| 101 | IDLE MODE | Indicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM. | Warning | Remove ground from the engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel. |
| 1122 | Rated/Idle Trans | Rated/Idle transition | Info | |
| 1123 | Shutdown After Battle Short | Shutdown after Battle Short | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | Delayed shutdown | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | When Battle Short mode is enabled, the Warning status indicator is lit along with displayed fault code 1131. Refer to Battle Short Mode description in Section 3. |
| 121 | Speed Signal Lost | Speed signal lost | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 1311 | Customer Input #1 | Customer input #1 (optional customer selection) | | Programmable (service tool): enable/disable input (default enable); status, warning or shutdown (default #1 = None); active closed or open (default closed [ground]); change display name up to 19 characters. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. |
| 1312 | Customer Input #2 | Customer input #2 (optional customer selection) | | Programmable (service tool): enable/disable input (default enable); status, warning or shutdown (default #2 = Warning); active closed or open (default closed [ground]); change display name. |
| 1313−1316 | Network Fault 1 thru 4 | Network fault 1 through 4 | | |
| 1317 | Customer Input #3 | Customer input #3 (optional customer selection) | | Programmable (service tool): enable/disable input; status, warning or shutdown; active closed or open; change display name. |
| 1318 | Customer Input #4 | Customer input #4 (optional customer selection) | | Programmable (service tool): enable/disable input; status, warning or shutdown; active closed or open; change display name. |
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | Noncrit Scaler Out Of Range | Non-critical scaler out of range | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | No message | Info | |
| 135 | Oil Pressure Sensor H | Oil pressure sensor high | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | Oil Pressure Sensor L | Oil pressure sensor low | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 1416 | Fail To Shutdown | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Refer to Battle Short Mode description in Section 3. |
| 1417 | Powr Down Error | The controller cannot power down because of some unknown condition; possible drain on battery | Warning | Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped below the warning trip point | Warning | If generator is powering critical loads and cannot be shut down, wait until the next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Initiates a warning when the engine jacket water coolant temperature falls below 70 deg F (21 deg C); provided to meet NFPA 110 requirements, in conjunction with illumination of the Warning LED. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater connection to power supply: check for blown fuse or disconnected heater cord and correct. Check for low coolant level and replenish if required; look for possible coolant leaks and repair. |
| 1438 | Fail To Crank | Possible fault with control, speed sensing or starting system | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 1442 | Weak Battery | During cranking, battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Dead battery − engine will not start | Shutdown | See code 441 for corrective action. |
| 1444 | KW Overload | kW overload | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | Short Circuit | Short circuit | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | High AC Voltage | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | Low AC Voltage | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |
| 1448 | Under Frequency | Under frequency | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | Over Frequency | Over frequency | Warning | Check fuel or air delivery problem; repair P7/P8 connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC enabled. | Warning | Refer to Section 5. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC enabled. | Warning | Refer to Section 5. |
| 1459 | Reverse Power | Reverse power | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine is operating near cooling system capacity | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check field circuit. |
| 1466 | Modem Failure | Modem failure | Warning | Check for open, short circuit to ground, and loose connections to the modem. |
| 1468 | Network Error | Network error | Warning | Refer to the LonWorks Network publications. |
| 1469 | Speed/Hz Match | Speed/Hz match | Shutdown | Check calibration file. |
| 1471 | Over Current | Over current | Warning | Check load and load lead connections. |
| 1472 | Over Current | Over current | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 151 | High Coolant Temp | Engine has overheated (coolant temperature has risen above the shutdown trip point) | Shutdown | Allow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the warning trip point. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3. |
| 204 | OIL PRESS SENDER | The control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime. | Warning | Reduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped. |
| 212 | Oil Temp Sensor H | Oil temperature sensor high | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | Oil Temp Sensor L | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only). | Shutdown | Check coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; isolate per troubleshooting table 4-18. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system; engine will not crank. | Shutdown | Check fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery. |
| 222 | OVERCRANK | Possible fuel system problem; engine stops cranking. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Inspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated. |
| 224 | FAIL TO SYNCHRONIZE | The generator set has not synchronized to the system bus within the allowable time frame. | | Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay. |
| 226 | FAIL TO CLOSE | Indicates that the paralleling breaker has been given a signal to close, but has not closed properly. | | Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Recharge or replace the battery; see 230 LOW DC VOLTAGE. |
| 2323−2326 | Network Fault 5 thru 8 | Network fault 5 through 8 | | |
| 2327 | PTC Fault | PTC module or communication link not working properly when PTC enabled. | Warning | Check blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Repower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Critical shutdown fault; suspends Battle Short and shuts down immediately. |
| 2336 | Memory Error | Memory error | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | Power transfer disabled | Warning | Use InPower to enable PTC feature; cycle power off for 5 seconds then repower. |
| 2338 | Pwr Tran Failure | Power transfer failure | Warning | Check blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power. |
| 2339 | Pwr Down Enabled | Power down enabled | Warning | None required. |
| 234 | Overspeed | Overspeed shutdown | Shutdown | Critical shutdown fault; suspends Battle Short and shuts down immediately. |
| 2341 | High Control Temp | High control temperature | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle | Genset has been in Idle mode too long. | Warning | Exit idle mode. |
| 235 | Low Coolant Level | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish; look for leaks; reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above over voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5. |