Cummins/Onan — Mis-Wired Current Transformers
Repair & overhaul
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan OTPC
Before you start
- Do not disconnect the current module while the current transformers are energized unless the secondaries are shorted.
Procedure
- If Source 2 is a genset, set the operation selector switch on the generator control panel to STOP.
- Open the transfer switch cabinet door.
- Remove the protective cover from TB4.
- Attach the shorting bar to the center of TB4, making sure to tighten each screw.
- Verify which CT is mis-wired. Reverse the jumper wires on the current module for the mis-wired CT. Do not remove any CT wires from TB4.
- Once all wiring is properly secured, remove the shorting bar.
- Reinstall the protective cover on TB4.
- Set the operation selector switch on the generator control panel to ON.
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.