltsfloat voltage adjustment
VoltageBattery charger float voltage, 12 volt lead acid batteries13.2voltsfloat voltage adjustment
VoltageBattery charger float voltage, 24 volt NiCad batteries28voltsfloat voltage adjustment
VoltageBattery charger float voltage, 24 volt lead acid batteries26.4voltsfloat voltage adjustment
VoltageLow controller battery fault threshold (Lithium batteries)5.2VDCcontroller sets fault status to active
VoltagePower Module 1 & 2 relay output CR3, CR4, CR520-30VDCat J11-29
VoltagePower Module 1 Source 1 transformer input NA/NB/NC3VDCat J11-1, J11-3, J11-5; use J12-13 for DC ground
VoltagePower Module 2 Source 1 transformer input NA/NB/NC18VACat J11-1&2, J11-3&4, J11-5&6
VoltageRegulated DC output, Power Module 1 and 210VDCat J18, J19; use only one source when checking

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
GreaseOnan part number 524-0157Lubricant applied as a thin coat to the slot in the handle.
OtherLoctite 242 (blue thread sealant)Onan part number 518-0309. Applied to interlock bar machine screw threads.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

7
CodeNameMeaningSeverityAction
1113ATS Fail to Close: TransferA transfer between Source 1 and Neutral failed or the allotted transfer time was exceeded. The controller automatically retries to close the switch every 30 seconds.Press the Reset button on the front panel. Refer to the fault definitions and Table 5-5.
1114ATS Fail to Close: RetransferA transfer between Source 2 and Neutral failed or the allotted retransfer time was exceeded. The controller automatically retries to close the switch every 30 seconds.Press the Reset button on the front panel. Refer to the fault definitions and Table 5-6.
1468Network Communications ErrorThe Network Control Module (NCM) indicates that a network communications error has occurred; the device is no longer communicating with other devices on the network.Press the Reset button on the front panel.
343Controller Checksum ErrorThe checksum of the Flash EPROM does not match the checksum stored in the controller.Reset the control by removing power (including the batteries). If checksum error is repeated on power up, replace the Digital Module.
441Low Controller BatteryLow Lithium battery voltage; the controller sets the fault status to active when battery voltage drops to 5.2 VDC.Replace controller batteries. Press the Reset button on the front panel. Reset real-time clock.
477Network Battery LowThe Network Control Module (NCM) indicates that the network battery voltage is low.Replace the Network Module batteries. Press the Reset button on the front panel.
597Battery Charger MalfunctionThe battery charger status signal indicates a fault condition.Press the Reset button on the front panel. Check the battery charger fuse(s). Replace, if necessary, with fuses of the correct rating. Refer to the fault definitions.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Membrane Switch Test diagnostic

Tools: Ohmmeter

  1. Remove the connector from J25 on the Digital Module circuit board.
  2. Press the switch down and measure the resistance between the switch common (pin 10) and each switch at the solder points on the connector.
  3. The resistance of a closed membrane switch should be in the range of 0 to 200 ohms depending on how hard you press.
  4. Attach the connector to J25.
  5. Close and lock the enclosure door.
Power Module Test diagnostic

Tools: Wiring break-out tool (34 pin) contained in the Cummins PCC Tool Kit, P/N 3824746

  1. When a Power Module failure occurs, the most common part to fail is the transformer.
  2. Use a 34-pin wiring break-out tool to measure J11 test points.
  3. Check the Source 1 and Source 2 transformer inputs and the regulated DC output at J18/J19.
  4. Check the CR3, CR4, CR5 output of 20-30 VDC at J11-29.
Planned Maintenance maintenance

⚠ The transfer switch presents a shock hazard that can cause severe personal injury or death unless all AC power is removed.

⚠ Ignition of explosive battery gases can cause severe personal injury. Do not smoke or cause any spark, arc, or flame while servicing batteries.

  1. Disconnect all sources of AC power; turn the genset operation selector switch to Stop; disconnect the battery charger and the starting battery (negative lead first).
  2. Thoroughly dust and vacuum all controls, meters, switching mechanism components, interior buswork, and connecting lugs.
  3. Close the cabinet door and wash exterior surfaces with a damp sponge (mild detergent and water); do not allow water to enter the cabinet.
  4. Check buswork and supporting hardware for carbon tracking, cracks, corrosion, or deterioration.
  5. Check stationary and movable contacts.
  6. Check system hardware, control wiring, and power cables for loose connections, wear, or deterioration.
  7. Tighten buswork, control wiring, power cables, and system hardware as necessary; retorque all cable lug connections.
  8. Service or replace the 3V lithium batteries in the Digital Module and the Network Module; replace every two years.
  9. Connect the set starting battery (negative lead last); reconnect normal AC power and verify battery charger operation.
  10. Test system operation; close and lock the cabinet door.
Generator Set Start Test operation
  1. Set the Test With/Without Load variable to the Without Load value.
  2. Press the Test switch. The generator set should start and run.
  3. At the end of the test period, press the Test switch again. The generator stops.
  4. In anticipation of scheduled exercise, set the With/Without Load variable to the desired value.
Manual Operation operation

⚠ Manual operation of the transfer switch under load presents a shock hazard that can cause severe personal injury or death. Do not attempt to operate switch manually when under load.

⚠ Automatic transfer switch operation results in rapid movement of the manual operator handles. Keep hands clear of handles when switching back to automatic operation.

  1. Open the cabinet door of the ATS.
  2. Move the Motor Disconnect switch to the Off position.
  3. Transfer from Source 1 to Source 2: pull the upper manual operator handle down, then push the lower manual operator handle down.
  4. Retransfer from Source 2 to Source 1: pull the lower manual operator handle up, then push the upper manual operator handle up.
  5. Move the Motor Disconnect switch to the Auto position.
  6. Close the cabinet door.
With-Load Standby System Test operation
  1. Set the Test With/Without Load variable to the With Load value.
  2. Press the Test switch. The generator set should start and assume the load after the transfer time delay.
  3. Press the Test switch again to retransfer load back to Source 1 after the retransfer time delay.
  4. To bypass the retransfer time delay and cause immediate load retransfer, press the Override switch. The generator stops after the stop time delay.
Auxiliary Switch Removal and Replacement (40 to 125 Amperes) repair

⚠ AC power within the cabinet presents an electrical shock hazard. Disconnect all sources of AC power from the transfer switch before servicing.

  1. Open the cabinet door and remove the four machine screws securing the plastic switch cover.
  2. Loosen the two machine screws securing the terminal bracket to the base and move the bracket for access.
  3. Remove the control wiring leads from the auxiliary switch terminals.
  4. Remove the hex head machine screws securing the auxiliary switch assembly bracket to the base.
  5. Disengage the auxiliary switch lever from the transfer switch crossbar and lift out the assembly.
  6. Remove the hex head machine screws and nuts securing the auxiliary switches to the bracket; lift out the four switches, insulating barriers, and switch lever.
  7. Place the auxiliary switch lever in the bracket (end with the octagonal hole engages the crossbar).
  8. Install the auxiliary switches (4) and insulating barriers (5) in the bracket; secure with hex head machine screws (2) and nuts (2); tighten to 10-15 in-lbs (1.1-1.7 Nm).
  9. Manually close the contacts coupled to the auxiliary switch lever and check lever alignment when the switch is closed.
  10. Secure the bracket to the base with hex head machine screws; tighten to 25-30 in-lbs (2.8-3.4 Nm).
  11. Install control wiring leads on the corresponding switch terminals; place the terminal bracket and tighten to 25-30 in-lbs.
  12. Secure the plastic switch cover and tighten to 25-30 in-lbs (2.8-3.4 Nm).
  13. Reconnect the starting battery and power sources; test the switch for proper operation and close the cabinet.
Block and Cross-Bar Assembly Removal and Replacement (40 to 125 Amperes) repair

⚠ AC power within the cabinet presents an electrical shock hazard. Disconnect all sources of AC power from the transfer switch before servicing.

  1. Remove the linear actuator as described for 40-125 ampere switches (steps 1-6 of Removing Actuator).
  2. Remove the interlock bar from the interlock arms.
  3. Disconnect the control wiring leads from the jumper bus bars.
  4. Remove the hardware securing the jumper bus bars to the load bus bars and lift off the jumper bus bars.
  5. Remove the control wiring leads from the power source terminals and remove the power source supply wires from the lug terminals.
  6. Remove the two round head machine screws, lock washers, and flat washers securing the block assembly to the base; remove the assembly.
  7. Clean all current-carrying surfaces with a wire brush.
  8. Hold the block assembly in position and check alignment of the auxiliary switch lever; it must be aligned vertically when contacts are closed.
  9. Secure the block assembly to the base with round head machine screws (2), lock washers (2), and flat washers (2); tighten to 25-30 in-lbs (2.8-3.4 Nm).
  10. Install power source supply wires, control wiring to power source terminals, and the jumper bus bars with electrical joint compound; tighten as specified.
  11. Apply thread sealant (Loctite 242, P/N 518-0309) to the interlock bar machine screws; install and tighten to 15-20 in-lbs (1.7-2.3 Nm).
  12. Attempt to close both sides of the transfer switch; the interlock assembly must hold one side open.
  13. Replace the linear actuator per steps 2 through 8 of Replacing Actuator; apply lubricant (P/N 524-0157) to the slot in the handle.
  14. Test the switch for proper operation and close the cabinet.
Digital Board Replacement repair

⚠ AC power within the cabinet and the inside of the cabinet door presents a shock hazard. Remove power to the door by disconnecting connector J1/P1 before working on the electronic control system.

Tools: InPower service tool

  1. Place the motor disconnect switch in the Off position.
  2. Disconnect connector P1.
  3. Remove the old digital board and install the new one.
  4. Connect connector P1.
  5. Use InPower to perform an initial calibration on the replacement digital board; select settings and features to match the nameplate values.
  6. Write a capture file to the replacement board, or set up individual parameters if no good capture file is available.
  7. Remove all power from the digital board, including the batteries, for the changes to take effect.
  8. Place the motor disconnect switch back in the On position.
Linear Actuator Removal and Replacement (150 to 260 Amperes) repair

⚠ AC power within the cabinet presents an electrical shock hazard. Disconnect all sources of AC power from the transfer switch before servicing.

  1. Disconnect both Source 1 and Source 2 and the genset starting battery (negative lead first).
  2. Remove the two self-locking nuts and two machine screws securing the plastic switch cover and lift off the cover.
  3. Separate the actuator lead wires from the wiring harness; remove wire ties as required.
  4. Pry the capacitor(s) loose; disconnect the red and white leads from the capacitor terminals.
  5. Disconnect the black actuator wire from the circuit breaker and the ground wire from the end of the actuator.
  6. Remove the hardware securing the actuator to the switch assemblies and lift out the spacers (4) and barriers (2).
  7. Disengage the actuator rod from the switch handle and remove the actuator.
  8. Remove the rod end assembly from the actuator rod and slide the rod out of the actuator motor.
  9. Insert the actuator rod into the replacement motor; install the rod end assembly and tighten capscrew to 70-75 in-lbs (7.9-8.5 Nm).
  10. Position the actuator over the switch assemblies with lead wires at the bottom; fit the rod assembly into the handle of the closed switch assembly.
  11. Secure the actuator with hex head capscrews (4), lock washers (4), flat washers (4), barriers (2), and spacers (4); tighten to 25-27 in-lbs (2.8-3.0 Nm).
  12. Connect the black lead to the circuit breaker and the red and white leads to the capacitor terminals.
  13. Connect the ground wire; check operation and rod alignment; secure the plastic cover and tighten to 25-30 in-lbs.
  14. Reconnect the starting battery and power sources; test and close the cabinet.
Linear Actuator Removal and Replacement (40 to 125 Amperes) repair

⚠ AC power within the cabinet presents an electrical shock hazard. Disconnect all sources of AC power from the transfer switch before servicing.

  1. Disconnect both Source 1 and Source 2 from the transfer switch and the genset starting battery (negative lead first).
  2. Open the cabinet door and remove the four machine screws securing the plastic switch cover.
  3. Separate the actuator lead wires from the wiring harness; remove wire ties as required.
  4. Pry the capacitor(s) loose; disconnect the red and white leads from the capacitor and the black lead from the circuit breaker.
  5. Remove the socket head capscrews and lock washers securing the actuator to the block assemblies; note the ground wire on the lower left capscrew.
  6. Disengage the actuator rod from the switch handle and remove the actuator from the block assembly.
  7. Remove the rod end assembly from the actuator rod and slide the rod out of the actuator.
  8. Insert the actuator rod into the replacement actuator motor; install the rod end assembly and tighten the capscrew to 70-75 in-lbs (7.9-8.5 Nm).
  9. Position the actuator motor on the block assemblies so load wires are at the bottom; fit the rod assembly into the handle of the closed switch assembly.
  10. Secure the actuator with socket head capscrews (4) and lock washers (4); reconnect the ground wire to the lower left screw; tighten to 25-30 in-lbs (2.8-3.4 Nm).
  11. Connect the black lead to the circuit breaker and the red and white leads to the capacitor terminals (red to C1 Terminal 1; white to C1 Terminal 2, or C2 Terminal 2 if two capacitors).
  12. Replace the capacitor end caps and install the capacitors in the brackets; use wire ties on the actuator leads.
  13. Check switch operation and actuator rod alignment by manually opening and closing both switch assemblies; secure the plastic cover.
  14. Reconnect the starting battery and power sources and test the switch for proper operation.
Linear Actuator Removal and Replacement (800 and 1000 Amperes) repair

⚠ AC power within the cabinet presents an electrical shock hazard. Disconnect all sources of AC power from the transfer switch before servicing.

  1. Disconnect both Source 1 and Source 2 and the genset starting battery (negative lead first).
  2. Remove the capscrew, flat washer, and lock washer securing a rod end assembly to the actuator rod; remove the rod end assembly and slide the rod out.
  3. Remove the twelve machine screws securing the three plastic switch covers and lift off the covers.
  4. Separate the actuator lead wires from the wiring harness; remove wire ties as required.
  5. Pry the capacitors loose; disconnect the red and white leads from the capacitor terminals.
  6. Disconnect the black actuator lead from the circuit breaker and the ground wire from the end of the actuator.
  7. Remove the hardware securing the actuator to the switch assemblies and lift out the spacers and actuator motor.
  8. Hold the actuator motor and spacers (4) in position over the switch assemblies with lead wires at the bottom.
  9. Secure the actuator motor with hex head capscrews (4), lock washers (4), and flat washers (4); tighten to 70-75 in-lbs (7.9-8.5 Nm).
  10. Connect the black lead to the circuit breaker and the red and white leads to the capacitor terminals.
  11. Replace the capacitor end caps and install the capacitors; connect the ground wire and secure leads with wire ties.
  12. Place the plastic switch covers in position and tighten to 25-30 in-lbs (2.8-3.4 Nm).
  13. Insert the actuator rod into the motor, secure the rod end assembly to 70-75 in-lbs, and fit into the handle of the closed switch assembly.
  14. Reconnect the starting battery and power sources; test and close the cabinet.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What voltage does the Cummins/Onan OTPC produce?

The Cummins/Onan OTPC is offered in 120 V, 190 V, 208 V, 220 V, 240 V, 380 V, 1 Phase, 2-W or 3-W,3 Phase, 3-W or 4-W-phase.

Troubleshooting

1

Symptoms & remedies

SymptomCauseRemedy
Loss of Single Phase SensorThree phase Level 2 controllers include a loss of single phase sensor. If a single phase is lost and the system loads are highly inductive, the line voltage may stay within acceptable limits.The controller indicates a fault when the relative phase angle between any line-to-line phase angle drops to less than 90 degrees. This feature can be disabled using the PC service tool or the digital display Setup sub-menus.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

20
Part #DescriptionQtySystem
6-43Brakes (Brake hose, Brake fluid)Hose Amazon eBay
R020Voltage: 120 VAC1Voltage Amazon eBay
R021208 VAC1Voltage Amazon eBay
R035Voltage: 440 VAC1Voltage Amazon eBay
R038Voltage: 190 VAC1Voltage Amazon eBay
6-17For LPG Gensets: Turn the idle mixture screw out 1-1/4 turns and the main fuel mixture screw out 2-1/2 turns so that the engine will start and run.Service part / kit Amazon eBay
6-20Block and Cross-Bar Assembly Removal and Replacement (150 to 260 Amperes)Service part / kit Amazon eBay
6-23Replacing Block and Cross-Bar Assembly (Normal or Emergency)Service part / kit Amazon eBay
6-24Auxiliary Switch Removal and Replacement (150 to 260 Amperes)Service part / kit Amazon eBay
6-26Linear Actuator Removal and Replacement (300 to 600 Amperes)Service part / kit Amazon eBay
6-35Removing ActuatorService part / kit Amazon eBay
6-38Block and Cross-Bar Assembly Removal and Replacement (800 and 1000 Amperes)Service part / kit Amazon eBay
6-42Replacing the Block and Cross-bar Assembly (Normal or Emergency)Service part / kit Amazon eBay
6-44Replacing Auxiliary Switch AssemblyService part / kit Amazon eBay
R022220 VAC1Service part / kit Amazon eBay
R023240 VAC1Service part / kit Amazon eBay
R024380 VAC1Service part / kit Amazon eBay
R025416 VAC1Service part / kit Amazon eBay
R026480 VAC1Service part / kit Amazon eBay
R027600 VAC1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Spec sheet — Cummins Onan OTPCE OTPCF OTPCG OTPCH OTPCJ (Cummins/Onan)Operator's manual — 962-0126A Onan OTPC 40-3000 Amp Transfer Switch Operators manual 10-2002 (Cummins/Onan)Parts manual — 962-0231 Cummins OTPCE thru OTPCJ 1200-4000 Parts (1-2014) (Cummins/Onan)Service manual — 962-0516A Onan OTPC (40-1000 Amp) Transfer Switch Service manual (10-2002) (Cummins/Onan)Service manual — 962-0612A Onan OTPC (40-3000 Amp) Transfer Switch Installation manual (10-2002) (Cummins/Onan)