The Power Zone–DLA (If Equipped) is a generator-set controller. It is used on generator sets from Generac, including the MLT6.
| Code | Meaning |
|---|---|
| 000192 | Engine down |
| Symptom | Cause | Remedy |
|---|---|---|
| Alarms, warnings, and engine Diagnostic Trouble Code (DTC) faults are displayed. | When an alarm occurs, the controller automatically switches to this screen and remains there until the alarm is cleared. The Stop LED also flashes. | |
| Faulty fuel filter | With engine running and lights off, measure voltage and frequency at the GFCI receptacle. Voltage should indicate 120VAC ± 5%, and frequency should indicate 60.7 Hz ± 5%. If frequency and voltage are both low (<114VAC, <58 Hz), replace the fuel filter. | |
| Faulty generator capacitor | Measure the capacitance of the generator capacitor. If measurement is outside rating (as indicated on the capacitor), replace the capacitor. | |
| Faulty thermostat | Contact a GMASD to replace. | |
| Generator output incorrect | Check the incoming voltage to the ballast driver by checking the available voltage on the GFCI receptacle. Incoming voltage should be 120V ± 5V. | If voltage is incorrect, the generator may require service. |
| High coolant temperature shutdown | Low coolant level | Add coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210 °F (99 °C) or more. |
| Incorrect mix/frozen radiator | Thaw the radiator with an external heat source and flush the coolant system with the correct coolant mixture. | |
| Low oil pressure shutdown | Low oil level | Verify oil level on dipstick. Add oil, if needed. |
| Mast lights off, checking inside the control box | Loose lighting connections | Inspect the connections inside the control box. |
| Mast lights off, checking outside the control box | Light fixture is too hot | Allow light to cool 10–15 minutes before restarting. |
| Oil leaking from engine | Inspect the engine for leaks. | |
| Oil pressure switch failure | Refer to OEM engine operator’s manual to identify corrective action. | |
| PAS engaged | Verify PAS is off. | |
| Unit cranks but does not start | Low fuel level | Check fuel level in tank. Verify fuel pump operation. |
| Water pump failure | Contact a GMASD to replace. |
Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.