Home›Engines›Cummins/Onan QSK38

Cummins/Onan QSK38 Engine

The Cummins/Onan QSK38 is a 37.8 L 12-cylinder 4-cycle industrial diesel engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the C1250D6E and C1500D6E. It holds 186 L (49.1 gal) of oil and 112 L (29.6 gal) of coolant.

Also known as: Cummins QSK38

Part of the Cummins/Onan QSK38 engine family — 7 variants share parts & fitment.

37.8 L
Displacement
12
Cylinders
1800 rpm
Rated speed
186.0 L
Oil capacity

Engine specifications

Oil capacity186.0 L
Coolant capacity112.0 L
Displacement37.8 L
Cylinders12
Aspiration4-cycle industrial diesel
Rated speed1800 rpm

Common problems

2
  • Derate
    Fix: The Derate function reduces output power of the genset in response to a fault condition. If a Derate command occurs while operating on an isolated bus, the control will issue commands to reduce the load on the genset via contact closures or Modbus. If a Derate command occurs while in utility parallel mode, the control will actively reduce power by lowering the base load kW to the derated target kW.
  • Battle short mode
    Fix: When enabled and the battle short switch is active, the control will allow some shutdown faults to be bypassed. If a bypassed shutdown fault occurs, the fault code and description will still be annunciated, but the genset will not shutdown. This will be followed by a fail to shutdown fault. Emergency stop shutdowns and others that are critical for proper operation (or are handled by the engine ECM) are not bypassed.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSK38.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter—
Battery—
Belt—
Coolant—
Oil—
Spark plug—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

5
ItemActionHoursMonthsNotes
Lubricating oilTest250 hr6 moFirst service — For high horsepower engines with Eliminator™ oil filter option: take oil samples every 250 hours and analyze per Cummins Engine Oil Recommendations Bulletin 3810340; repeat for at least three oil change intervals.
filtersChange1000 hrwith CENTINEL, depending on load factors
ELIMINATOR self cleaning filter coreOther1500 hrRequires servicing only every 1,500 hours. Saves up to 90% of lube system maintenance costs and increases productivity.
fuel filterChange1500 hrFleetguard NanoNet media
engine oilChange4500 hrwith CENTINEL, railway applications

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilCummins Engine Oil Recommendations Bulletin 3810340Used to analyze oil samples for high horsepower engines with Eliminator™ oil filter option.
Fuel40-50 Cetane numberASTM D975 No. 2-D300-500 ppm Sulfur
Fuel40-50 Cetane number, ASTM D975 No. 2-DASTM D975300-500 ppm Sulfur; #2 Diesel low-sulfur/ultra-low sulfur required for start-up
FuelB100 biodieselASTM D6751Must conform prior to blending; revised to include a cold soak test; stability requirement still in effect.
FuelB20 biodiesel blendASTM D7467Applies to biodiesel blends B6–B20; includes oxidation stability requirement; replaces Cummins' previous EMA B20 specification requirement. Must be purchased from a BQ9000 Certified Marketer; B100 must be sourced from a BQ9000 Accredited Producer.
FuelB5 biodieselAll Cummins automotive and industrial engines are compatible with B5 biodiesel.
Fuelbiodiesel (Europe)EN 14214Published by CEN, European Committee for Standardization. Equivalent biodiesel specifications required internationally.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

9
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase has dropped below a preset value. Adjustable over a range of 50-95% of reference voltage, time delay 2-20 seconds. Default value is 85% for 10 seconds. Function tracks reference voltage. Control does not nuisance trip when voltage varies due to the control directing voltage to drop, such as during a V/Hz roll-off or synchronizing.ShutdownShutdown genset.
32Reverse power shutdownAdjustment range: 5-20% of standby kW rating, delay 1-15 seconds. Default: 10%, 3 seconds.ShutdownShutdown genset.
40Reverse Var shutdownShutdown level is adjustable: 15-50% of rated Var output, delay 10-60 seconds. Default: 20%, 10 seconds.ShutdownShutdown genset.
46Negative sequence overcurrent warningControl protects the generator from damage due to excessive imbalances in the three phase load currents and/or power factors.WarningWarning.
51Overcurrent warning/shutdownImplementation of the thermal damage curve with instantaneous trip level calculated based on current transformer ratio and application power rating.ShutdownShutdown or warning.
51GGround fault overcurrentControl detects a ground fault either by an external ground fault relay via a contact input or the control can measure the ground current from an external current transformer. Associated time delays and thresholds are adjustable via InPower or HMI.ShutdownShutdown or warning.
59High AC voltage shutdownOutput voltage on any phase exceeds preset values. Time to trip is inversely proportional to amount above threshold. Values adjustable from 105-125% of nominal voltage, with time delay adjustable from 0.1-10 seconds. Default value is 110% for 10 seconds.ShutdownShutdown genset.
81 uUnder frequency shutdownGenset output frequency cannot be maintained. Settings are adjustable from 2-10 Hz below reference governor set point, for a 5-20 second time delay. Default: 6 Hz, 10 seconds. Under frequency protection is disabled when excitation is switched off, such as when engine is operating in idle speed mode.ShutdownShutdown genset.
81oOver frequency shutdown/warningGenset is operating at a potentially damaging frequency level. Settings are adjustable from 2-10 Hz above nominal governor set point for a 1-20 second time delay. Default: 6 Hz, 20 seconds, disabled.WarningWarning or shutdown.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Series C4E-1D Cast Iron Spring-Flex Mounting Installation installation

Tools: Wrench

  1. Space and arrange isolators per installation drawings; ship fully assembled.
  2. Set isolators on floor or sub-base; align centerlines with equipment mounting holes.
  3. Shim or grout as required; level all base plates at same elevation (1/4 in max difference).
  4. Unless specified, mountings need not be fastened to floor. If required, bolt through slots.
  5. Remove adjusting bolt C with nut B from top housing A; do not discard.
  6. Place machine onto top plate A; weight lowers upper housing onto lower housing.
  7. Align equipment mounting hole to top housing tapped hole.
  8. Turn nuts B up on leveling bolts so they will not interfere with leveling.
  9. Insert bolts C through machine base holes and hand-screw into tapped hole as far as possible.
  10. Adjust each isolator in sequence: screw down one complete turn on adjusting bolt.
  11. Adjust until 1/4 in gap is obtained on all mounts.
  12. Turn nut on adjusting bolt C down against machine leg and lock with wrench.
  13. Installation is complete.
Oil sampling for high horsepower engines with Eliminator™ oil filter option maintenance
  1. Take oil samples every 250 hours of operation.
  2. Analyze samples according to Cummins Engine Oil Recommendations Bulletin 3810340.
  3. Repeat for at least three oil change intervals to ensure consistent oil behavior.
Switching from petrodiesel to B20 on used engines maintenance

⚠ B20 has a solvent nature and may clean the vehicle fuel tank and lines.

  1. Install new fuel filters when switching to B20.
  2. Replace fuel filters at half the standard interval for the next two fuel filter changes.
  3. After the initial period, revert to intervals specified in the O & M manual.
  4. For EPA 2007 on-highway midrange engines, sample oil for the first 6 months to monitor fuel dilution.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan QSK38 family

4
Part #DescriptionCategory
MCBQSK0068Water Pump Gasket SetGasket
M-2885786Cylinder Liner KitService part / kit
M-3007525Cylinder Liner KitService part / kit
M-3022157Cylinder LinerService part / kit

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan QSK38?

The Cummins/Onan QSK38 engine has an oil capacity of 186.0 liters.

What is the displacement of the Cummins/Onan QSK38?

The Cummins/Onan QSK38 has a displacement of 37.8 liters with 12 cylinders.

Which generators use the Cummins/Onan QSK38 engine?

The Cummins/Onan QSK38 powers 3 generator set(s), including Cummins/Onan C1250D6E, Cummins/Onan C1500D6E, Cummins/Onan QSK38.

What is a common problem with the Cummins/Onan QSK38 engine?

A commonly reported issue on generators using the Cummins/Onan QSK38 is: Derate. Fix: The Derate function reduces output power of the genset in response to a fault condition. If a Derate command occurs while operating on an isolated bus, the control will issue commands to reduce the load on the genset via contact closures or Modbus. If a Derate command occurs while in utility parallel mode, the control will actively reduce power by lowering the base load kW to the derated target kW..