PowerZone–DLA Controller

The PowerZone–DLA is a generator-set controller. It is used on generator sets from Generac, including the MLT4060MVD, MLT4200IV and MLT6.

3
Generator sets
Generac
Brand
6–30 kW
Power range
Diesel
Fuel

Generator sets using this controller

3

Engines paired with this controller

3

Troubleshooting

30

Fault codes

CodeMeaningRemedy
Fail to StartFail to Start — engine does not start and run within three starting cycles; LCD screen displays the "Fail to Start" alarmThe starting sequence can be repeated after the starter cools for at least two minutes. Pressing the Stop (O) button will clear the alarm and reset the controller.

Symptoms & remedies

SymptomCauseRemedy
CAN Data FailIndicates failure of the CAN data link to the engine ECU.Check all wiring and termination resistors (if required).
CAN ECU Warning / CAN ECU ShutdownThis indicates a fault condition detected by the engine ECU and transmitted to the controller.
Continuous starting of generator when in AUTO modeCheck that there is no signal present on the Remote Start input. Check configured polarity is correct; Check the mains supply is available and within configured limits
Controller seems to revert to an earlier configurationWhen editing a configuration using the PC software it is vital that the configuration is first read from the controller before editing it. This edited configuration must then be written back to the controller for the changes to take effect; When editing a configuration using the fascia editor, be sure to press the AUTO Mode button to save the change before moving to another item or exiting the fascia editor
Electrical Trip fault operatesCheck relevant switch and wiring of fault indicated on LCD display; Check configuration of input.
Engine runs but the lights do not turn onCheck Warm up timer has timed out; Ensure Inhibit Light Input 1, 2, 3 or 4 are not active on the module inputs; Check connections to the lights; The genset may not take load in MANUAL/START Mode unless there is an active load signal.
Fail to Start is activated after pre-set number of attempts to startCheck wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speed-sensing signal is present on the controller inputs. See engine manual.
Generator fails to start on receipt of Remote Start signal.Check Start Delay timer has timed out; Check signal is on Remote Start input. Confirm correct configuration of input is configured to be used as Remote Start; Check that the oil pressure switch or sensor is indicating low oil pressure to the controller. Depending on configuration, then set does not start if oil pressure is not low.
High Coolant Temperature operates after engine has fired.Check engine temperature; Check switch/sensor and wiring; Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the controller.
High coolant temperature shutdownLow coolant levelAllow engine to cool, then check coolant level in radiator. Add coolant if needed
Incorrect reading on engine gauges — Fail To Stop when engine is at restCheck engine is operating correctly; Check that sensor is compatible with the controller and that the controller configuration is suited to the sensor.
Low Oil Pressure operates after engine has firedCheck engine oil pressure; Check oil pressure switch/sensor and wiring; Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the controller and is correctly configured.
Low oil pressure shutdownLow oil levelCheck oil level. Add oil if necessary
Mast lights off, checking inside control boxLoose lighting connectionsInspect the connections inside the control box.
Mast lights off, checking inside the control boxLoose lighting connectionsInspect the connections inside the control box.
Mast lights off, checking outside the control boxLight fixture is too hotAllow light to cool 10–15 minutes before restarting.
One or more lights do not turn onLight breaker trippedInspect light breakers
Pre-heat inoperativeCheck wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat configuration is correct.
Shutdown fault operatesCheck relevant switch and wiring of fault indicated on LCD display; Check configuration of input.
Starter motor inoperativeCheck wiring to starter solenoid. Check battery supply. Check battery supply is present on the Starter output of module. Ensure oil pressure switch or sensor is indicating the low oil pressure state to the controller.
The lights are flashingDusk-to-dawn sensor adjustment neededAdjust the dusk-to-dawn sensor according to Dusk to Dawn Sensor
Unit cranks but does not startLow fuel levelCheck fuel level in tank. Verify fuel pump operation.
Unit cranks, but will not startLow fuel levelVerify fuel level in tank
Unit is inoperative — Read/Write configuration does not operateCheck the battery and wiring to the unit; Check the DC supply; Check the DC fuse.
Unit shuts downCheck DC supply voltage is not above 35 V or below 9 V; Check the operating temperature is not above 70 °C. Check the DC fuse.
Unit stalls when export power is usedLoad exceeds unit ratingTurn outlet breaker ON and load sense switch OFF, confirm generator output is 60 Hz ± 2 Hz. Reapply load
Unit starts but stumbles and diesLow ambient temperatureVerify if ambient temperature is within unit limits.
Unit starts, but stumbles and diesLow ambient temperatureVerify if ambient temperature is within unit limits
Warning fault operatesCheck relevant switch and wiring of fault indicated on LCD display; Check configuration of input.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.