Kohler ES799 Troubleshooting

Kohler ES799 troubleshooting: 17 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler ES799 — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

17

Symptoms & remedies

SymptomCauseRemedy
No build-up.L Open circuit between battery and field. l Battery discharged.*Make correct connections. *l Charge battery.
Generator output erratic.L Regulator sensing terminals not connected properly.*Check terminals 5 and 6 (120 V. connection) or terminals 5 and 7 (240 V. connection). *l Correct connections.
Badly worn, dirty or improperly seated brushes.*Replace, clean or reseat brushes.
S1 to terminal t3 on regulator open.*Correct connections.
Dirty commutator.*Clean commutator.
Choke heater circuit failureThe choke valve could ‘stick’ the air cleanerCheck the Ohm value of the resistor with a Volt-Ohmmeter. If faulty and allows higher voltage, it could cause the choke for starting
Cranking contactor C contacts do not close when switch is moved to on positionReplace relay C
Cranking reset trips during crankingReset the reset button--if plant still does not crank, check for open circuit
Insufficient loadA load of 60 watts or more is needed to start automatic plant. A remote switch can be added to test run these plants--check diagrams
Load relay L dirty or open contactsCheck for dirty or open contacts--replace relay if needed
Center tap missing on three wire automatic plantsCheck for loose leads or missing center tap
Starter not engagingDrive pinion may be spinning. Automotive crank plants only
Battery not being charged properlyCheck condition of battery--may be sulfated or have cracked cell. Replace as neededCheck charge switch if left in HAND CRANK position, battery will not be charged
Generator faulty on plants with automotive crankingCheck for faulty DC generator--excessive resistance in R2 resistor. If overcharging occurs, R2 resistance may be too little
No outflow (no exciter voltage-into AC volts)Regulator relay RR could be causing overcharged or undercharged battery--check this after resistor checkCheck contacts of relay CC may not be closing to complete battery charging circuit. Check brushes, AC leads, and AC armature for open circuits
AC voltage but no exciter voltageAC brushes not riding on collector rings--check for sticking or excessively worn brushesCheck for open AC lead. Lift AC brushes and check for open circuit in AC armature
Check field circuit for open shuntOpen field resistor connection

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler ES799: No build-up — what causes it?

Documented causes: L Open circuit between battery and field. l Battery discharged.. See the table for the matching fixes.

Kohler ES799: Generator output erratic — what causes it?

Documented causes: L Regulator sensing terminals not connected properly.. See the table for the matching fixes.

Kohler ES799: Choke heater circuit failure — what causes it?

Documented causes: The choke valve could ‘stick’ the air cleaner. See the table for the matching fixes.