Caterpillar 3500 series Generator Set

Caterpillar 3500 series generator set: . Specifications, engine details, filters, oil capacity and 3 document types.

3
Document types

How to read your Caterpillar serial & model number →

Service parts for the 3500 series

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Cooling system

2 required
119-5150Coolantsee priceeBay
9Y1022Coolant filter$20.00eBay

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Ratings spec sheet not in our library yet — see the documents below.

Filters & service parts

model family
ItemSpecCapacityPart #Interval
Air filterCan be cleaned up to six times if properly cleaned and inspected; replace at least once per year612506 Amazon eBay $100.00 PartsGeek $66.97
BatteryMaintain electrolyte level to FULL mark; use distilled water—250 hr
BeltDeflect 13 to 19 mm (0.50 to 0.75 inch) with 110 N (25 lb) force—250 hr
CoolantCaterpillar EC-1 specification; 1:1 premixed solution with distilled water119-515012000 hr eBay
Coolant filterCat ELC Extender added once9Y10226000 hr eBay $20.00
OilSee SEBU6251-16 recommendations139.0—

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.

Service intervals

30
ItemActionHoursMonthsNotes
InsulationTest100 hr3 moEvery 100 Service Hours or 3 Months
Engine oil (S-O-S oil sample)Test125 hrSevere service occurs at high loads, in high temperatures, and in dusty conditions
Aftercooler CoreClean250 hrClean/Test - Every 9500 L (2500 US gal) of Fuel or 250 Service Hours or Yearly
Alternator and Fan BeltsReplace250 hrInspect/Adjust/Replace - Every 19 000 L (5000 US gal) of Fuel or 250 Service Hours
Battery Electrolyte LevelCheck250 hrEvery 19 000 L (5000 US gal) of Fuel or 250 Service Hours
Coolant (S-O-S coolant analysis Level 1)Test250 hrCat ELC - Every 250 Hours; also the recommended sampling interval for all conventional heavy-duty coolant/antifreeze and for commercial coolants that meet Cat EC-1
Cooling System Coolant Sample (Level 1)Test250 hrObtain - Every 250 Service Hours
Cooling System Supplemental Coolant Additive (SCA)Test250 hrTest/Add - Every 19 000 L (5000 US gal) of Fuel or 250 Service Hours
Engine Crankcase BreatherClean250 hrEvery 19 000 L (5000 US gal) of Fuel or 250 Service Hours
Engine Protective DevicesCheck250 hrEvery 19 000 L (5000 US gal) of Fuel or 250 Service Hours
Engine Valve LashAdjust250 hrFirst service — Inspect/Adjust - First 19 000 L (5000 US gal) of Fuel or 250 Service Hours
Engine crankcase oil (S-O-S oil sample)Test250 hrTable 6 S-O-S Oil Sampling Interval; severe applications may require a more frequent oil sampling interval
Magnetic PickupsClean250 hrFirst service — Clean/Inspect - First 19 000 L (5000 US gal) of Fuel or 250 Service Hours
SCA (Supplemental Coolant Additive) concentrationTest250 hrTest the concentration of SCA or submit a coolant sample at 250 hour intervals or at PM Level 1 intervals; check at every oil change or every 250 hours, whichever occurs first
Coolant (S-O-S coolant analysis Level 2)Test500 hr12 moFirst service — For new systems, refilled systems, and converted systems that use Cat ELC or Cat DEAC; also every year; use the interval that occurs first
Cooling System Coolant Sample (Level 2)Test2000 hr12 moObtain - Every 2000 Service Hours or 1 Year
EngineClean2000 hr6 moEvery 2000 Service Hours or 6 Months
Fuel SystemOther2000 hr6 moPrime - Every 2000 Service Hours or 6 Months
GeneratorOther2000 hr6 moDry - Every 2000 Service Hours or 6 Months
Generator Lead (Round Cable)Check2000 hrEvery 2000 Service Hours
Generator SetTest2000 hr6 moEvery 2000 Service Hours or 6 Months
Generator Set VibrationInspect2000 hr6 moEvery 2000 Service Hours or 6 Months
Rotating RectifierTest2000 hr6 moEvery 2000 Service Hours or 6 Months
Severe Service ApplicationCheck2000 hr6 moEvery 2000 Service Hours or 6 Months
Cat ELC Extender addition (cooling system)Other6000 hrTreat the cooling system with Cat ELC Extender at 6000 hours or one half of the coolant service life
Cooling System Coolant Extender (ELC)Other6000 hr36 moAdd - Every 6000 Service Hours or 3 Years
Coolant (Cat ELC)Change12000 hr12000 service hours or six years; use the interval that occurs first
Cooling System Coolant (ELC)Change12000 hr72 moEvery 12 000 Service Hours or 6 Years
Coolant (S-O-S coolant analysis Level 1 and Level 2)Test12 moCat DEAC - Yearly
Fuel System Primary Filter (Water Separator) ElementReplace500 hr12 moEvery Year

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

42
TypeItemValueUnitCondition
OtherBelt tension deflection0.50 to 0.75inch110 N (25 lb) force midway between pulleys
OtherBelt tension deflection13 to 19mm110 N (25 lb) force midway between pulleys
OtherCoolant level below filler pipe bottom13mm
OtherCooling system fill rate (maximum)19L per minuteto avoid air locks
OtherEngine valve rotator operationshould turn slightly when valves close
OtherGenerator excitation PMG short circuit capability3 X In for 10 seconds
OtherVibration damper inspectiondented, cracked, leaking, bent or discolored damper must be replaced
PressureCoolant system pressure test - use 9S-8140 Pressurizing Pump9S-8140
PressureFuel pressure (below which engine will not operate properly)160kPa
PressureMaximum air pressure for cleaning205kPadeadheaded nozzle with chip guarding
PressureMaximum water pressure for cleaning275kPa
PressureMinimum recommended oil pressure103kPa600 rpm
PressureMinimum recommended oil pressure15psi600 rpm
PressurePrimary filter/water separator change pressure50 to 70kPa15 to 20 inches Hg
PressureTypical engine oil pressure at rated rpm with SAE10W30 (turbocharged)275 to 606kParated rpm
PressureTypical engine oil pressure at rated rpm with SAE10W30 (turbocharged)40 to 88psirated rpm
ResistanceInsulation resistance minimum (contaminated generator)1megohm
SpeedActual RPM of overspeed (1500 full load rpm)1770rpmmultiply full load RPM by 1.18
SpeedActual RPM of overspeed (1800 full load rpm)2124rpmmultiply full load RPM by 1.18
SpeedGenerator set functional test minimum phase voltage85VAChalf rated speed
SpeedLow idle (50 Hz units)80percent of full load speed
SpeedLow idle (60 Hz units)66percent of full load speed
SpeedMagnetic pickup crank termination400rpmstarter pinion disengagement
SpeedOverspeed switch setpoint118percent of rated engine speed
SpeedTest RPM for overspeed (1500 full load rpm)1328rpmmultiply full load RPM by 0.885
SpeedTest RPM for overspeed (1800 full load rpm)1593rpmmultiply full load RPM by 0.885
TemperatureAir cleaner oven drying maximum82°C
TemperatureAir cleaner wash water maximum60°Csoak six hours
TemperatureFuel heater maximum fuel supply temperature37°C
TemperatureGenerator bearing shutdown temperature50°C above ambient
TemperatureGenerator drying winding temperature ramp rate10°C per hourup to 85 C (185 F)
TemperatureGenerator oven drying65°C4 hours forced air
TemperatureJacket water coolant temperature (maximum allowable)104°C
TemperatureJacket water coolant temperature (typical)87 to 98°C
TemperatureJacket water heater maintained coolant temperature32°Cambient 0 C (32 F)
TorqueAir cleaner service indicator18lb in
TorqueAir cleaner service indicator2N·m
TorqueFuel line nuts30 ± 5lb ft
TorqueFuel line nuts40 ± 7N·m
Valve clearanceValve Lash (exhaust)0.76mmcold
Valve clearanceValve Lash (inlet)0.38mmcold
VoltageUnit injector system voltage90-120volts

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantCat DEAC (Diesel Engine Antifreeze/Coolant)Acceptable coolant; commercial heavy-duty antifreeze/coolant must meet ASTM D4985 or ASTM D6210Conventional heavy-duty coolant/antifreeze. Caterpillar recommends a 1:1 mixture of water and glycol. Do not use a commercial coolant/antifreeze that only meets the ASTM D3306 specification. Do not use Cat SCA at the initial fill when Cat DEAC is used.
CoolantCat DEAC Diesel Engine Antifreeze/CoolantASTM D4985 or ASTM D534558.0 LAcceptable; 1:1 mixture of water and glycol; service life three years; does not require SCA at initial fill
CoolantCat ELC (Extended Life Coolant)Caterpillar EC-1 specification (preferred); also meets ASTM D4985, ASTM D6210, and ASTM D3306Service life of 12000 service hours or six years. Premixed ELC provides freeze protection to -37 C (-34 F); ELC Concentrate can be used to lower the freezing point to -52 C (-62 F). An Extender is the only additional maintenance needed at 6000 service hours or one half of the ELC service life. Cat ELC cooling systems can withstand contamination to a maximum of ten percent of conventional heavy-duty coolant/antifreeze and/or SCA.
CoolantCat ELC Extended Life CoolantCaterpillar EC-158.0 LPreferred; 1:1 mixture of water and glycol; service life six years; add ELC Extender once
CoolantCat SCA (Supplemental Coolant Additive) with waterSCA concentration in a cooling system that uses SCA and water should be six to eight percent by volume; do not exceed the eight percent maximum concentration. If Cat SCA is not used, the commercial SCA must provide a minimum of 2400 mg/L or 2400 ppm (140 grains/US gal) of nitrites in the final coolant mixture when used with water, and a minimum of 1400 mg/L or 1400 ppm (82 grains/US gal) with heavy-duty coolant/antifreeze.
CoolantCaterpillar SCA and WaterFor stationary applications not requiring boiling/freezing protection; minimum six percent to maximum eight percent SCA concentration; service life two years
CoolantGlycol (ethylene glycol / propylene glycol)Propylene glycol coolant must meet ASTM D6210-04Ethylene glycol: 50 percent = freeze protection -37 C (-34 F), boil protection 106 C (223 F); 60 percent = -52 C (-62 F), 111 C (232 F). Propylene glycol: 50 percent = -32 C (-26 F), 106 C (223 F). Do not use propylene glycol in concentrations that exceed 50 percent; do not use ethylene glycol in concentrations that exceed 60 percent. All Caterpillar diesel engines equipped with air-to-air aftercooling (ATAAC) require a minimum of 30 percent glycol.
Engine oilCat DEO (Diesel Engine Oil) 10W-30 and 15W-40Cat ECF-1 (exceeds); API CI-4, API CI-4 PLUS, API CH-4, API CG-4, API CF (Cat DEO SAE 15W-40)Caterpillar oils are used to fill diesel engines at the factory. Non-Caterpillar commercial oils are second choice oils. Do not use API CF-4 oils in Caterpillar diesel engines. Do not use single grade API CF oils or multigrade API CF oils in 3500 Series, C175 Series and smaller DI diesel engines.
Engine oilCommercial oils (DI engines)Cat ECF-1 required; API CG-4 multigrade acceptable; API CH-4, API CI-4 and API CI-4 PLUS acceptable only if the requirements of Cat ECF-1 are met; do not use API CF-4 oilsMinimum TBN must be 10 times the fuel sulfur level (ASTM D2896); minimum TBN of the oil is 5 regardless of a low fuel sulfur level. API CG-4 oils: do not exceed the standard oil drain interval.
Engine oilCommercial oils (PC engines)Cat ECF-1; API CH-4, API CI-4, API CI-4 PLUS (if Cat ECF-1 requirements met); API CG-4 multigrade; API CF-4 multigrade; API CFMinimum TBN of the oil that is used in PC engines must be 20 times the fuel sulfur level; minimum TBN of new oil is five. Change the oil when the TBN deteriorates to 50 percent of the original TBN.
Engine oilRe-refined base stock oilsAcceptable if they meet the performance requirements specified by Caterpillar; filtering is inadequate for producing high quality re-refined base stock oils.
Engine oilSynthetic base stock oilsAcceptable if they meet the performance requirements specified for the engine compartment. Caterpillar does not recommend the automatic extension of oil drain intervals for any type of oil.
Engine oilSAE 0W-20-40°C to 10°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 0W-30-40°C to 30°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 0W-40-40°C to 40°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 5W-30-30°C to 30°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 5W-40-30°C to 50°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 10W-30-18°C to 40°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines); SAE 10W-30 is the preferred viscosity grade for the 3116, 3126, C7, C-9 and C9 diesel engines between -18 C (0 F) and 40 C (104 F)
Engine oilSAE 10W-40-18°C to 50°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 15W-40-9°C to 50°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilCat SAEO SAE 30API CF-4 category0°C to 40°CTable 2 - 3116 and 3126 Marine Engines with mechanical unit injection; factory fill has API CF-4 category and viscosity grade of SAE 30
Engine oilSAE 300°C to 40°CTable 3 Lubricant Viscosities for Ambient Temperatures - PC engines only
Engine oilCat SAEO SAE 40API CF-4 category5°C to 50°CTable 2 - 3116 and 3126 Marine Engines with mechanical unit injection. Caterpillar does not recommend the use of multigrade oils in the 3116 and 3126 Marine Diesel Engines that use mechanical unit injection.
Engine oilSAE 405°C to 50°CTable 3 Lubricant Viscosities for Ambient Temperatures - PC engines only
FuelBiodiesel blendsCaterpillar biodiesel specification, ASTM D6751, or EN 14214May be blended in amounts up to a maximum of 30 percent (models C6.6, C7, C9, C11, C13, C15, C18, C27, C32, 3114, 3116, 3126, 3176, 3196, 3208, 3306, C-9, C-10, C-12, 3406, C-15, C-16, C-18, 3456, 3408, 3412, 3500 Series, C175 Series, 3600 Series, C280 Series, CM20, CM25 and CM32); for 3003 through 3034, 3046, 3054, 3056, 3064, and 3066 engines, maximum ratio of 5% biodiesel to 95% acceptable diesel fuel. Caterpillar recommends a maximum of one year for fuel storage.
FuelJP-5, JP-8, Jet A-1MIL-DTL-5624U, MIL-DTL-83133E, ASTM D1655-05Table 8 - may be used in extreme cold ambient conditions down to -54 C (-65 F); these fuels typically do NOT meet ULSD fuel requirements; if viscosity is below 1.4 cSt at 40 C (104 F) use the fuel only in temperatures below 0 C (32 F); do not use any fuels with a viscosity of less than 1.2 cSt at 40 C (104 F).
FuelNo. 1-D / No. 2-D distillate diesel fuelASTM D975; Caterpillar Specification for Distillate Diesel Fuel (Table 7)Cetane number 40 minimum (DI engines) or 35 minimum (PC engines); aromatics 35% maximum; ash 0.02% maximum (weight); carbon residue on 10% bottoms 0.35% maximum (weight); copper strip corrosion No. 3 maximum; distillation 10% at 282 C (540 F) maximum, 90% at 360 C (680 F) maximum; flash point legal limit minimum; pour point 6 C (10 F) minimum below ambient temperature; sulfur 0.1% maximum; kinematic viscosity 1.4 cSt minimum and 20.0 cSt maximum as delivered to the fuel injection pumps; water and sediment 0.1% maximum; water 0.1% maximum; sediment 0.05% maximum; gums and resins 10 mg per 100 mL maximum; lubricity 0.52 mm (0.0205 inch) maximum at 60 C (140 F) by ASTM D6079; cloud point must not exceed the lowest expected ambient temperature.
FuelNo. 1-D or No. 2-DASTM D975Use No. 1 diesel fuel or a blend of No. 1 and No. 2 for cold-weather operation; No. 2 is most commonly used
FuelUltra Low Sulfur Diesel (ULSD)ASTM D5453, ASTM D2622, or DIN 51400; <15 ppm (0.0015%) sulfurIn North America, diesel fuel identified as "ASTM D975 Grade No. 1-D S15" or "ASTM D975 Grade No. 2-D S15" meeting "ASTM D975 Thermal Stability Guideline X2.10.2.2" generally meets the Caterpillar requirements for ULSD fuel.
Gear oilCat TDTO (Transmission/Drive Train Oil)Caterpillar TO-4 oil specificationTable 4 - SAE 30: -15 C (5 F) to 80 C (176 F); SAE 50: -5 C (23 F) to 95 C (203 F). Formulated for transmissions and drive trains only and should not be used in engines. Cat GO (Gear Oil) is not the same as Cat TDTO and does not meet Caterpillar's specifications for TO-4 oil.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Engine Valve Lash - Inspect/Adjust adjustment

⚠ Hot engine components can cause burns.

⚠ Only qualified service personnel should perform this maintenance.

  1. Ensure the engine cannot be started; do not use the starting motor to turn the flywheel.
  2. Ensure the engine is stopped and allow valves to cool.
  3. Refer to the Systems Operation/Testing and Adjusting Manual for the complete procedure.
  4. Set inlet valve lash to 0.38 mm (0.0150 inch).
  5. Set exhaust valve lash to 0.76 mm (0.030 inch).
  6. Perform initial adjustment at the first scheduled oil change.
Determining the cause of a plugged fuel filter (ice or wax) diagnostic
  1. Remove the fuel filters.
  2. Cut the fuel filters open.
  3. Inspect the fuel filter before the filter warms. The inspection will show that the filter is filled with particles of either ice or wax.
Rotating Rectifier - Test (Brushless Exciter) diagnostic

Tools: 6V-7070 Digital Multimeter, 9U-7330 Multimeter, 146-4080 Digital Multimeter (RS-232), 7X-1710 Multimeter Probe Group

  1. Remove the cover from the exciter.
  2. Remove the nut securing the rectifier to the heat sink.
  3. Remove the diode lead and lift the rectifier from the heat sink.
  4. Connect ohmmeter leads across the rectifier and note reading.
  5. Reverse the ohmmeter leads and note reading.
  6. Low resistance one direction and high the other indicates a good rectifier.
  7. Low resistance both directions indicates shorted rectifier.
  8. High resistance both directions indicates open rectifier; replace faulty rectifiers.
Battery - Replace maintenance

⚠ Batteries give off combustible gases which can explode.

⚠ Removing cables with cover in place may cause battery explosion.

  1. Turn key start switch to OFF; remove key and all electrical loads.
  2. Turn OFF and disconnect battery charger.
  3. Disconnect NEGATIVE - cable from NEGATIVE - battery terminal.
  4. Disconnect POSITIVE + cable from POSITIVE + battery terminal.
  5. Remove the used battery.
  6. Install the new battery.
  7. Connect cable from starting motor to POSITIVE + terminal.
  8. Connect cable from ground plane to NEGATIVE - terminal.
Battery Disconnect Switch - Check maintenance

⚠ Never move the battery disconnect switch to OFF while the engine is operating.

  1. With switch ON verify electrical components, hour meter and cranking function.
  2. Turn the battery disconnect switch to the OFF position.
  3. Verify electrical components, hour meter and cranking do not function.
  4. Consult your Caterpillar dealer if any item continues to function.
Changing to Cat ELC maintenance

⚠ Do not leave an empty SCA maintenance element on a system that is filled with ELC. The element housing may corrode and leak causing an engine failure.

⚠ Improper or incomplete rinsing of the cooling system can result in damage to copper and other metal components.

⚠ The cooling system cleaner must be thoroughly flushed from the cooling system. Cooling system cleaner that is left in the system will contaminate the coolant. The cleaner may also corrode the cooling system.

Tools: Caterpillar cleaner for cooling systems, 5P-3413 Pipe Sealant, Suitable containers to collect fluids

  1. Drain the coolant into a suitable container.
  2. Dispose of the coolant according to local regulations.
  3. If equipped, remove the empty SCA maintenance element and the element base. Plug the coolant lines or bypass the coolant lines.
  4. Flush the system with clean water in order to remove any debris.
  5. Use Caterpillar cleaner for cooling systems in order to clean the system. Follow the instructions on the label.
  6. Drain the cleaner into a suitable container. Flush the cooling system with clean water.
  7. In systems with heavy deposits, disconnect the hoses. Clean deposits and debris from the hoses and fittings. Install the hoses and tighten the hose fittings.
  8. Fill the cooling system with clean water and operate the engine until the engine is warmed to 49 C to 66 C (120 F to 151 F).
  9. Drain the cooling system into a suitable container and flush the cooling system with clean water.
  10. Repeat Steps 8 and 9 until the system is completely clean.
  11. Fill the cooling system with the Cat ELC.
  12. Operate the engine until the engine is warmed. While the engine is running, inspect the engine for leaks. Tighten hose clamps and connections in order to stop any leaks.
  13. Attach the Special Publication, PEEP5027, "Label" to the cooling system filler for the engine in order to indicate the use of Cat ELC.
Cooling System Coolant (DEAC) - Change maintenance

⚠ Pressurized system: hot coolant can cause serious burns.

Tools: 9S-8140 Pressurizing Pump

  1. Stop engine and allow to cool; loosen filler cap slowly and remove.
  2. Open drain valve or remove drain plug; allow coolant to drain.
  3. Flush cooling system with clean water.
  4. Close drain valve; clean and install drain plugs per SENR3130 torques.
  5. Fill with clean water and cleaner; run at low idle minimum 30 minutes at 82 C.
  6. Drain and flush until all cleaning agent is gone.
  7. Fill with coolant/antifreeze; do not install filler cap.
  8. Run engine at high idle 1 minute to purge air; check level and cap.
Engine Oil and Filter - Change maintenance

⚠ Hot oil and hot components can cause personal injury.

Tools: 1U-8760 Chain Wrench, 175-7546 Oil Filter Cutter Gp

  1. Drain crankcase with engine stopped and oil warm.
  2. If no drain valve, remove oil drain plug; clean and install plugs.
  3. Remove oil filter with 1U-8760 Chain Wrench.
  4. Cut filter open with 175-7546 Oil Filter Cutter Gp and inspect for debris.
  5. Clean sealing surface of filter mounting base.
  6. Apply clean engine oil to new oil filter gasket.
  7. Install oil filter; tighten by hand per filter instructions.
  8. Fill crankcase; run at low idle 2 minutes and check level.
Fuel System - Prime maintenance

⚠ Personal injury or death can result from a fire; clean up spilled fuel.

  1. Unlock priming pump; operate until resistance is felt.
  2. Push in plunger and hand tighten.
  3. Crank the engine.
  4. If equipped, open vent valve on fuel injection pump housing.
  5. Operate priming pump until fuel flow is continuous and free of air.
  6. Close vent valve; push in and hand tighten plunger.
  7. If no priming pump, crank engine until fuel flows freely.
  8. Loosen fuel line nuts at valve cover base one at a time; prime until air-free; retighten.
Fuel System Primary Filter (Water Separator) Element - Replace maintenance

⚠ Fuel leaked or spilled onto hot surfaces or electrical components can cause a fire.

  1. Stop the engine and turn start switch to OFF.
  2. Shut off fuel tank supply valve.
  3. If equipped, open drain valve and drain fuel from filter case.
  4. Remove the fuel filter bowl and wash with clean diesel fuel.
  5. Remove the fuel filter.
  6. Clean gasket sealing surface of the filter base.
  7. Apply clean diesel fuel to the new filter gasket.
  8. Install new filter; spin until gasket contacts base and tighten 3/4 turn by hand; install bowl.
Generator - Dry (Controlled Current Method) maintenance

⚠ Personal injury or death can result from improper troubleshooting and repair procedures.

Tools: 225-8266 Ammeter Tool Gp, Rheostat, External Power Source

  1. Make an external power source.
  2. Disconnect F1+ and F2- from voltage regulator; disconnect generator load.
  3. Connect rheostat at maximum resistance and external power source to F1+ and F2-.
  4. Start generator set and run at IDLE speed.
  5. Monitor phase current; gradually increase RPM until rated phase current or full speed.
  6. Slowly turn rheostat until rated phase current is reached.
  7. On an hourly basis stop and check insulation resistance.
  8. Repeat until insulation resistance is acceptable.
Generator Isolating for Maintenance maintenance

⚠ High voltage can cause electrical shocks.

Tools: Audio/visual proximity tester

  1. Stop the engine.
  2. Attach DO NOT OPERATE tag to engine starting circuit; disconnect starting circuit.
  3. Disconnect the generator from the distribution system.
  4. Lock out the circuit breaker and attach DO NOT OPERATE tag.
  5. Remove fuses for power, sensing and control transformers.
  6. Attach DO NOT OPERATE tag to generator excitation controls.
  7. Remove cover of generator terminal box.
  8. Use audio/visual proximity tester to verify de-energized; add ground straps.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
three-phase10 Lead Wye Configuration - High VoltageTerminal T0 is the neutral leadFor 3306B and 3406C generator sets only
three-phase10 Lead Wye Configuration - Low VoltageTerminal T0 is the neutral leadFor 3306B and 3406C generator sets only
three-phase12 Lead Delta ConfigurationTerminals T6 and T9 become the neutral connection when tied together and grounded; T2 and T10 connection is the high phase
three-phase12 Lead Wye Configuration - High VoltageTerminals T10, T11 and T12 become neutral connection when tied together
three-phase12 Lead Wye Configuration - Low VoltageTerminals T10, T11 and T12 become neutral connection when tied together
three-phase4 Lead Wye ConfigurationTerminal T0 is the neutral leadFor 3306B and 3406C generator sets only
three-phase6 Lead Delta Configuration
three-phase6 Lead Wye ConfigurationTerminals T4, T5 and T6 become neutral connection when tied together
240three-phaseDelta Configuration (60 Hz, 12 Lead)T6 and T9 neutral when tied together and grounded208 Volts between high phase and neutral; 240 Volts between either low phase and neutral
480three-phaseWye Configuration (typical series Wye, 60 Hz, 12 Lead)T10, T11, T12 neutral when tiedFor 3406E, 3412C and 3500 series generator sets only - high voltage

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What air filter fits the Caterpillar 3500 series?

The Caterpillar 3500 series uses air filter part number 612506.

Troubleshooting

3

Fault codes

CodeMeaningRemedy
i01226491Engine overspeedStop the engine by shutting off the fuel supply to the engine and/or shutting off the air supply to the engine.
21Fault shutdown
22Fault alarm

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

11model family
Part #DescriptionQtySystem
119-5150Concentrate1 GallonFluid eBay
119-5152Cat Engine Oil (quart bottle)quart bottleFluid Amazon eBay
156-2649Cat DEAC (Diesel Engine Antifreeze/Coolant) (Concentrate) - bulkFluid buy
210-0786Cat ELC Extender 3.8 L (1 US gal)1Fluid eBay
217-0617Caterpillar Liquid SCA (Supplemental Coolant Additive) 20 L (5.3 US gal)1Fluid buy
217-0618Caterpillar Liquid SCA (Supplemental Coolant Additive) 208 L (55 US gal)1Fluid buy
2P-9868Cat DEAC (Diesel Engine Antifreeze/Coolant) (Concentrate) - bulkFluid eBay
5P-2907Caterpillar Liquid SCA - 208 L (55 US gal)1Fluid Amazon eBay $10.25
8C-3680Caterpillar Liquid SCA - 19 L (5 US gal)1Fluid Amazon eBay
8C-3686Cat Antifreeze - 208 L (55 gal)1Fluid buy
245-5829Coolant Battery Tester Refractometer1Service part / kit Amazon eBay $98.00

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Reference — LEDM3457-27 (Caterpillar)Owner's manual — CAT-3412C- Generator-Set- Manual (Caterpillar)Service manual — Caterpillar Diesel Engine Fluid Recommendations (Caterpillar)Service manual — SEBU6251-16 (Caterpillar)