| 1123 | Shutdown After BS | | Shutdown | |
| 1124 | Delayed Shutdown | | Warning | |
| 1131 | Battle Sh Active | | Warning | |
| 121 | Speed Signal Lost | | Shutdown | |
| 1311 | Customer Input #1 | Optional customer selection (example: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Default display name Customer Fault 1; default status None. | | Each fault function can be programmed (using service tool): enable/disable input (default enable), status/warning/shutdown, active closed or open, change display name up to 19 characters. |
| 1312 | Customer Input #2 | Optional customer selection. Default display name Ground Fault; default Warning. | | Programmable using service tool (enable/disable, status, active state, display name). |
| 1317 | Customer Input #3 | Optional customer selection. Default display name Low Fuel; default Warning. | | Programmable using service tool (enable/disable, status, active state, display name). |
| 1318 | Service Engine (begin spec J) | Warning lamp. Emissions criteria might not be met due to engine running in open loop, lean mixture, rich mixture, or a failed fuel system component. | Warning | |
| 1334 | Crit Scaler OR | | Shutdown | |
| 1335 | Noncrit Scaler OR | | Warning | |
| 135 | Oil Pressure Sensor H | | Warning | |
| 141 | Oil Pressure Sensor L | | Warning | |
| 1416 | Fail To Shutdown | | Warning | |
| 1417 | Powr Down Error | Warning lamp. The controller cannot power down because of some unknown condition; possible drain on battery. | Warning | Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Warning lamp. Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Shutdown lamp. Indicates local Emergency Stop. | Shutdown | To reset: pull the button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required. |
| 1434 | Remote E-Stop | Shutdown lamp. Indicates remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Warning lamp. Set is not operating; warning occurs when engine coolant temperature is 70 deg F (21 deg C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply (blown fuse or disconnected heater cord). Check for low coolant level and replenish; look for coolant leakage points and repair. |
| 1438 | Fail To Crank | Shutdown lamp. Possible fault with control, speed sensing or starting system. | Shutdown | See code 441 for corrective action. |
| 144 | Coolant Sensor High | | Warning | |
| 1442 | Weak Battery | Warning lamp. During cranking, battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time. | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Shutdown lamp. Dead battery - engine will not start. | Shutdown | See code 441 for corrective action. |
| 1444 | KW Overload | | Warning | |
| 1445 | Short Circuit | | Shutdown | |
| 1446 | High AC Voltage | | Shutdown | |
| 1447 | Low AC Voltage | | Shutdown | |
| 1448 | Under Frequency | Shutdown lamp. Possible fuel system problem or overload condition. | Shutdown | Check for dirty or plugged air filter and replace if necessary. Check operation by disconnecting load and restarting generator set. Fuel system requires adjustment; contact an authorized service center. Gaseous fuel delivery to the set is inadequate; contact an authorized service center. Reset the control and restart after correcting the problem. |
| 1449 | Over Frequency | | Warning | |
| 145 | Coolant Sensor Low | | Warning | |
| 1452 | Gen CB Not Close | | Warning | |
| 1453 | Gen CB Not Open | | Warning | |
| 1459 | Reverse Power | | Shutdown | |
| 146 | Pre-High Coolant Temp | Warning lamp. Engine has begun to overheat (coolant temperature has risen to an unacceptable level). | Warning | Reduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove obstructions to airflow. If engine can be stopped, follow code 151 procedure. |
| 1461 | Loss Of Field | | Shutdown | |
| 1466 | Modem Failure | | Warning | |
| 1468 | Network Error | | Warning | |
| 1469 | Speed/Hz Match | | Shutdown | |
| 1471 | Over Current | | Warning | |
| 1472 | Over Current | | Shutdown | |
| 151 | High Coolant Temp | Shutdown lamp. Engine has overheated (coolant temperature above the shutdown trip point). | Shutdown | Allow engine to cool completely. Check coolant level and replenish; look for coolant leaks. Check for obstructions to cooling airflow. Check fan belt and repair or tighten. Check blower fan and circulation pumps on remote radiator installations. Reset control and restart after correcting problem. |
| 197 | Low Coolant Level | Warning lamp (Optional). Engine coolant level has fallen below the warning trip point. | Warning | If powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure. |
| 2327 | PTC Fault | | Warning | |
| 2329 | Low S1 Frequency | | Warning | |
| 2331 | Low S1 Voltage | | Warning | |
| 2335 | Excitation Fault | | Shutdown | |
| 2336 | Memory Error | | Shutdown | |
| 2337 | Pwr Tran Disabled | | Warning | |
| 2338 | Pwr Tran Failure | | Warning | |
| 2339 | Pwr Down Enabled | | Warning | |
| 234 | Overspeed | | Shutdown | |
| 2341 | High Control Temp | | Warning | |
| 2342 | Too Long In Idle (10 min.) | Warning lamp. Genset has been in Idle mode too long (10 minutes maximum). | Warning | |
| 235 | Low Coolant Level | Shutdown lamp (Optional). Engine coolant level has fallen below the shutdown trip point. | Shutdown | Allow engine to cool completely. Check coolant level and replenish if low; look for coolant leakage points and repair. Reset control and restart after locating and correcting problem. |
| 2358 | High S1 Voltage | | Warning | |
| 2396 | S1 CB Not Close | | Warning | |
| 2397 | S1 CB Not Open | | Warning | |
| 2966 | PTC Timeout | | Warning | |
| 2967 | Governor Fault | | Warning | |
| 2968 | AVR Fault | | Warning | |
| 2969 | LON Failure | | Warning | |
| 2972 | Field Overload | | Shutdown | |
| 359 | Fail To Start | Shutdown lamp. Possible fuel system problem (engine cranks but fails to start). | Shutdown | Open any closed fuel shutoff valve. Check for dirty or plugged air filter and replace if necessary. Gaseous fuel delivery to the set is inadequate; contact an authorized service center. Reset the control and restart after correcting the problem. |
| 415 | Low Oil Pressure | Shutdown lamp. Engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. |
| 441 | Low Bat Voltage | Warning lamp. Battery voltage supply to the control is approaching a low level at which unpredictable operation will occur. | Warning | Check battery charger fuse; recharge or replace the battery. Clean the battery cable terminals and tighten all connections. Check battery charge voltage float level if applicable (raise float level). |
| 442 | High Bat Voltage | Warning lamp. Battery voltage supply to the control is approaching a high level at which damage to the control can occur. | Warning | Check float level on battery charger if applicable (lower float level). |
| Fault 1 | Fault 1 (red) | Engine shut down because of a system fault; part of a 10-second time-delay shutdown circuit (customer-wired). | Shutdown | |
| Fault 2 | Fault 2 (red) | Engine shut down because of a system fault; part of a non-time-delay shutdown circuit (customer-wired). | Shutdown | |
| High Engine Temperature | High Engine Temperature (red) | Engine shut down due to excessively high coolant temperature (greater than 230°F / 110°C). | Shutdown | |
| Low Engine Temperature | Low Engine Temperature (yellow) | Engine temperature less than 65°F (18°C) or 90°F (32°C); possibility engine might not start. | Warning | |
| Low Fuel | Low Fuel (yellow, optional) | Fuel supply pressure is 5 inches (127 mm) WC or less; also indicates operation on secondary fuel supply for dual-fuel sets. | Warning | |
| Low Oil Pressure | Low Oil Pressure (red) | Engine shut down due to excessively low oil pressure (less than 25 psi / 173 kPa). | Shutdown | |
| Overcrank | Overcrank (red) | Engine did not start during the timed cranking period (approx. 75 seconds, including two rest periods). | Shutdown | |
| Overspeed | Overspeed (red) | Engine shut down due to overspeed condition. | Shutdown | |
| Pre High Engine Temperature | Pre High Engine Temperature (yellow) | Engine coolant temperature abnormally high (greater than 220°F / 104°C). | Warning | |
| Pre Low Oil Pressure | Pre Low Oil Pressure (yellow) | Engine oil pressure abnormally low (less than 30 psi / 207 kPa). | Warning | |
| Run | Run indicator (green) | Starter has disconnected and set is running. | Info | |
| Switch-off | Switch-off (flashing red) | Run/Stop/Remote switch is in the Stop position, preventing remote/automatic operation. | Info | |