Generac RD048 Troubleshooting

Generac RD048 troubleshooting: 20 fault codes and 24 symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac RD048 — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

44

Fault codes

CodeMeaningRemedy
F1Open F1 5 amp fuseReplace F1 5 amp fuse if fuse blows again.*
NOT ACTIVATEDUnit will not start in AUTO with utility lossRefer to activation section in Owner's Manual.
HIGH TEMPERATUREUnit shuts down during operationCheck ventilation around the intake, exhaust and rear of generator. Contact serving dealer if no obstruction is found.
OVERLOADUnit shuts down during operationClear alarm and remove household loads from the generator. Put back in AUTO and restart.
RPM SENSE LOSSUnit was running and shuts down, attempts to restartClear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact servicing dealer to investigate possible fuel issue.
LOW OIL PRESSUREUnit will not start in AUTO with utility lossCheck oil level. Add oil per Owner's Manual. Contact servicing dealer if oil level is correct.
RPM SENSE LOSSUnit will not start in AUTO with utility lossClear alarm. From the MAIN menu on the control panel, navigate to the BATTERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
OVERCRANKUnit will not start in AUTO with utility lossClear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact servicing dealer.
FUSE PROBLEMUnit will not start in AUTO with utility lossCheck ATO 7.5 amp fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.
OVERSPEEDUnit will not start in AUTO with utility lossContact servicing dealer.
UNDER VOLTAGEUnit will not start in AUTO with utility lossContact servicing dealer.
UNDERSPEEDUnit will not start in AUTO with utility lossContact servicing dealer.
MISWIREUnit will not start in AUTO with utility lossContact servicing dealer.
OVERVOLTAGEUnit will not start in AUTO with utility lossContact servicing dealer.
LOW BATTERYWarning activeClear alarm. From the MAIN menu on the control panel, navigate to the BATTERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
BATTERY PROBLEMWarning activeContact servicing dealer.
CHARGER WARNINGWarning activeContact servicing dealer
SERVICE SCHEDULE AWarning activePerform SERVICE SCHEDULE A maintenance; press ENTER to clear.
SERVICE SCHEDULE BWarning activePerform SERVICE SCHEDULE B maintenance; press ENTER to clear.
SERVICE SCHEDULE CWarning activePerform SERVICE SCHEDULE C maintenance; press ENTER to clear.

Symptoms & remedies

SymptomCauseRemedy
The engine will not crankFuse blownReplace 7.5 amp fuse in generator control panel. Correct short circuit condition if fuse blows again.
The engine will not crankLoose, corroded or defective battery cablesTighten, clean or replace as necessary.*
The engine will not crankDefective starter contactTighten, clean or replace as necessary.*
The engine will not crankDefective starter motorTighten, clean or replace as necessary.*
The engine will not crankDead BatteryCharge or replace battery.
The engine cranks but will not startOut of fuelReplenish fuel. Turn on fuel valve.
The engine cranks but will not startDefective fuel solenoid*
The engine cranks but will not startDefective fuel system*
The engine cranks but will not startNo fuel to pumpPrime fuel system.*
The engine starts hard and runs roughAir cleaner plugged or damagedCheck/replace air cleaner.
The generator is set to OFF, but the engine continues to runDefective keypad*
The generator is set to OFF, but the engine continues to runDefective control board*
There is no AC output from the generatorMain line circuit breaker is in the OFF (OPEN) positionReset circuit breaker to ON (CLOSED) position.
There is no AC output from the generatorGenerator internal failure*
There is no transfer to standby after utility source failureDefective transfer switch coil*
There is no transfer to standby after utility source failureDefective transfer relay*
There is no transfer to standby after utility source failureTransfer relay circuit open*
There is no transfer to standby after utility source failureDefective control logic board*
Unit consumes large amounts of oilEngine over filled with oilAdjust oil to correct level.
Unit consumes large amounts of oilEngine breather defective*
Unit consumes large amounts of oilIncorrect oil type or viscositySee Engine Oil Recommendations.
Unit consumes large amounts of oilDamaged gasket, seal or hoseCheck for oil leaks.
Unit running in AUTO but no power in houseCheck MLCB. Contact servicing dealer if MLCB is in the ON position.
Unit will not start in AUTO with utility lossCheck screen for start delay countdown. If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Generac RD048: The engine will not crank — what causes it?

Documented causes: Fuse blown; Loose, corroded or defective battery cables; Defective starter contact; Defective starter motor. See the table for the matching fixes.

Generac RD048: The engine cranks but will not start — what causes it?

Documented causes: Out of fuel; Defective fuel solenoid; Defective fuel system; No fuel to pump. See the table for the matching fixes.

Generac RD048: There is no transfer to standby after utility source failure — what causes it?

Documented causes: Defective transfer switch coil; Defective transfer relay; Transfer relay circuit open; Defective control logic board. See the table for the matching fixes.