The Digital Evolution is a generator-set controller. It is used on generator sets from Generac, including the RD015, RD020, RD030 and RD048.

18
Generator sets
Generac
Brand
8–150 kW
Power range
2
Fuel types

Generator sets using this controller

18

Also fitted to: Generac 006269-0, Generac 006270-0, Generac 006271-0.

Troubleshooting

29

Fault codes

CodeMeaningRemedy
BATTERY PROBLEMWarning activeContact servicing dealer.
CHARGER WARNINGWarning activeContact servicing dealer
F1Open F1 5 amp fuseReplace F1 5 amp fuse if fuse blows again.*
FUSE PROBLEMUnit will not start in AUTO with utility lossCheck ATO 7.5 amp fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.
HIGH TEMPERATUREUnit shuts down during operationCheck ventilation around the intake, exhaust and rear of generator. Contact serving dealer if no obstruction is found.
LOW BATTERYWarning activeClear alarm. From the MAIN menu on the control panel, navigate to the BATTERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
LOW OIL PRESSUREUnit will not start in AUTO with utility lossCheck oil level. Add oil per Owner's Manual. Contact servicing dealer if oil level is correct.
MISWIREUnit will not start in AUTO with utility lossContact servicing dealer.
NOT ACTIVATEDUnit will not start in AUTO with utility lossRefer to activation section in Owner's Manual.
OVERCRANKUnit will not start in AUTO with utility lossClear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact servicing dealer.
OVERLOADUnit shuts down during operationClear alarm and remove household loads from the generator. Put back in AUTO and restart.
OVERSPEEDUnit will not start in AUTO with utility lossContact servicing dealer.
OVERVOLTAGEUnit will not start in AUTO with utility lossContact servicing dealer.
RPM SENSE LOSSUnit was running and shuts down, attempts to restartClear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact servicing dealer to investigate possible fuel issue.
RPM SENSE LOSSUnit will not start in AUTO with utility lossClear alarm. From the MAIN menu on the control panel, navigate to the BATTERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
SERVICE SCHEDULE AWarning activePerform SERVICE SCHEDULE A maintenance; press ENTER to clear.
SERVICE SCHEDULE BWarning activePerform SERVICE SCHEDULE B maintenance; press ENTER to clear.
SERVICE SCHEDULE CWarning activePerform SERVICE SCHEDULE C maintenance; press ENTER to clear.
UNDER VOLTAGEUnit will not start in AUTO with utility lossContact servicing dealer.
UNDERSPEEDUnit will not start in AUTO with utility lossContact servicing dealer.

Symptoms & remedies

SymptomCauseRemedy
The engine cranks but will not startOut of fuelReplenish fuel. Turn on fuel valve.
The engine starts hard and runs roughAir cleaner plugged or damagedCheck/replace air cleaner.
The engine will not crankFuse blownReplace 7.5 amp fuse in generator control panel. Correct short circuit condition if fuse blows again.
The generator is set to OFF, but the engine continues to runDefective keypad*
There is no AC output from the generatorMain line circuit breaker is in the OFF (OPEN) positionReset circuit breaker to ON (CLOSED) position.
There is no transfer to standby after utility source failureDefective transfer switch coil*
Unit consumes large amounts of oilEngine over filled with oilAdjust oil to correct level.
Unit running in AUTO but no power in houseCheck MLCB. Contact servicing dealer if MLCB is in the ON position.
Unit will not start in AUTO with utility lossCheck screen for start delay countdown. If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.