Kohler 22.5ROZ Troubleshooting

Kohler 22.5ROZ troubleshooting: 13 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 22.5ROZ — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

13

Symptoms & remedies

SymptomCauseRemedy
Battery voltage switched to starter (engine not necessarily turning).Lights only during ‘‘on-crank’' cycles.
CR relay coil energized.Deenergizes C relay
1TS contacts in series with CR relay open to stop cranking (or stop unit if started and producing no AC output).The overcrank reset switch must be activated to reset 1TS contacts.
CR relay energized.Initiates cranking, Energizes ignition circuit, Energizes 1TS circuit, Energizes primary field, Energizes hourmeter, Energizes anti-diesel solenoid (Gasoline only), Energizes water valve (city-water cooled only), Energizes choke (Gasoline only), Energizes gas valve (Gasoline only)
SDR relay energized.Locks in SDR relay, Energizes reset lamp, Deenergizes CR coil
Fuse blown.Generator set will stop. Unit will not crank with a blown fuse. If set has stopped due to causes other than lack of fuel, or fault shut-down — check fuse. If blown, replace the fuse and attempt to restart generator set. If the set will not start, or if the fuse blows again, locate and correct the cause.
LAMP TEST button on controller does not flash.If not, push LAMP TEST button on controller. If other lamps do not light, check/replace 3 amp fuse at rear of controller, and/or replace bulbs as needed.
CRK. lamp does not light (voltage not conducted to starter circuit).Replace uni-board. Fix 1CR relay wiring or replace relay. Repeat test.
IGN., CRK., and REG. lamps of Fast Check do not light.Check wiring to 1CR. Replace uni-board. Repeat test.
No or low AC outputBlown fuse on sensing leads V7, V8 and V9; regulator board or SCR module overcurrent condition; exciter field issue; controller issue; stator winding problem; rotor resistance or ground issue.Check for blown fuses. Check controller and exciter field. Inspect stator windings, rotor resistance, and grounding.
Generator Set will stop.3-Amp fuse 'blows'.Check fuse. If blown, replace the fuse and attempt to restart generator set.
Unit will not crank with a blown 15-Amp fuse.If this fuse blows while the generator set is running, the unit will shut down. If set has stopped due to causes other than lack of fuel, or fault shut-down — check fuse. If blown, replace the fuse and attempt to restart generator set.
No or low AC output.Unbalanced stator windings.Check for continuity between 'quick disconnect' point on each brush lead and its adjacent slip ring. Repair or replace assembly if fault is detected.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler 22.5ROZ: No or low AC output — what causes it?

Documented causes: Blown fuse on sensing leads V7, V8 and V9; regulator board or SCR module overcurrent condition; exciter field issue; controller issue; stator winding problem; rotor resistance or ground issue.; Unbalanced stator windings.. See the table for the matching fixes.

Kohler 22.5ROZ: Generator Set will stop — what causes it?

Documented causes: 3-Amp fuse 'blows'.. See the table for the matching fixes.