| AC Sens Loss | AC Sensing Lost | In Auto mode, generator output AC sensing is lost. Detection begins 10 seconds after crank disconnect. | Warning | Contact authorized distributor/dealer for service |
| ATS ComError | ATS Communication Error | Warning is displayed if ATS interface connection is lost | Warning | Check communication wiring between transfer switch interface board and generator set. |
| ATS PhaseRot | ATS PhaseRot | Transfer switch phase rotation does not match; ATS will not transfer | Warning | Correct the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch. |
| Accy PwrOver | Accessory Power Overload | An over current fault (short circuit) on the accessory controller power output | Warning | Contact authorized distributor/dealer for service |
| Accy PwrOver Warning | Accy PwrOver Warning | An over current fault (short circuit) on the accessory controller power output. | Warning | Contact an authorized distributor/dealer for service |
| Advanced Diagnostic | Advanced Diagnostic | Shutdown during the reduced speed portion of an exercise. Event history shows Advanced Diagnostic Active. Engine restarts, runs at full speed for 2 minutes, and stops. Controller returns to AUTO mode. | Shutdown | If the generator set does not restart and return to AUTO, check for other faults that prevent generator set operation. |
| Aux Input | Auxiliary Input | Optional customer-connected input (from PIM) is closed | Shutdown | Check customer-supplied equipment. |
| Batt Chg Flt | Battery Charger Fault | Input to PIM from an external battery charger (not the built-in battery charger). | Warning | Check external battery charger. |
| Battery CrLo | Battery Crank Low | Engine starting battery voltage falls below 11 VDC for more than 10 seconds | Warning | Clears when battery voltage returns to acceptable level |
| Battery CrLo Warning | Low Cranking Battery Voltage Warning | Engine starting battery voltage falls below 11 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when battery voltage returns to acceptable level. | Warning | Check the battery rating and condition. Check the battery charger operation. Charge or replace the battery. |
| Battery High | Battery High | Engine starting battery voltage rises above 16 VDC for more than 10 seconds (inhibited during crank) | Warning | Check battery rating/condition and charger operation |
| Battery Voltage High | Battery Voltage High | Engine starting battery voltage rises above 16 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when voltage returns to acceptable level. | Warning | Check the battery rating and condition. Check the battery charger operation. |
| Battery Voltage Low | Battery Voltage Low | Engine starting battery voltage falls below 12.5 VDC for more than 90 seconds when engine not running. Not operative during crank cycle. Clears when voltage returns to acceptable level. | Warning | Check the battery rating and condition. Check the battery charger operation. Charge or replace the battery. |
| Eng Speed High | Eng Speed High | Engine speed exceeds 115% of normal running speed for more than 0.3 seconds | Shutdown | Contact an authorized distributor/dealer for service |
| Eng Speed Low | Eng Speed Low | Engine speed drops below 85% of normal running speed for more than 3 seconds | Shutdown | Reduce the load; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists |
| Engine Speed High | Engine Speed High | Engine speed exceeds 115% of the normal running speed for more than 0.3 seconds. | Shutdown | Contact an authorized dealer for service. |
| Engine Speed Low | Engine Speed Low | Engine speed drops below 85% of the normal running speed for more than 3 seconds. | Shutdown | Reduce the load. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service. |
| Exer Not Sch | Exercise Not Scheduled | No exercise is scheduled on the controller. | Warning | Set the exerciser per Section 3.6 |
| Frequency High | Frequency High | Governed frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds. Active 10 seconds after engine start. | Shutdown | Contact an authorized distributor/dealer for service |
| Frequency Low | Frequency Low | Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds. Active 10 seconds after engine start. | Shutdown | Reduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists |
| Lo Crank Vlt | Low Cranking Voltage | Battery voltage dropped below 3.5 VDC during engine cranking. | Warning | Charge or replace the battery. |
| Locked Rotor | Locked Rotor | No engine rotation sensed during cranking; shuts down 3 seconds after detection | Shutdown | Check the battery. Check for loose connections. Contact an authorized dealer for service. |
| Low Oil Level or Oil Pressure | Low Oil Level or Oil Pressure | Oil level switch on the 26 kW indicates low oil level. LOP switch indicates low oil pressure for more than 5 seconds. Active 30 seconds after crank disconnect. Does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if low. Check the oil level or oil pressure switch and wiring. If fault persists, do not run the generator set; contact an authorized dealer. |
| MainPwrOverL | MainPwrOverL | Main power overload; an over current fault on the controller output (short circuit). | Shutdown | Contact an authorized distributor/dealer for service |
| Not in Auto | Not in Auto | The generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored. | Warning | Press AUTO to place the generator set in Automatic mode, when appropriate. |
| Oil Press Low | Oil Pressure Low | The LOP switch indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect (30 second inhibit). The low oil pressure shutdown does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. Check the oil pressure switch and wiring. If the fault persists, do not run the generator set. Contact an authorized dealer for service. |
| Over Crank | Over Crank | Three unsuccessful starting attempts. | Shutdown | Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized dealer for service. |
| Spd Sens Flt | Speed Sensor Fault | Engine speed sensor has failed or engine stalled. | Shutdown | Contact an authorized distributor/dealer for service |
| Volts L1-L2 High | Volts L1-L2 High | Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds. | Shutdown | Contact an authorized distributor/dealer for service |
| Volts L1-L2 Low | Volts L1-L2 Low | Output voltage falls below 80% of the nominal system voltage for more than 10 seconds. | Shutdown | Reduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists |