The Generac 480c is a 0.66 L engine. It powers generator sets from Generac, including the POWERPACT 55, POWERPACT 66, POWERPACT 70 and QUIETPACT 55.
Also known as: Generac 480c
| Displacement | 0.66 L |
|---|
Compiled from service & troubleshooting documentation across every generator set that uses the Generac 480c.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Engine Oil Level | Check | 8 hr | At least every eight hours of operation, or before use | |
| Foam Precleaner | Clean | 25 hr | 3 mo | Every three months or every 25 hours, whichever occurs first |
| Spark Arrestor | Clean | 50 hr | Inspect and clean every 50 hours or once each year, whichever comes first | |
| Air Pre-filter | Clean | 100 hr | From RV Generator Service Interval list | |
| Engine Oil and Oil Filter | Change | 100 hr | First service — Every 100 operating hours; more often under heavy load or high ambient temperature | |
| Spark Plug | Clean | 100 hr | Clean plug and reset gap every 100 hours | |
| Spark Plugs | Inspect | 100 hr | RV Generator Service Interval list | |
| Paper Air Filter Element | Replace | 250 hr | ||
| Fuel Filter | Replace | 400 hr | Gasoline only; once each year or every 400 hours, whichever comes first | |
| Spark Plugs | Replace | 500 hr | ||
| Valve Lash | Adjust | 500 hr | First service — 1st 50 hours, then every 500 hours | |
| Battery | Test | 6 mo | Every six months - check state of charge and condition with hydrometer |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Spark plug gap | 0.030 | inch (0.8 mm) | |
| Other | AC voltage regulation | 115 | volts | at 60 Hertz AC frequency |
| Other | Compression ratio | 8.6 to 1 | ||
| Pressure | Fuel pump outlet pressure | 2.0 to 3.5 | psi | |
| Pressure | LP gas pressure at gaseous fuel solenoid valve and secondary regulator inlet | 11 | inches water column | optimum |
| Pressure | LP gas pressure to solenoid valve | 14 | inches water column | do NOT exceed |
| Pressure | LP gas system leak test pressure | 90 | psi (620 kPa) | not less than, test with soap and water solution |
| Pressure | Low oil pressure switch trip point | below 10 | psi | switch closes below this pressure |
| Resistance | Rotor minimum insulation resistance | 1.5 | megohms | |
| Resistance | Stator minimum insulation resistance (120 VAC) | 1.12 | megohms | per formula (rated volts/1000)+1 |
| Speed | No-load frequency | 62 | Hz | governor set point, no electrical load |
| Temperature | High temperature switch setting (LP models) | 284 | °F (140°C) | closes on high temp |
| Temperature | High temperature switch setting (gasoline models) | 270 | °F (132°C) | closes on high temp |
| Torque | Crankcase breather screws | 5-8 | ft-lbs | |
| Torque | Governor clamp bolt | 70 | inch-pounds (8 N-m) | |
| Torque | Rocker arm jam nut | 174 | inch-pounds | |
| Valve clearance | Exhaust Valve | 0.002-0.004 | inch | engine at room temperature, piston at TDC compression |
| Valve clearance | Intake Valve | 0.002-0.004 | inch | engine at room temperature, piston at TDC compression |
| Voltage | Battery cable voltage drop | 0.12 | volts per 100 amperes of cranking current | maximum, for best cold weather starting |
| Voltage | No-Load AC output voltage | 124 | VAC | at 62.5 Hz no-load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | 5W-30 or 5W-20 | Data decal (SAE VISCOSITY) alternate viscosity | |||
| Engine oil | SAE 10W-30 | API classification 'For Service SF' | 1.8 liters | Crankcase capacity 1.8 liters or 1.9 quarts with oil filter change; do not pour in additives | |
| Engine oil | SAE 30 or 10W-30 | Data decal (SAE VISCOSITY); temperature 40°F and higher | |||
| Engine oil | SAE 5W-30 | API classification 'For Service SF' | Used to refill crankcase during out-of-service storage | ||
| Fuel | High quality UNLEADED gasoline | Leaded REGULAR grade acceptable substitute; alcohol content must not exceed 10 percent ethanol; do NOT use methanol | |||
| Other | LP (liquid propane) gas | Vapor withdrawal type systems only |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Tools: 10mm allen wrench, feeler gauge, crow's foot torque wrench
Tools: Pliers
⚠ Adjustment must be done only when unit is running at correct governed no-load speed
⚠ Insulation resistance testers are a source of high and dangerous electrical voltage
Tools: Hi-pot tester or megohmmeter
⚠ Damage will result if the battery connections are made in reverse.
⚠ DO NOT USE ANY FLAME TO TEST FOR LEAKS.
Tools: soap and water solution, separate 12 volt DC source
⚠ You must not allow the unit to overheat during prolonged operation.
⚠ DO NOT FILL ABOVE THE 'FULL' MARK.
Tools: suitable container for oil, clean lint-free cloth
⚠ Never operate the engine with the oil level below the 'Add' mark.
⚠ DO NOT FILL ABOVE THE 'FULL' MARK.
Tools: clean lint-free cloth
⚠ Do not blast the spark plug to clean.
Tools: wire brush, commercial solvent, wire feeler gauge
⚠ DO NOT TWIST the foam precleaner
Tools: clean cloth
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120 | single phase | 120 VAC loads only - one load with maximum total wattage equal to the generator's rated power output; 120V across the generator output terminals | T1 (red), T2 (white), T3 (black), green ground; grounded neutral | Figure 1.1/5.1 - Connection for 120 Volts Only |
| 120 VAC only | 1-Phase | Single load, 120V across output terminals | 11P/22P, 33/44 | Max wattage equal to rated output |
| 120/240 | single phase | 120/240 VAC loads - one load with maximum total wattage equal to rated output at 240V; or two separate loads each up to half rated output at 120V | T1 (red), T3 (black) are 'hot'; T2 (white) is the grounded neutral; green lead connects to ground | Figure 1.2/5.3 - Connection for 120/240 Volts; units not listed per RVIA/ANSI when reconnected for dual voltage output |
| 120/240 VAC | 1-Phase | Dual voltage output, two hot leads T1(11P/44 red) T3(33 black), neutral T2 (22P/33 white) | 11P, 22P, 33, 44 | No longer RVIA listed if reconnected for dual voltage |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Generac 480c has a displacement of 0.66 liters.
The Generac 480c powers 4 generator set(s), including Generac POWERPACT 55, Generac POWERPACT 66, Generac POWERPACT 70, Generac QUIETPACT 55.
A commonly reported issue on generators using the Generac 480c is: ENGINE WILL NOT CRANK.