Kohler 15RMY Troubleshooting

Kohler 15RMY troubleshooting: 67 symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 15RMY — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

67

Symptoms & remedies

SymptomCauseRemedy
No AC output (RY models)Blown fuse on sensing leads V7, V8 or V9 (CSA models)Check and replace fuse
No AC output (RY models)Weak brush springs, loose holder, sticking brushes or improper brush-to-slip ring alignment causing brushes to wear excessively or unevenlyRepair or replace brush assembly
No AC output (RY models)Running short in the rotor (ammeter current increases considerably during separate excitation)Replace rotor
No AC output (RY models)Open rotor (ammeter current drops to zero during separate excitation)Replace rotor
No AC output (RY models)Faulty stator winding (no output on any winding)Repair or replace stator
No AC output (RY models)Fault in Automatic Voltage Regulation (AVR) circuit (output available when separately excited)Check SCR module; check regulator board
No AC output (RY models)Faulty SCR moduleReplace SCR module
No AC output (RY models)Faulty regulator boardReplace regulator board and refer to new board adjustment procedure
No AC output (RZ models)Blown fuse on sensing leads V7, V8 or V9 (CSA models)Check and replace fuse
No AC output (RZ models)No battery voltage across F3 and F4Problem is in controller
No AC output (RZ models)Current at F3 high or lowProblem is in the exciter field
No AC output (RZ models)No output (25-35 volts) at L1, L2, L3, V7, V8, V9, VO and V4Refer to No Output checks
No AC output (RZ models)Fault in Automatic Voltage Regulation (AVR) circuit (output available when separately excited)Check SCR module; check regulator board
No AC output (RZ models)Faulty SCR moduleReplace SCR module
No AC output (RZ models)Faulty regulator boardReplace regulator board and refer to new board adjustment procedure
Generator set will not crankBlown 10 amp fuse inside the controllerReplace the fuse and attempt to restart generator set; if the set will not start or the fuse blows again, locate and correct the cause
Generator set stopsBlown 10 amp fuse inside the controller (short in the wiring)Replace the fuse and attempt to restart generator set; if the set will not start or the fuse blows again, locate and correct the cause
Generator set will not crankBlown 15-amp fuse (protects CR and 1CR relay contacts from overcurrent in the event of a short in the wiring or engine accessories)Locate and correct the cause; replace fuse
Generator set shuts down while runningBlown 15-amp fuse (protects CR and 1CR relay contacts from overcurrent in the event of a short in the wiring or engine accessories)Locate and correct the cause; replace fuse
SWITCH OFF lamp on controller does not flashLamp test not performed; faulty fuse or bulbs; faulty switch or harness connections; faulty uni-boardPush LAMP TEST button on controller; check/replace 3 amp fuse at rear of controller and/or replace bulbs; check switch and harness connections; replace uni-board; repeat test
IGN., CRK. and REG. lamps of Fast Check do not light when Generator Main Switch is moved to TESTWiring to 1CR faulty; faulty uni-boardCheck wiring to 1CR; replace uni-board; repeat test
CRK. lamp alone does not light (voltage not conducted to starter circuit)Faulty uni-board; faulty 1CR relay wiring or relayReplace uni-board; fix 1CR relay wiring or replace relay; repeat test
IGN. or REG. lamps do not lightFaulty uni-board; faulty CR relay wiring or relayReplace uni-board; fix CR relay wiring or replace relay; repeat test
After second cranking cycle IGN., CRK. and REG. lamps do not go out and OVERCRANK lamp plus A.D. and ALARM lamps do not lightFaulty uni-boardReplace uni-board; repeat test
Cyclic cranking does not stop after 45-75 secondsIncorrect adjustment; faulty uni-boardTry adjustment; repeat test; replace uni-board
CRK. lamp does not go out when Fast Check engine switch is moved to RUNFaulty 1CR relay or wiring; faulty uni-boardCheck 1CR relay and wiring; replace uni-board; repeat test
Engine turns over rapidly, exhausts white smoke but does not start (below 40°F)Preheater not usedDepress preheat switch for 15-20 seconds, release and initiate starting procedure
No outputBlown fuse on CSA models (fuses on sensing leads V7, V8 and V9 protect regulator board and SCR module against an overcurrent condition)
No outputFault in the Automatic Voltage Regulation (AVR) circuit (output available when separately excited)
No outputShorted or open rotorReplace rotor
No outputRunning short in the rotor (ammeter current increases considerably when separately excited)Replace rotor
No outputOpen rotor (ammeter current drops to zero when separately excited)Replace rotor
No outputFaulty stator winding (no output from any winding)Repair or replace stator
No outputWeak brush springs, loose holder, sticking brushes or improper brush-to-slip ring alignment causing brushes to wear excessively or unevenlyRepair or replace brush assembly
No outputNo continuity between quick disconnect point on brush lead and its adjacent slip ringRepair or replace assembly
No outputFaulty SCR module (ohmmeter checks indicate faulty SCR module)Replace SCR module
No outputFaulty regulator board (regulator board test indicates faulty regulator board)Replace regulator board and refer to new board adjustment procedure
No output (RZ models)No voltage present across F3 and F4Check controller
No output (RZ models)Current high or low at F3 (ammeter should read 4/10 of 1 amp)Check exciter field
No output (RZ models)No voltage at L1, L2, L3, V7, V8, V9, VO and V4 (should read 25-35 volts)Refer to No Output checks
Generator set stopsBlown 10 amp fuse inside the controller (short develops in the wiring)Replace the fuse and attempt to restart generator set; if the set will not start, or if the fuse blows again, locate and correct the cause
Generator set shuts down while running15-amp fuse blows while the generator set is running
SWITCH OFF lamp on controller does not flashSwitch and harness connectionsCheck switch and harness connections; replace uni-board; repeat test
Other lamps do not light when LAMP TEST button is pushedBlown 3 amp fuse at rear of controller and/or burned out bulbsCheck/replace 3 amp fuse at rear of controller, and/or replace bulbs as needed
IGN., CRK., and REG. lamps of Fast Check do not light (CRK. should light for around 10 seconds)Wiring to 1CRCheck wiring to 1CR; replace uni-board; repeat test
CRK. lamp alone does not light (voltage not conducted to starter circuit)Uni-board or 1CR relay wiring/relayReplace uni-board; fix 1CR relay wiring or replace relay; repeat test
IGN. or REG. lamps do not lightUni-board or CR relay wiring/relayReplace uni-board; fix CR relay wiring or replace relay; repeat test
After second cranking cycle, IGN., CRK. and REG. lamps do not go out and OVERCRANK lamp on controller plus A.D. and ALARM lamps on Fast Check do not lightUni-boardReplace uni-board; repeat test
Cyclic cranking does not stop after 45-75 secondsCranking cycle adjustmentTry adjustment; repeat test; replace uni-board
CRK. lamp does not go out when Fast Check engine switch is moved to RUN1CR relay and wiringCheck 1CR relay and wiring; replace uni-board; repeat test
No outputAny stator winding shows no outputRepair or replace stator
No outputFaulty SCR module (ohmmeter checks 2-5 or SCR test steps 8-10 indicate a fault)Replace SCR module
No outputFaulty regulator board (regulator board test indicates a fault)Replace regulator board and refer to new board adjustment procedure
No output (RZ models)Battery voltage not present across F3 and F4Problem is in controller
No output (RZ models)Current at F3 high or low (should read 4/10 of 1 amp)Problem is in the exciter field
No output (RZ models)No voltage (25-35 volts) at L1, L2, L3, V7, V8, V9, VO and V4Refer to No Output checks
Generator set will not crankBlown 10 amp fuse inside the controller (protects against damage in the event a short develops in the wiring)Replace the fuse and attempt to restart generator set; if the set will not start or the fuse blows again, locate and correct the cause
Generator set will not crankBlown 15-amp fuse (protects the CR and 1CR relay contacts from overcurrent in the event of a short in the wiring or engine accessories)Locate and correct the cause; replace fuse
Generator set stopsBlown 10 amp fuse inside the controller (if set has stopped due to causes other than lack of fuel or fault shut-down)Check fuse; if blown, replace the fuse and attempt to restart generator set; if the set will not start or the fuse blows again, locate and correct the cause
SWITCH OFF lamp on controller does not flashLamp test not performed; other lamps do not lightPush LAMP TEST button on controller; check/replace 3 amp fuse at rear of controller and/or replace bulbs as needed
SWITCH OFF lamp on controller does not flashFuse is good and other lamps light when LAMP TEST button is pushed, but SWITCH OFF lamp does not flashCheck switch and harness connections; replace uni-board; repeat test
IGN., CRK., and REG. lamps of Fast Check do not light when Generator Main Switch is moved to TESTWiring to 1CR faulty or uni-board faultyCheck wiring to 1CR; replace uni-board; repeat test
CRK. lamp alone does not light (voltage not conducted to starter circuit)Uni-board faulty; 1CR relay wiring faulty or relay faultyReplace uni-board; fix 1CR relay wiring or replace relay; repeat test
IGN. or REG. lamps do not lightUni-board faulty; CR relay wiring faulty or relay faultyReplace uni-board; fix CR relay wiring or replace relay; repeat test
After second cranking cycle, IGN., CRK. and REG. lamps do not go out and OVERCRANK lamp on controller plus A.D. and ALARM lamps on Fast Check do not lightUni-board faultyReplace uni-board; repeat test
Cyclic cranking does not stop after 45-75 secondsCranking cycle out of adjustment or uni-board faultyTry adjustment; repeat test; replace uni-board
CRK. lamp does not go out when Fast Check engine switch is moved to RUN1CR relay or wiring faulty; uni-board faultyCheck 1CR relay and wiring; replace uni-board; repeat test

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler 15RMY: No output — what causes it?

Documented causes: Blown fuse on CSA models (fuses on sensing leads V7, V8 and V9 protect regulator board and SCR module against an overcurrent condition); Fault in the Automatic Voltage Regulation (AVR) circuit (output available when separately excited); Shorted or open rotor; Running short in the rotor (ammeter current increases considerably when separately excited). See the table for the matching fixes.

Kohler 15RMY: No AC output (RY models) — what causes it?

Documented causes: Blown fuse on sensing leads V7, V8 or V9 (CSA models); Weak brush springs, loose holder, sticking brushes or improper brush-to-slip ring alignment causing brushes to wear excessively or unevenly; Running short in the rotor (ammeter current increases considerably during separate excitation); Open rotor (ammeter current drops to zero during separate excitation). See the table for the matching fixes.

Kohler 15RMY: No AC output (RZ models) — what causes it?

Documented causes: Blown fuse on sensing leads V7, V8 or V9 (CSA models); No battery voltage across F3 and F4; Current at F3 high or low; No output (25-35 volts) at L1, L2, L3, V7, V8, V9, VO and V4. See the table for the matching fixes.