PCL-001 Controller

The PCL-001 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 36 DGBC, 40 DGBC, 48 DGCA and 51 DGCA.

18
Generator sets
Cummins/Onan
Brand
40–500 kW
Power range
Diesel
Fuel

Generator sets using this controller

18
Cummins/Onan 36 DGBCCummins/Onan 40 DGBCCummins/Onan 48 DGCACummins/Onan 51 DGCACummins/Onan 580 DFHACummins/Onan 59 DGCBCummins/Onan 640 DFHBCummins/Onan 65 DGCBCummins/Onan 66 DGCCCummins/Onan 72 DGCCCummins/Onan 751 DFHCCummins/Onan 76 DGDACummins/Onan 800 DFHDCummins/Onan 95 DGDBCummins/Onan DFE

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
101Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. When ground is removed from this input, the set returns to normal speed and voltage.
102Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
1123Shutdown After Battle Short
1124Delayed Shutdown
1131Battle Short Active
121Speed Signal Lost
1244Engine Normal Shutdown
1245CAN - Engine Shutdown
1246CAN - Unknown Engine Fault
1247CAN - Engine Unannounced Fault
1248CAN - Engine Warning Fault
1311Customer Inputs #1
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
141Oil Pressure Sensor Low
1416Fail To Shut Down
1417Power Down Failure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1434Remote Emergency Stop
1435Low Coolant Temperature
1438Fail to Crank
144Coolant Temperature Sensor High
1442Weak Battery
1443Battery Failed
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146HIGH COOLANT TEMP WARNINGA. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure.
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match
1471Over Current
1472Over Current
151HIGH COOLANT TEMP ALARMA. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair if necessary. d. Reset control and restart after locating and correcting problem.
152LOW COOLANT TEMPA. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low jacket water coolant level and replenish if required. Look for possible coolant leakage points and repair as required.
197COOLANT LEVEL WARNINGA. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem.
212Shutdown lamp lights.Indicates engine has overheated (coolant temperature has risen above the shutdown trip point: 223° F – standby / 215° F – primary) or the coolant level is low. Allow engine to cool down completely before proceeding with the following checks:A. Check coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair or tighten if necessary. d. Reset control and restart after locating and correcting problem. Contact an authorized service center if none of the above.
213The light will display the fault codes (active or inactive) in succession, starting with the most recent. Up to 32 (unacknowledged) fault codes can be stored in control panel memory.
2331Low AC Voltage
2335Excitation Fault
2336Memory Error
234Overspeed
2341High Control Temperature
2342Too Long in Idle
235COOLANT LEVEL ALARMA. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem.
2358High AC Voltage
2967Governor Fault
2968AVR Fault
2969LON Failure
2972Field Overload

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.