Home› Troubleshooting›Kohler 38RCL

Kohler 38RCL Troubleshooting

Kohler 38RCL troubleshooting: 5 fault codes and 33 symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 38RCL — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

38

Fault codes

CodeMeaning
F1Fuse F1, 5 amps
F2Fuse F2, ECM 10 amps
M3Fuse M3, battery charging alternator, 70 amps
F4Fuse F4, ignition, 15 amps
F6Fuse F6, starter, 20 amps

Symptoms & remedies

SymptomCauseRemedy
The generator set does not crankBattery weak or deadRecharge or replace the battery.
The generator set does not crankBattery connections reversed or poorCheck the connections.
The generator set does not crankBlown fuse(s)Replace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly.
The generator set does not crankGenerator set is OFFPress the RUN button to start the engine or press AUTO to allow remote starting.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyAir cleaner cloggedClean and/or replace the air cleaner.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyBattery weak or deadRecharge or replace the battery.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyBattery connection poorClean and tighten the battery connections.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallySpark plug wire connection looseCheck the spark plug wires.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyLow oil pressure shutdownCheck for oil leaks. Check the oil level and add oil if necessary.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyFuel pressure insufficientCheck the fuel supply and valves.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyEngine fuse blownReplace the fuse. If the fuse blows again, contact an authorized Kohler distributor/dealer.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyEngine malfunctionContact an authorized Kohler distributor/dealer.
No AC outputAC circuit breaker in the OFF positionPlace the circuit breaker in the ON position.
No AC outputAC circuit breaker tripping because of overloadReduce the load on the generator set.
No AC outputAC circuit breaker tripping because of short circuitContact an authorized Kohler distributor/dealer for service.
No AC outputEngine fuse blownReplace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly.
Low output or excessive drop in voltageGenerator set overloadedReduce the load.
Generator set stops suddenlyLow oil pressure shutdownCheck for oil leaks. Check the oil level and add oil if necessary.
Generator set stops suddenlyOut of fuelCheck fuel supply.
Generator set stops suddenlyOvercrank shutdownReset the controller. If the overcrank fault occurs again, contact an authorized Kohler distributor/dealer.
Generator set stops suddenlyBlown fuse(s)Replace the fuse. If the fuse blows again, contact an authorized Kohler distributor/dealer.
Generator set stops suddenlyOverspeed shutdownReset the controller. If the overspeed fault occurs again, contact an authorized Kohler distributor/dealer.
Generator set stops suddenlyGenerator set is OFFPress the RUN button to start the engine or press AUTO to allow remote starting.
Generator set stops suddenlyRemote stop command received from a remote switch, ATS, or OnCueCheck the remote switch position.
Generator set stops suddenlyEngine malfunctionContact an authorized Kohler distributor/dealer.
Fans run after engine shuts downThe fans continue to run for 2 minutes after the engine shuts down to evacuate the engine compartment.
Controller LCD display is offLow or no battery voltageCheck connections. Check generator set battery. See Figure 5-1.
Controller display backlight is offBacklight turns off after about 1 minute with no activityBacklight will turn on when a button is pressed or the generator set starts.
Loss of communication to accessory modulesBad connectionsCheck wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual.
Loss of communication to accessory modulesLow or no battery voltageCheck battery connections. Check generator set battery. See Figure 5-1.
LCM relays do not operateBad connectionsCheck wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual.
LCM relays do not operateLow or no battery voltageCheck battery connections. Check generator set battery. See Figure 5-1.
Date is flashingController power was disconnected and then reconnectedCheck battery connections. See Figure 5-1. Check utility power connection for the built-in battery charger. Reset the time, date, and exercise schedule. See Section 2.5.7, Setting the Exerciser at Power-Up.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler 38RCL: The generator set cranks but does not start, starts hard, lacks power, or operates erratically — what causes it?

Documented causes: Air cleaner clogged; Battery weak or dead; Battery connection poor; Spark plug wire connection loose. See the table for the matching fixes.

Kohler 38RCL: Generator set stops suddenly — what causes it?

Documented causes: Low oil pressure shutdown; Out of fuel; Overcrank shutdown; Blown fuse(s). See the table for the matching fixes.

Kohler 38RCL: The generator set does not crank — what causes it?

Documented causes: Battery weak or dead; Battery connections reversed or poor; Blown fuse(s); Generator set is OFF. See the table for the matching fixes.