RDC Controller

The RDC is a generator-set controller. It is used on generator sets from Kohler, including the 14RES and 20RES.

2
Generator sets
Kohler
Brand
14–20 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Generator sets using this controller

2

Engines paired with this controller

2

Troubleshooting

30

Fault codes

CodeMeaning
LossOfComm2Communication Lost with Secondary Controller

Symptoms & remedies

SymptomCauseRemedy
Accy PwrOver Warning or MainPwrOverL ShutdownInternal circuit protection is activated.Press OFF to reset. Contact an authorized Kohler distributor/dealer for service.
Auxiliary winding circuit breaker tripped.Reset the circuit breaker (located in controller’s service access area). Contact an authorized distributor/dealer for service if breaker trips repeatedly.
Battery acid cleanupAdd 500 g (1 lb.) of bicarbonate of soda to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid until all evidence of a chemical reaction has ceased. Flush the resulting liquid with water and dry the area.
Battery acid on skinFlush the affected area for 15 minutes with large quantities of clean water and seek medical aid if necessary.
Battery acid splashes in the eyesImmediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid.
Battery short circuitsDisconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (-) lead first when disconnecting the battery. Reconnect the negative (-) lead last when reconnecting the battery.
Bodily injury and/or equipment damageBattery short circuitsDisconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Controller display backlight is off.Backlight turns off after about 1 minute with no activity. Backlight will turn on when a button is pressed or the generator set starts.
Controller display is off.Low or no battery voltage.Check connections. Check generator set battery. See Figure 5-5.
Engine malfunction.Contact an authorized distributor/dealer.
Fault messages displayed on the controllerIdentify and correct the cause of the fault condition. Then reset the controller after a fault shutdown. See Section 2.5.4.
Fault shutdown.Check the controller display for fault messages. See Section 2.5. Correct the fault condition and reset the controller.
Fuel pressure insufficient.Check the fuel supply and valves.
Generator set accidentally startsDisconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Generator set circuit breaker trips repeatedlyContact an authorized distributor/dealer for service.
Generator set in the OFF mode.Press the RUN button to start the engine or press AUTO to allow remote starting.
Generator set stops suddenly.Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if necessary.
Generator thermostat tripped.Check for obstructed air inlets and outlets. Reset the thermostat. See Section 5.5.
Hot engine and exhaust systemDo not work on the generator set until it cools.
Line circuit breaker tripping because of overload.Reduce the load on the generator set.
Line circuit breaker tripping because of short circuit.Contact an authorized distributor/dealer for service.
Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if necessary.
Low output or excessive drop in voltage.Generator set overloaded.Reduce the load.
No AC output.Line circuit breaker in the OFF position.Place the circuit breaker in the ON position.
No fuel.Check fuel valves and fuel supply.
Overcrank shutdown.Reset the controller. If the overcrank fault occurs again, contact an authorized distributor/dealer.
Remote stop command received from a remote switch, ATS, or OnCuerPlus.Check the remote switch position. Check OnCuerPlus.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Air cleaner clogged.Clean and/or replace the air cleaner.
The generator set does not crank.Battery weak or dead.Recharge or replace the battery.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.