HomeCummins/OnanCummins/Onan 5KW GO

Cummins/Onan 5KW GO Generator Set

The Cummins/Onan 5KW GO is a 5 kW gasoline standby generator set powered by a Continental Red Seal engine. It is available at 110 V and 115 V, single-phase and 60 Hz.

5 kW
Standby
1
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 5–10 kW Gasoline generators →

Compare with other 5–10 kW Gasoline generators →

Specifications

Fuelgasoline
Frequency60.0 Hz
Standby power5 kW
Prime power5 kW
Voltage options110 V, 115 V
Phasesingle
Battery voltage12 V
Battery quantity1

Engine

Continental Red Seal
Rated speed1800 rpm

Maintenance & consumables

for the Continental Red Seal
ItemSpecCapacityPart #Interval
Air filterOil bath air cleaner
Fuel filterFuel pump filter screen
Oil filterFilter element cartridge
Battery12-volt automotive battery
CoolantEngine coolant for radiator11.0 quarts
OilUndiluted engine oil for crankcase3.0 quarts50 hr
Spark plugSpark plugs×4200 hr

Common questions

How many kW is the Cummins/Onan 5KW GO?

The Cummins/Onan 5KW GO is rated 5 kW standby.

What engine does the Cummins/Onan 5KW GO use?

The Cummins/Onan 5KW GO is powered by the Continental Red Seal engine.

Is the Cummins/Onan 5KW GO diesel or gas?

The Cummins/Onan 5KW GO runs on gasoline.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
Generator overheatingOverloaded. Brush rig out of position.Reduce load. Be sure to line up marks. See Brush Rig.
Voltage drops under heavy loadEngine lacks power. See remedies for engine mising under heavy load. Poor compression. Tighten cylinder head and spark Plugs. If still not corrected, grind the valves. Replace piston rings, if necessary.See MAINTENANCE AND REPAIR.
Engine misfires at light loadCarburetor idle adjustment set wrong or clogged. Spark plug gaps too narrow. Adjust to correct gap. Refer ta TABLE OF CLEARANCES. Intake air leak. Tighten or replace gaskets. Faulty ignition. Clean, adjust, or replace breaker points, plugs, condenser, coil, etc., or retime ignition, Uneven compression. Tighten cylinder head and spark plugs. If still not corrected, grind valves. Replace piston rings, if necessary.
Engine misfires at all loadsFouled spark plug. Defective or wrong spark plug. Sticking valves. Broken valve spring. Defective ignition wires. Defective or improperly adjusted paints.Clean and adjust, Replace, Clean stems and guides. Replace. Adjust or replace breaker points. See Periodic Service - Weekly.
Low oil pressureToo long screw on center main bearing. Oil too light. Oil badly diluted. Oil level too low. Oil relief valve not seating. Badly worn bearings.See MAIN BEARINGS. Drain, refill with proper oil. See PREPARATION. Drain, refill with proper oil. Add oil. Remove and clean, or replace. See LUBRICATION SYSTEM. Replace. See MAINTENANCE AND REPAIR.
Plant starts but does not continue to runSTART button released too soon. Defective panel equipment.Hold in contact longer. See Controls.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan 5KW GO troubleshooting guide (22 entries) →

Available documents

Service manual — 903-0000 Onan 5KW GO Genset Operator's & Service manual (1945) (Cummins/Onan)