| 5 | Starting failed | STARTING FAILS | Shutdown | Acknowledge with Start/Stop button; check starting system and fuel supply. |
| 9 | Watchdog Error | WATCHDOG | Shutdown | Acknowledge with Start/Stop button; check controller. |
| 12 | Winding temperature fault | FAULT: WINDING | Shutdown | Acknowledge with Start/Stop button; check winding temperature and cooling. |
| 13 | Winding temperature out of range | OUT: WINDING | Shutdown | Check winding temperature sensor and wiring. |
| 14 | Exhaust temperature fault | FAULT: EXHAUST | Shutdown | Acknowledge with Start/Stop button; check exhaust temperature and cooling. |
| 15 | Exhaust temperature out of range | OUT: EXHAUST | Shutdown | Check exhaust temperature sensor and wiring. |
| 16 | Engine temperature fault | FAULT: CYL.HEAD | Shutdown | Acknowledge with Start/Stop button; check engine temperature and cooling. |
| 17 | Oil pressure fault | FAULT: OILPRESS | Shutdown | Check oil level and oil pressure; repair if necessary. |
| 18 | Battery voltage low | BATTERY LOW | Shutdown | Recharge battery; check charging system and battery connections. |
| 19 | unexpected stop/Problem with fuel supply | PROBLEM WITH / FUEL SUPPLY! | Shutdown | Check fuel supply, fuel filter and fuel pump. |
| 22 | Emergency stop | EMERGENCY STOP! | Shutdown | Release emergency stop switch; investigate cause. |
| 23 | Engine temperature out of range | OUT: CYL.HEAD | Shutdown | Check cylinder head temperature sensor and wiring. |
| 30 | Inverter overtemp | Inverter overtemp | Shutdown | Check PMGi cooling and air flow. |
| 31 | inverter overload | Inverter overload | Shutdown | Reduce load; check for overload. |
| 32 | inverter communication lost | Inverter com. lost | Shutdown | Check PMGi communication cable and connections. |
| 33 | inverter synchronisation lost | INV. SYNC. FAILED | Shutdown | Check inverter synchronization and connections. |
| 34 | Engine fault (EDC) | ENGINE FAULT | Shutdown | Check engine ECU and engine fault codes. |
| 35 | CAN communication lost | CAN. COMM.LOST | Shutdown | Check CAN bus wiring and connections. |
| 36 | inverter overload slave 1 | L1 OVERLOAD | Shutdown | Reduce load on phase L1. |
| 37 | inverter overload slave 2 | L2 OVERLOAD | Shutdown | Reduce load on phase L2. |
| 38 | inverter overload slave 3 | L3 OVERLOAD | Shutdown | Reduce load on phase L3. |
| 39 | inverter overload slave DC | DC OVERLOAD | Shutdown | Reduce DC load. |
| 40 | Overvoltage | FAULT: OVERVOLTAGE | Shutdown | Check AC output voltage and load. |
| 41 | Undervoltage | FAULT: LOWVOLTAGE | Shutdown | Check AC output voltage and load. |
| 42 | DC-Overvoltage | DC OVERVOLTAGE | Shutdown | Check DC input voltage. |
| 66 | RedundantTempSwitchOff | NOTSTOP! | Shutdown | Check temperature sensors and cooling system. |
| 100 | Communication Error | NO CONNECTION / BUS ERROR! | Shutdown | Check bus wiring and plug connections. |
| 207 | Init failed (no generator type is selected) | INIT FAILED! | Shutdown | Select correct generator type in configuration. |
| BATTERY LOW | Battery power too low | Battery power too low. | Shutdown | Check battery and charging. |
| FAULT: CYL.HEAD | Cylinder head temperature too high | Cylinder head temperature too high. | Shutdown | Acknowledge with Start/Stop; check cooling and sensor. |
| FAULT: EXHAUST | Exhaust manifold temperature too high | Exhaust manifold temperature too high. | Shutdown | Acknowledge with Start/Stop; check cooling water and exhaust. |
| FAULT: OILPRESS | Oil pressure error | Oil pressure error. | Shutdown | Check oil level and oil pressure. |
| FAULT: WINDING | Winding temperature too high | Winding temperature too high. | Shutdown | Acknowledge with Start/Stop; check load and winding. |
| HIGH | Cylinder head temperature high | Cylinder head temperature is too high; warning threshold reached. | Warning | |
| INIT FAILED! | Initialisation failed | Parameters were not correctly adopted into EEPROM when generator type was initialised. | Shutdown | Reset generator type. |
| Inverter overload | Generator overloaded | Generator overloaded; also issued when generator output cable is not connected to inverter. | Shutdown | Reduce load and check output cable. |
| Inverter overtime | Inverter temperature too high | Inverter temperature too high. | Shutdown | Check PMGi cooling and load. |
| LOW | Starter battery voltage low | Starter battery voltage is too low; warning threshold reached. | Warning | |
| NO CONNECTION BUS ERROR | Communication error on Fischer Panda bus | Communication error on Fischer Panda bus. | Shutdown | Check bus wiring and plug connections. |
| OUT | Temperature out of range | Out of range; broken cable on corresponding temperature sensor. | Shutdown | Check sensor and wiring. |
| PROBLEM WITH FUEL SUPPLY! | Fuel supply not suitable | Fuel supply not suitable. | Shutdown | Check fuel supply and filters. |
| STARTING FAILS | Generator start has failed | Generator start has failed. | Shutdown | Acknowledge; check fuel, glow plugs, and starting system. |