Home›Engines›Cummins/Onan QSK60-G6 NR2

Cummins/Onan QSK60-G6 NR2 Engine

The Cummins/Onan QSK60-G6 NR2 is a 60.2 L 16-cylinder turbocharged and low temperature after-cooled engine rated at 1800 rpm, producing up to 1905 kW. It powers generator sets from Cummins/Onan, including the 1750DQKAA, 2000DQKAB, DQKAA and DQKAB. It holds 334 L (88.2 gal) of oil and 492 L (130.0 gal) of coolant.

Also known as: Cummins Inc. QSK60-G6 NR2

Part of the Cummins/Onan QSK60 engine family — 31 variants share parts & fitment.

60.2 L
Displacement
16
Cylinders
1800 rpm
Rated speed
1905 kW
Gross power

Engine specifications

Oil capacity334.0 L
Coolant capacity492.0 L
Displacement60.2 L
Cylinders16
AspirationTurbocharged and low temperature after-cooled
Rated speed1800 rpm
Gross power1905 kW

Common problems

15
  • Emergency stop
    Fix: Annunciated whenever either emergency stop signal is received from an external switch.
  • Battle short mode
    Fix: If enabled and the battle short switch is active, some shutdown faults will be bypassed. However, emergency stop shutdowns and other critical faults are not bypassed.
  • General prime mover protection - Low and high battery voltage warning
    Fix: Indicates status of battery charging system (failure) by continuously monitoring battery voltage.
  • Derate
    Fix: The Derate function reduces output power of the genset in response to a fault condition. In utility parallel mode, it actively reduces power by lowering the base load kW to the derated target kW.
  • Under frequency shutdown 81u
  • Reverse power shutdown 32
  • General prime mover protection
    Fix: Low and high battery voltage warning - Indicates status of the battery charging system (failure) by continuously monitoring battery voltage. Weak battery warning - The control system will test the battery each time the genset is signaled to start and indicate a warning if the battery indicates impending failure. Low coolant level warning – Can be set up to be a warning or shutdown.
  • Configurable alarm and status inputs
    Fix: The control accepts up to four configurable alarm or status inputs. The control is programmable for warning, derate, shutdown, shutdown with cooldown or status indication and for labeling the input.
  • Weak battery warning
    Cause: The control system will test the battery each time the genset is signaled to start and indicate a warning if the battery indicates impending failure.
  • Overspeed shutdown
    Cause: Default setting is 115% of nominal.
  • Off load running (protection)
    Cause: This feature protects the engine in the event the genset is being called to go off load for too long.
  • Low lube oil pressure warning/shutdown
    Cause: Level is preset (configurable with InPower or HMI) to match the capabilities of the engine used. Control includes time delays to prevent nuisance alarms.
  • Low coolant temperature warning
    Cause: Indicates that engine temperature may not be high enough for a 10 second start or proper load acceptance.
  • Low coolant level warning
    Cause: Can be set up to be a warning or shutdown.
  • Low and high battery voltage warning
    Cause: Indicates status of battery charging system (failure) by continuously monitoring battery voltage.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSK60-G6 NR2.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterDry replaceable element—
Fuel filterDual element, 10 micron filtration, spin-on fuel filters with 15 micron water separator—
Oil filterFour spin-on, combination full flow filter and bypass filters—
Battery2200 amps minimum at -18C to 0C ambient, 24 volt negative ground—
CoolantCoolant capacity with standard set-mounted radiator492.0 L—
OilLube oil capacity334.0 L—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service specifications

54
TypeItemValueUnitCondition
OtherAC waveform THD (THDV)< 5%no load to full linear load
OtherAC waveform total harmonic distortion< 5% no load to full linear load, < 3% for any single harmonic
OtherBMEP at set rated load (prime)1885kPaprime rating
OtherBMEP at set rated load (standby)2109kPastandby rating
OtherBreaker fail to synchronize default time delay120sadjustable 10–900 s
OtherCompression ratio14.5:1
OtherDerate above 1402 m (4600 ft) / 40 °C4.5% per 305 m (1000 ft) and 11.0% per 10 °C (18 °F)standby and prime
OtherFrequency regulationIsochronous
OtherGovernor regulation classISO8528 Part 1 Class G3
OtherHigh AC voltage shutdown default110%% of nominal voltagefor 10 s; adjustable 105–125%, 0.1–10 s
OtherInstantaneous pickup (Ii) range (Micrologic 3.0 and 5.0)1.5–12 x Inx In
OtherLong-time delay tr0.5–24sat 6 x Ir
OtherLong-time pickup (Ir) adjustment range0.4–1.0 x Inx Insensor plug rating In
OtherLow AC voltage shutdown default85%% of reference voltagefor 10 s; adjustable 50–95%, 2–20 s
OtherOver frequency shutdown/warning default6Hz above nominalfor 20 s, disabled; adjustable 2–10 Hz above set point, 1–20 s
OtherOver load (kW) warning default105%% of rated kWadjustment range 80–140%, 0–120 s delay; default 60 s
OtherPiston speed11.4m/s
OtherRandom frequency variation± 0.25%
OtherReverse Var shutdown default20%% of rated Varfor 10 s; adjustable 15–50%, 10–60 s
OtherReverse power shutdown default10%% of standby kWfor 3 s; adjustable 5–20%, 1–15 s
OtherShort circuit protection threshold175%% of ratingoutput current on any phase
OtherTelephone Harmonic Factor (THF)< 3
OtherTelephone Influence Factor (TIF)< 50per NEMA MG1-22.43
OtherUnder frequency shutdown default6Hz below referencefor 10 s; adjustable 2–10 Hz below set point, 5–20 s
OtherWire stripping length1.38 In (35 mm)in
PressureBMEP at set rated load2193kPaPrime rating
PressureBMEP at set rated load2413 (350)kPa (psi)standby rating
PressureBMEP at set rated load2710kPaStandby rating
PressureMaximum air cleaner restriction3.7kPa
PressureMaximum air cleaner restriction6.2kPa
PressureMaximum back pressure6.7kPa
PressureMaximum back pressure6.8kPaexhaust
PressureMaximum back pressure6.8 (27)kPa (in H2O)
PressureMaximum cooling air flow static restriction0.12kPa
PressureMaximum fuel inlet restriction16.9kPa
PressureMaximum fuel inlet restriction16.9 (5)kPa (in Hg)
PressureMaximum fuel inlet restriction30kPa
PressureMaximum fuel return line restriction34kPa
PressureMaximum fuel return line restriction34 (10)kPa (in Hg)
SpeedOverspeed limit2070rpm
SpeedOverspeed limit2100 ±50rpm
SpeedRated speed1800rpm60 Hz
TemperatureAmbient design (standard set-mounted radiator)50°C
TemperatureExhaust temperature at set rated load (prime)463°Cprime
TemperatureExhaust temperature at set rated load (standby)469°Cstandby
TemperatureMaximum aftercooler inlet temp49°C
TemperatureMaximum aftercooler inlet temp66 (150)°C (°F)
TemperatureMaximum fuel inlet temperature71°C
TemperatureMaximum jacket water outlet temp104 (220)°C (°F)optional remote radiator cooling
TemperatureMaximum jacket water outlet temp (remote radiator)104°Cstandby
TorqueCircuit breaker terminal tightening torque (AWG 1/0...750 kcmil)548.75 Lbf.In (62 N.m)Lbf.In0.08…0.62 in² (50…400 mm²)
VoltageRandom voltage variation± 0.5%
VoltageStandard temperature rise150°CStandby at 40 °C ambient
VoltageVoltage regulation, no load to full load± 0.5%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelASTM D975 No. 2-DASTM D975 No. 2-DCetane number: 40-50. 300-500 ppm Sulfur.
FuelASTM D975 No. 2-D, 300-500 ppm SulfurASTM D975Cetane number: 40-50. Reference conditions: air inlet temperature 25 °C (77 °F), fuel inlet temperature 40 °C (104 °F)
FuelDiesel

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

10
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase has dropped below a preset value.ShutdownAdjustable 50-95% of reference voltage, time delay 2-20 seconds; default 85% for 10 seconds.
32Reverse power shutdownReverse power detected.ShutdownAdjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds.
40Reverse Var shutdownReverse reactive power detected.ShutdownAdjustable 15-50% of rated Var output, delay 10-60 seconds; default 20%, 10 seconds.
46Negative sequence overcurrent warningExcessive imbalances in the three phase load currents and/or power factors.WarningControl protects generator from damage due to phase imbalance.
51Overcurrent warning/shutdownImplementation of the thermal damage curve with instantaneous trip level based on CT ratio and application power rating.ShutdownAmpSentry protective relay action; see document R1053 time over current curve.
51GGround fault overcurrentDetects a ground fault via external ground fault relay contact input or measured ground current from external CT.ShutdownTime delays and thresholds adjustable via InPower or HMI.
59High AC voltage shutdownOutput voltage on any phase exceeds preset values; trip time inversely proportional to amount above threshold.ShutdownAdjustable 105-125% of nominal voltage, time delay 0.1-10 seconds; default 110% for 10 seconds.
81 uUnder Frequency ShutdownGenset output frequency cannot be maintained. Adjustable 2-10 Hz below reference governor set point, time delay 5-20 s. Default 6 Hz, 10 s.Shutdown
81oOver frequency shutdown/warningGenset is operating at a potentially damaging frequency level.WarningAdjustable 2-10 Hz above nominal governor set point, 1-20 second delay; default 6 Hz, 20 seconds, disabled.
81uUnder frequency shutdownGenset output frequency cannot be maintained.ShutdownAdjustable 2-10 Hz below reference governor set point, 5-20 second delay; default 6 Hz, 10 seconds.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Trip Unit Operation Verification diagnostic

Tools: Trip unit test kit

  1. Connect a test kit to the trip unit test plug receptacle.
  2. Perform verification tests per instructions shipped with the test kit to verify trip unit functions.
Battery replacement / battery rack installation maintenance
  1. Isolate DC supply before working on battery connections.
  2. Install battery rack with hold-down, floor standing.
  3. Install battery with minimum 2200 amps capacity at -18 °C to 0 °C.
  4. Verify 24 volt negative ground connection.
Trip Unit Switch Adjustment operation

⚠ Wait a minimum of 15 minutes after circuit breaker trips before resetting to allow thermal imaging to reset completely to zero.

Tools: Wire seal MICROTUSEAL

  1. Open switch cover.
  2. Adjust the appropriate switches to desired values.
  3. Replace switch cover.
  4. Use wire seal MICROTUSEAL, if necessary, to provide tamper evidence.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
124703-phaseWye, 3-phaseWinding No. 87; Feature Code B567; ADS-521; Temp rise 105/80 C; Duty S/P; Max surge kVA 6038
12470-138003Wye, 3-phaseWinding no. 6062Temp rise 125/105/80 °C; ADS-521; feature code B448; max surge kVA 91
12470-138003-phaseWye, 3-phaseWinding No. 91; Feature Code B448; ADS-521; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 6062
13200-138003-phaseWye, 3-phaseWinding No. 91; Feature Code B612; ADS-521; Temp rise 105/80 C; Duty S/P; Max surge kVA 6062
138003-phaseWye, 3-phaseWinding No. 91; Feature Code B610; ADS-521; Temp rise 80 C; Duty S; Max surge kVA 6833
220/38036 leads6Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C
240/41636 leads6Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C
254/44036 leads6Winding no. 312; 125°C rise rating 2000 kW / 2500 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C
277/48036 leads6Winding no. 312; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C
277/4803Wye, 4 WireFeature code R002-2 Voltage-277/480, 3 Phase, Wye, 4 Wire
346/60036 leads6Winding no. 07; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00220 Ohms; rotor resistance 2.31 Ohms @22°C
3803Wye, 3-phaseWinding no. 7327Temp rise 150/125/105 °C; ADS-335; feature code B595; max surge kVA 312
3803-phaseWye, 3-phaseWinding No. 13; Feature Code B595; ADS-515; Temp rise 150/125/105 C; Duty S/P/C; Max surge kVA 7327
41603Wye, 3-phaseWinding no. 6307Temp rise 125/105/80 °C; ADS-324; feature code B467; max surge kVA 51
41603-phaseWye, 3-phaseWinding No. 51; Feature Code B467; ADS-518; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 6307
4403-phaseWye, 3-phaseWinding No. 312; Feature Code B663; ADS-334; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 7361
4803Wye, 3-phaseWinding no. 7361Temp rise 125/105/80 °C; ADS-333; feature code B462; max surge kVA 312
4803-phaseWye, 3-phaseWinding No. 312; Feature Code B462; ADS-334; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 7361
6003Wye, 3-phaseWinding no. 7361Temp rise 125/105/80 °C; ADS-333; feature code B465; max surge kVA 07
6003-phaseWye, 3-phaseWinding No. 07; Feature Code B465; ADS-334; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 7361

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan QSK60 family

201
Part #DescriptionCategory
140-3288-02Cleaner, AirAir filter
140-3813Element, Air Cleaner PrimaryAir filter
140-3814Element, Safety (Air Cleaner)Air filter
140-3815Cleaner, Air (Dust Ejector)Air filter
140-3963Cleaner, Air (Spec A-C Metal)Air filter
AF25593Element, Replacement (Spec A) (Fleetguard Part Number)Air filter
AF25708MElement, Replacement (Spec D-E) (Fleetguard Part Number)Air filter
AF25750Element, Replacement (Spec B-C) (Fleetguard Part Number)Air filter
511-0161-17Belt, V RibbedBelt
M-3649982Juntade culata de cilindro - sobredimensionada 0,020" - M-3649982Cylinder head盖板
QSK60Gas engineEngine
QSK60-G9Engine model for C2500 D5A generator setsEngine
QSK60GEngine model QSK60GEngine
4321098765Fault Acknowledge ButtonFault acknowledge button
130-4546Bracket, Mounting – Coolant HeaterFluid
130-4552Cover, Coolant HeaterFluid
338-3335-01Harness, Wiring – AC – Coolant Heater (From Coolant Heater Bottom To Coolant Heater Control Box) (Includes Conduit Connectors) (30”)Fluid
338-3335-09Harness, Wiring – AC – Coolant Heater (From Coolant Heater Bottom To Coolant Heater Control Box) (Includes Conduit Connectors) (108”)Fluid
338-3831Harness, Wiring – DC – Engine Heater (From Coolant Heater Control Box To Engine And Main Engine Harness) (Includes Parts Marked *)Fluid
FS1006Filter, Fuel Water SeparatorFuel filter
130-3684GasketGasket
130-5099GasketGasket
130-6405Gasket, RadiatorGasket
130-7145Gasket, RadiatorGasket
130-7232Gasket, Radiator (4")Gasket
130-7293Gasket, Radiator (65NB)Gasket
154-3182Gasket, Flange (Fuel Line)Gasket
155-3704Gasket, Exhaust (10" BS Flange)Gasket
155-4109Gasket, FlangeGasket
155-4601Gasket, ExhaustGasket
155-4735Gasket, Exhaust (10" ANSI Flange)Gasket
186-6088Plate, Valve SpringGasket
186-6090Carrier, Valve SpringGasket
186-6091Cotter, ValveGasket
186-6092Guide, ValveGasket
186-6093Seal, Valve StemGasket
186-6109Gasket, Cylinder HeadGasket
186-6112Gasket, Cylinder HeadGasket
186-6436Gasket, Cylinder HeadGasket
186-6758Valve, InletGasket
186-7004Insert, Inlet ValveGasket
186-7005Insert, Exhaust ValveGasket
186-7013Head Assy, CylinderGasket
186-7014Head Assy, CylinderGasket
186-7015Head Assy, CylinderGasket
319-3950Gasket, Operator PanelGasket
319-3951Gasket, Switch PanelGasket
330-0141-04Gasket, CoverGasket
MCBQSK0045Turbocharger Installation KitGasket
MCBQSK0048Water Pump Gasket SetGasket
MCBQSK0058Water Pump Gasket SetGasket
128-0108Insulation, Hose – Bulk (Order By The Foot – 12 Feet Required)Hose
130-4885Radiator (Includes Jacketwater, Aftercooler, Cap, Overflow Hose and Sight Gauge Sevice Parts) 130–3588Hose
416-0680Cable, Battery (10")Hose
501-0838Line, Fuel (DN80 Gas 500mm)Hose
502-0656Adapter, Male (1–5/16–12 Tubing to 1” Pipe)Hose
502-0827Fitting, Hose – Barbed (1/2” ID Pipe to 3/4” ID Hose)Hose
502-0836Fitting, Brass – Hose – Barbed (3/4” Pipe to 3/4” Hose)Hose
502-1257Connector, Hose – Barbed (Fits 3/4” ID Hose)Hose
503-0189Clamp, HoseHose
503-0249Hose − Bulk (Order by the Foot − 3 Feet Required)Hose
503-1136Clamp, HoseHose
503-1418Hose − Bulk (1/4” ID) (Order By The Foot − 18 Feet Required)Hose
503-1634-01Hose, Rubber (3/4” ID x 4”)Hose
503-1726Hose (5” ID x 6”)Hose
503-1727Hose, Radiator (3” ID x 10”)Hose
503-1728Hose (3” ID x 5–1/2”)Hose
503-1745Hose – Bulk – Front Grease Fitting (Order By The Foot – 2 Feet Required)Hose
503-1863Hose, Radiator (1–1/2” ID x 4”)Hose
503-1872-01Clamp, HoseHose
503-1872-05Clamp, HoseHose
503-1872-09Clamp, Hose (5” ID)Hose
503-2204-06Hose, Steam (19mm x 300)Hose
503-2204-07Hose, Steam (19mm x 800)Hose
503-2204-08Hose, Steam (19mm x 1000)Hose
503-2204-09Hose, Steam (19mm x 1700)Hose
503-2518Hose, VentHose
505-1429Nipple, Pipe – Combination (1–1/2” Pipe to 1–1/2” Hose)Hose
505-2086Nipple, Pipe (3/4)Hose
505-2098Nipple, Pipe (1/2)Hose
518-0548-24Clamp, HoseHose
518-0548-25Clamp, Hose (3/8” ID)Hose
0098-6074-02Label, WarningLabel
098-2304Label, WarningLabel
098-2304-01Label, WarningLabel
098-4500DecalLabel
098-4730Label, WarningLabel
098-4732Label, WarningLabel
098-4798Label, WarningLabel
098-5347Label, DangerLabel
098-5347-02Label, DangerLabel
098-5759Label, WarningLabel
098-5822Label, WarningLabel
098-5842Label, CautionLabel
098-6074-02Label, WarningLabel
098-6195Label, CautionLabel
098-6537Label, GroundLabel
098-6650-01Label, DangerLabel
098-6775LabelLabel
098-7614Label, WarningLabel
098-7877Label, Battery WarningLabel
098-7902-01Label, LogoLabel
098-7902-03Label, LogoLabel
098-7902-04Label, LogoLabel
098-7904Label, DangerLabel
098-8075Label, GroundLabel
098-8144Label, InformationLabel
098-8204Label, WarningLabel
098-8220Label, InformationLabel
098-8445Label, InformationLabel
098-8732-02Label, InformationLabel
098-8940Label, WarningLabel
A029M832Label, WarningLabel
A029S884Label, InformationLabel
A029Z072Label, InformationLabel
LF9050Lube, CombinationOil filter
0130-5997-05Cummins Part No. 312/212, 37564; Cummins Part No. 312/212, 37604; Cummins Part No. 212, 37558; Cummins Part No. 212, 37614; Cummins Part No. 212, 37627; Cummins Part No. 313/312, 0179-2921; Cummins Part No. 313/312, 0179-2988; Cummins Part No. 312, 0179-3291; Cummins Part No. 312/212, 130-5791; Cummins Part No. 312/212, 37644; Cummins Part No. 312/212, 37624; Cummins Part No. 312/212, 37625; Cummins Part No. 212, 37648; Cummins Part No. 212, 37643; Cummins Part No. 212, 37678; Cummins Part No. 212, 37665; Cummins Part No. 312/212, 37676; Cummins Part No. 312/212, 37610; Cummins Part No. 313/212, 37642Service part / kit
0179-2862Nema 284T frame has the following arrangement: 6311 C3 / 18gram Polyrex – EM /20,000hService part / kit
0179-3291Nema 284T frame has the following arrangement: 6311 C3 / 11gram Polyrex – EM /20,000hService part / kit
098-5387Label, DangerService part / kit
130-5077-02Tube, HeaterService part / kit
130-5078-02Tube, HeaterService part / kit
130-5079-02Tube, HeaterService part / kit
130-5080-02Tube, HeaterService part / kit
130-5089-02Tube, HeaterService part / kit
155-4734Flange, Exhaust (10" ANSI Flange)Service part / kit
155-4736Flange, Exhaust (10" BS Flange)Service part / kit
186-6087Valve, ExhaustService part / kit
186-6089Part 186-6089Service part / kit
3163156Service cable for InPower™Service part / kit
323-1491* Pin, Contact (Used With Inline G)Service part / kit
323-1492* Socket, Contact (Used In Stations 18, 19)Service part / kit
323-1688* Socket, Contact (Used In P1)Service part / kit
323-1718* Pin, Contact (Used In Station 17)Service part / kit
333-0634-02Heater, Coolant - 6420 WattService part / kit
3886301InPower™ electronic service toolService part / kit
4-2002PowerCommand ControlService part / kit
416-1019Boot, Battery (Red)Service part / kit
504-0215Valve, Check (1/4)Service part / kit
504-0239Valve, Ball (3/4)Service part / kit
504-0247Valve, Ball (1/2)Service part / kit
504-0294Valve, Ball (3 Way 2" DN80) - ANSI FlangesService part / kit
504-0295Valve, Ball (3 Way 3" DN80) - ANSI FlangesService part / kit
504-0301Valve, Ball (3 Way 2" DN80) - BS FlangesService part / kit
504-0302Valve, Ball (3 Way 3" DN80) - BS FlangesService part / kit
525-0304Gallon CanService part / kit
525-030512 oz. Pressurized Spray CanService part / kit
525-0306Quart CanService part / kit
5410770Cummins enclosed C2000D5 diesel generator set powered by QSK60G3 engine provides reliable continuous power for Bab Gas Compression Facility.Service part / kit
898-1254-25Sleeving – Heater Leads (59”)Service part / kit
A026N045Bracket, MountingService part / kit
A026N055Bracket, MountingService part / kit
A026N058Leg, BoxService part / kit
A026N061Leg, BoxService part / kit
A026N070Panel, CoverService part / kit
A029F250Insulation, DuctService part / kit
A029F255Insulation, DuctService part / kit
A029S366Lead, GroundService part / kit
A029Y658StudService part / kit
A040C685Bracket, SupportService part / kit
A041U339Shim, Generator MountingService part / kit
A041U341Shim, Generator MountingService part / kit
A056A610RECOMMENDED SPARES LIST (RSL) FOR DQKAD GENERATOR SETSService part / kit
A056A611RECOMMENDED SPARES LIST (RSL) FOR DQKAE GENERATOR SETSService part / kit
A056A612RECOMMENDED SPARES LIST (RSL) FOR DQKAF GENERATOR SETSService part / kit
A056F840Recommended Spares List (RSL) for DQKAN Generator SetsService part / kit
M-3089173Bushing - CamshaftService part / kit
M-4007741Bushing - CamshaftService part / kit
M-4089083Single Cylinder HeadService part / kit
M-4089200Juego de Junta Modul. N. ° de PiezaService part / kit
M-4089201Juego Posenfriador Cuadrante N. ° de PiezaService part / kit
M-4089202Juego Sistema Enfriamiento N. ° de PiezaService part / kit
M-4089231Juego de Junta Modul. N. ° de PiezaService part / kit
M-4089232Juego Posenfriador Cuadrante N. ° de PiezaService part / kit
M-4089307Juego Bomba Inferior N. ° de PiezaService part / kit
M-4089308Juego Combustible Inferior N. ° de PiezaService part / kit
M-4089508Juego de Junta Modul. N. ° de PiezaService part / kit
M-4089509Juego Sistema Enfriamiento N. ° de PiezaService part / kit
M-4089874Juego Bloque Inferior N. ° de PiezaService part / kit
M-4955369Juego Posenfriador Cuadrante N. ° de PiezaService part / kit
M-4955370Juego de Junta Modul. N. ° de PiezaService part / kit
M-4956000Culata Cilindro Simple N. ° de Pieza ARService part / kit
132-0475Pump, Water (Remote)Pump
A054B161Schematic DiagramSchematic diagram
323-1445* Seal, Cable (Used With Station 17)Seal
323-1708# Seal, Cable (P8)Seal
503-2129-05Line, Vent – Flexible – With One Male Pipe Swivel and One Female Pipe Swivel With O–Ring Face Seal (1/4” ID x 94–1/2”) Right SideSeal
509-0283-01SealSeal
509-0478Seal - O RingSeal
193-0486Sender, Low Coolant LevelSensor
338-3832Harness, Wiring – Low Coolant Level Sender (4 Wire, 169”) (Includes Parts Marked *)Sensor
504-0262Valve, SolenoidSensor
AM47478880Temperature Sender, Exhaust Temperature Replaces 47367178, 87482353, LB52S00001P1Sensor
AM47520140Sensor, 8-Pin/NH3/Ammonia Replaces 47368956, 84382712Sensor
AM47520143Sensor, Def/AdBlue Quality Replaces 84553250Sensor
AM504372225Sensor, MAP Temperature/Pressure Replaces 2852821, 4896794, 504073323Sensor
M-3331970Spacer Gasket for QSK45 and QSK60 Engine applicationsSpacer gasket
309-0649Thermostat (Includes Connector Socket) (S11)Thermostat
309-0711ThermostatThermostat
M-4089203Juego Turbo e Interenfriador N. ° de PiezaTurbocharger
M-4089233Juego Turbo e Interenfriador N. ° de PiezaTurbocharger

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan QSK60-G6 NR2?

The Cummins/Onan QSK60-G6 NR2 engine has an oil capacity of 334.0 liters.

What is the displacement of the Cummins/Onan QSK60-G6 NR2?

The Cummins/Onan QSK60-G6 NR2 has a displacement of 60.2 liters with 16 cylinders.

Which generators use the Cummins/Onan QSK60-G6 NR2 engine?

The Cummins/Onan QSK60-G6 NR2 powers 6 generator set(s), including Cummins/Onan 1750DQKAA, Cummins/Onan 2000DQKAB, Cummins/Onan DQKAA, Cummins/Onan DQKAB, Cummins/Onan DQKAD.

What is a common problem with the Cummins/Onan QSK60-G6 NR2 engine?

A commonly reported issue on generators using the Cummins/Onan QSK60-G6 NR2 is: Emergency stop. Fix: Annunciated whenever either emergency stop signal is received from an external switch..