Home TroubleshootingKohler 38RCLB

Kohler 38RCLB Troubleshooting

Kohler 38RCLB troubleshooting: 41 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 38RCLB — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

41

Fault codes

CodeMeaningRemedy
CoolntTemp 0Coolant temperature is extremely high.Check coolant level. Check radiator and fans for obstruction. Contact an authorized distributor/dealer for service and provide the fault code.
CoolntTemp 3The ECM reported a problem with the coolant temperature sensor reading: 3 = high voltage.Contact an authorized distributor/dealer for service and provide the fault code.
CoolntTemp 4The ECM reported a problem with the coolant temperature sensor reading: 4 = low voltage.Contact an authorized distributor/dealer for service and provide the fault code.
CoolntTemp 5The ECM reported a problem with the coolant temperature sensor reading: 5 = open circuit.Contact an authorized distributor/dealer for service and provide the fault code.
Crank LostCrankshaft Position Sensor (CPS) timeout error occurred.Contact an authorized distributor/dealer for service and provide the fault code.
Emerg StopThe emergency stop switch has been activated, or there has been an open circuit in the wiring.Contact an authorized distributor/dealer for service.
Eng Speed HighEngine speed exceeds 115% of the normal running speed for more than 0.3 seconds.Contact an authorized distributor/dealer for service.
Eng Speed LowEngine speed drops below 85% of the normal running speed for more than 3 seconds.Reduce the load by turning off appliances. Contact an authorized distributor/dealer for service.
Exer Not SchExercise Not Scheduled. No exercise has been scheduled on the RDC2 controller.See Section 2.5 for instructions to set the exerciser.
Frequency HighGoverned frequency exceeds 110% of the system’s frequency setpoint for more than 10 seconds.Contact an authorized distributor/dealer for service.
Frequency LowGoverned frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds.Reduce the load by turning off appliances and restart the generator set. Contact an authorized distributor/dealer for service.
TP-6905 4/16Generator set serial number is unavailable.Contact an authorized distributor/dealer for service. See section 3.11.
IAT High 1Engine manifold air temperature is too high.Contact an authorized distributor/dealer for service and provide the fault code.
IAT Volt LoThe ECM reported an Engine Air Temperature/Manifold Absolute Pressure Sensor (TMAP) error.Contact an authorized distributor/dealer for service and provide the fault code.
Lo Crank VltLow cranking voltage. Battery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged.Charge or replace the battery.
Locked RotorNo engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.Check the battery. Check for loose connections. Check for obstruction of alternator or engine. Contact an authorized distributor/dealer for service.
MainPwrOverLMain power overload. An over current fault on the 70 controller power output (short circuit).Check for shorted run relay. Check wiring for short circuits. Contact an authorized distributor/dealer for service.
Maint Req’dEngine maintenance is due.Check the maintenance schedule in the operation manual for tasks such as changing the oil, spark plugs or the air filter.
Not in AutoThe generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.Press AUTO to place the generator set in Automatic mode, when appropriate.
Oil Pres LowThe engine ECM indicates low oil pressure.Note: The low oil pressure shutdown does not protect against low oil level. Check the engine oil level regularly as recommended in Section 4. Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. Check the oil pressure switch and wiring.
Over CrankThree unsuccessful starting attempts.Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized distributor/dealer for service.
PrimLoopOpnIgnition coil 1 voltage is below normal or there is an open circuit.Check the battery voltage. Contact an authorized distributor/dealer for service and provide the fault code.
PrimLoopShtIgnition coil 1 voltage is abnoContact an authorized distributor/dealer for service and provide the fault code.

Symptoms & remedies

SymptomCauseRemedy
ECM warningsContact an authorized distributor/dealer for service and provide the fault code.
Ground Fault WarningCheck customer equipment connected to the PIM.
The generator set does not crank.Battery weak or dead, Battery connections reversed or poor, Blown fuse(s)Recharge or replace the battery, Check the connections, Replace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Air cleaner clogged, Battery weak or dead, Battery connection poor, Spark plug wire connection looseClean and/or replace the air cleaner, Recharge or replace the battery, Clean and tighten the battery connections, Check the spark plug wires
Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if necessary
Fuel pressure insufficient.Check the fuel supply and valves
Engine malfunction.Contact an authorized Kohler distributor/dealer
No AC output.AC circuit breaker in the OFF positionPlace the circuit breaker in the ON position
AC circuit breaker tripping because of overload.Reduce the load on the generator set
AC circuit breaker tripping because of short circuit.Contact an authorized Kohler distributor/dealer for service
Low output or excessive drop in voltage.Generator set overloadedReduce the load
Generator set stops suddenly.Low oil pressure shutdown, Out of fuelCheck for oil leaks. Check the oil level and add oil if necessary, Check fuel supply
Overcrank shutdown.Reset the controller. If the overcrank fault occurs again, contact an authorized Kohler distributor/dealer
Blown fuse(s).Replace the fuse. If the fuse blows again, contact an authorized Kohler distributor/dealer
Overspeed shutdown.Reset the controller. If the overspeed fault occurs again, contact an authorized Kohler distributor/dealer
Generator set is OFF.Press the RUN button to start the engine or press AUTO to allow remote starting
Remote stop command received from a remote switch, ATS, or OnCuer Plus.Check the remote switch position
Fans run after engine shuts downThe fans continue to run for 2 minutes after the engine shuts down to evacuate the engine compartment.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler 38RCLB: The generator set does not crank — what causes it?

Documented causes: Battery weak or dead, Battery connections reversed or poor, Blown fuse(s). See the table for the matching fixes.

Kohler 38RCLB: The generator set cranks but does not start, starts hard, lacks power, or operates erratically — what causes it?

Documented causes: Air cleaner clogged, Battery weak or dead, Battery connection poor, Spark plug wire connection loose. See the table for the matching fixes.

Kohler 38RCLB: No AC output — what causes it?

Documented causes: AC circuit breaker in the OFF position. See the table for the matching fixes.