Advanced Digital Features Controller

The Advanced Digital Features is a generator-set controller. It is used on generator sets from Kohler, including the 12 RES and 8.5 RES.

2
Generator sets
Kohler
Brand
7–12 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Generator sets using this controller

2

Engines paired with this controller

2

Troubleshooting

22

Fault codes

CodeMeaningCauseRemedy
AFInput from a customer-supplied switch that closes when the fault is active. The generator set shuts down and will not start when the fault is active (input is grounded).Check the cause of the auxiliary fault.
HBFault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.
HEShutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
LBFault code is displayed if the engine starting battery voltage falls below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.Charge or replace the battery.
LOPShutdown occurs if a low oil pressure condition exists 7 seconds after the engine has reached crank disconnect speed.Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Check for leaks in the lubrication system.Check the oil level and add oil if the level is low.
OCShutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest. The generator set also shuts down after 1 crank attempt if no speed signal is sensed. Shuts down 1 second after the fault is detected.Check the fuel supply, spark plug, and battery. Check for loose connections.Contact an authorized distributor/dealer for service if problem continues.
OFShutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 1 second. This protective becomes active 30 seconds after engine start.Contact an authorized distributor/dealer for service if problem continues.
OSShutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 1 second.Contact an authorized distributor/dealer for service if problem continues.
OUShutdown occurs if the voltage exceeds 120% of the voltage regulator setpoint for more than 1 second.Contact an authorized distributor/dealer for service if problem continues.
UFShutdown occurs when the governed frequency falls 1 Hz below the system’s frequency setpoint for more than 1 second.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UUShutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 1 second. This protective becomes active 30 seconds after engine start.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.

Symptoms & remedies

SymptomCauseRemedy
Accidental startingDisconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Battery short circuitsDisconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Battery short circuits.Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Fuse blows repeatedlyReplace Auxiliary winding fuse (F1). Contact an authorized distributor/dealer if the fuse blows again.
Generator set master switch in the OFF/RESET positionMove generator set master switch to the AUTO or RUN position.
Green LED stays on when the battery is known to be lowOne or more defective or damaged cells.Load test the battery and replace, if necessary.
Neither of the LEDs turn onNo AC power available at the battery charger.Connect AC power or reset the AC breaker on the main panel.
Red LED stays on for more than 24 hoursOne or more defective or damaged cells.Load test the battery and replace, if necessary.
Red and green LEDs stay on for more than 24 hoursOnboard DC systems are drawing between 1.5 and 5 amps.Turn off all DC equipment while charging.
Severe electrical equipment damageWelding on generator setBefore welding on the generator set perform the following steps: (1) Remove the battery cables, negative (-) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery-charging alternator connections. (5) Attach the weld ground connection close to the weld location.
The generator set does not crank.Battery weak or dead, Battery charger fuse blown, Battery connections reversed or poor, Controller fuse (F3) blown, Relay interface board fuse (F2) blownCheck power to the battery charger. Recharge or replace the battery. Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. Check the connections. Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.